Corrigo ventilation communication guide Contains the most commonly used variables. From version 3.3.
DISCLAIMER The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no warranties as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to Regin, so that corrections may be made in future editions. The information in this document is subject to change without prior notification.
Table of contents CHAPTER 1 INTRODUCTION ........................................................................................................... 4 Corrigo ventilation ....................................................................................................................... 4 About this manual ....................................................................................................................... 4 Signals .......................................................................
Chapter 1 Introduction Corrigo ventilation Corrigo ventilation is a pre-programmed application for control of an air handling unit. The Corrigo controller can either be used stand-alone or integrated in an existing EXO project, in both cases it is © configured via the display or using the configuration tool E tool on a PC. About this manual This document provides an introduction to communication via Modbus, BACnet and EXOline and contains a list of commonly used signals. This list is found in chapter 3.
Chapter 2 Signal types and functions Signal types All signals accessible from a SCADA system are described further in this document. Signals with a default value are settings that can be changed via a SCADA system. Signals without a default value are actual values which cannot be changed using a SCADA system. EXOL type The EXOL type of signals: R = Real (-3.3E38 - 3.
Supported Modbus functions: 1 = Read Coils 2 = Read Discrete Input 3 = Read Holding Register 4 = Read Input Register 5 = Write Single Coil 6 = Write Single Register 15 = Write Multiple Coils 16 = Write Multiple Registers BACnet type The BACnet type of signals: 10XXX = Read and write binary 20XXX = Read binary 30XXX = Read and write analogue 40XXX = Read analogue 30XXX = Read and write multistate 40XXX = Read multistate (Where XXX = Modbus address) 6 Signal types and functions Communication guide
Chapter 3 Commonly used signals To simplify system integration, a register of commonly used signals is provided below. Please refer to the document Corrigo ventilation variables for EXOline, Modbus and BACnet for a complete list. Default value BACnet EXOL type Signal name Modbus address 3.1 Input Status Function Description VentActual.Cor_ ExtendedRunActi veFull L 8 BV, 20008 Actual/Setpoint Set if extended operation full speed VentActual.
VentSettings.Cor_ RoomSetP R 19 AV, 30019 VentSettings.Cor_ SAFFullspeedPre ssure R 24 VentSettings.Cor_ SAFHalfspeedPre ssure R VentSettings.
Communication guide Modbus address VentSettings.Cor_ AirUnitAutoMode X 368 MSV, 30368 VentSettings.Cor_S upplyPID_Select X 369 VentSettings.Cor_S upplyPID_ManSet R VentSettings.Cor_S AFAutoMode(0) Default value Signal name EXOL type 3.
EXOL type Modbus address VentSettings.Cor_ HeatCoilAutoMode (0) X 377 - VentSettings.Cor_ HeatCoilManual(0) R 378 VentSettings.Cor_E xchCoilAutoMode X VentSettings.
Modbus address X 451 Default value EXOL type VentSettings.Cor_E xternalControl BACnet Signal name MSV, 30451 2 Function Description Manual/Auto External control: Modbus: 0=Extended run full speed 1=External stop 2=No external control 3=External stop with support control BACnet: 1=Extended run full speed 2=External stop 3=No external control 4=External stop with support control 3.4 Input Registers Communication guide R 1 VentActual.Cor_Ef ficiency R 2 Default value VentActual.
VentActual.Cor_Ru nMode X 3 VentActual.Cor_Su pplyAirTemp R VentActual.
Communication guide VentActual.Cor_C O2Sensor R 17 VentActual.Cor_Fr ostprotectionTemp R VentActual.Cor_De IcingTemp Default value EXOL type Modbus address Signal name Description AV, 40017 CO2 CO2 (ppm) 19 AV, 40019 Frost protection Frost protection temp R 21 AV, 40021 Extract air temp/De-icing exchanger De-icing temp exchanger VentActual.Cor_Hu midityRoom R 23 AV, 40023 Humidity Humidity room VentActual.
Appendix Alarm list No.
No. Alarm text 39 Manual Extract Air Fan mode C Extract air fan in manual control 40 Freq.
No.