Chiller | Close Control | Water terminals SyScroll 20 to 35 Air NEW Air Cooled Water Chillers Cooling Only and Heat Pump Engineering Data Manual 20.0 to 33.0 kW 21.0 to 35.
SyScroll 20-35 Air | Key points R410A refrigerant. Simpler refrigerant circuit layout with only one compressor. Great accessibility to internal components for service operations. Aeraulic independence between refrigerant circuit and condensing side. Optimized fin spacing according coil version (CO/HP). New display on external panel allowing the complete control of the unit. Wide operating limits. Low water temperature applications in cooling mode (down to -8 °C).
| SyScroll 20-35 Air Specifications Sy Scroll SIZES S Air - CO HP BC - PH CO = Cooling Only; HP = Heat Pump; BC = Brine Application; Version - = BLN. General The new SyScroll Air air cooled water chillers have been designed and optimized to operate with R410A refrigerant fluid. They are available in cooling only CO and heat pump HP versions. Each version consists of 4 sizes and covers a nominal cooling capacity range from 20.0 to 33.0 kW and a nominal heating capacity range from 21.0 to 35.
SyScroll 20-35 Air | Condenser fans Units are equipped with two 500mm diameter axial fans with profiled, sickle shaped blades designed with bionical know how, optimized full bellmouth with static blades (motor suspension) and short diffusor. They are placed directly in front of the coil in order to increase the air flow and the heat transfer between air and refrigerant. Fan motors have IP54 protection grade, and thermostat protection placed in the bearings. Both fans are equipped with a safety grill.
| SyScroll 20-35 Air Factory-installed option: Coil with blue fins treatment (only HP), Coil with “E-Coating” treatment, Soft starter, Electronic Expansion Valve, Coil guard. Field-installed accessories Compressor jacket, Mechanical Gauge kit, Hydro kit (112 l water tank), Water flow switch, Water pressure switch, In/out valve kit, Remote On/Off control, ModBus protocol kit for BMS, Power factor correction capacitors, Sequencer for up to 4 chillers installation Remote terminal.
SyScroll 20-35 Air | Accessories & Options SyScroll Air Delivery Abbreviation Description & Befenit Sequence phases control Std PHC It allows to check the correct sense R-S-T of electric supply phases for 400/3/50 units. Control circuit transformer 230V/12V Std TRF Voltage transformer to provide correctly the separated voltage to the auxiliary line. Main switch Std Front operated switch-disconnector with direct mounted handle to cut the power Supply Line according CE standards.
| SyScroll 20-35 Air EN 14511-2011 Starting 2012 Campaign Eurovent Certification Company took decision to start certify only performances declared in according severe European Standard EN14511. BEFORE 2012: GROSS PERFORMANCES Before this date all capacity performances are declared, measured and certified by Eurovent, as GROSS performances.
SyScroll 20-35 Air | Refrigerant Flow Diagram - Syscroll 20-35 Air CO ST 2 KM S A AT 1 B S S KM EEV CONTROL F D C L 3 4 6 UNIT CONTROL 5 ELECTRONIC EXPANSION VALVE (OPTIONAL) 7 MECHANICAL EXPANSION VALVE (STANDARD) 3 BT 15 4 N E 5 S N FS 12 HYDROKIT L 13 11 9 10 14 8 13 COMPONENTS 1 Compressor scroll type 2 Air cooled condenser 3 Filter drier 4 Sight glass 5 Expansion valve 6 Plate heat exchanger 7 Pump 8 Drain valve 9 Water buffer tank 10 Water filter (loose) 11 Automati
| SyScroll 20-35 Air Refrigerant Flow Diagram - Syscroll 20-35 Air HP 3 2 KM S A AT 1 I ST BT H EEV CONTROL D ON S B KM S F C L 4 5 8 6 ELECTRONIC EXPANSION VALVE (OPTIONAL) 9 MECHANICAL EXPANSION VALVE (STANDARD) 4 UNIT CONTROL 17 5 6 7 N E S HYDROKIT N FS 14 L 15 13 11 12 16 10 15 COMPONENTS 1 Compressor scroll type 2 Four-way valve 3 Air cooled condenser 4 Biflow filter drier 5 Sight glass 6 Biflow expansion valve 7 Liquid receiver 8 Plate heat exchanger 9 Pump
SyScroll 20-35 Air | Operating Limits Operating limits Syscroll 20-35 Air Model Water Liquid outlet temperature Chilled liquid Brine Temperature spread Maximum operating pressure Water Leaving water temperature Heated liquid Temperature spread Maximum operating pressure Outdoor air Outdoor air temperature (cooling) Outdoor air temperature (heating) Power supply voltage °C +5 to +18 °C -8 / +5 (with glycol and electronic expansion valve); +5/+18 (standard application) K 3 to 7 bar 3 °C
| SyScroll 20-35 Air Performances corrective factors (brine) Unit capacity, absorbed power, brine flow rate, brine pressure drop, have to be corrected according following formula: CORRECTED UNIT CAPACITY QCORRECTED/GLYCOL = QNOMINAL x Kc x KcE,P Where Kc : Capacity corrective factor according to LWT (ΔT = 5 [K]) → refer to Table 1 KcE : Capacity corrective factor according to glycol percentage (ETHYLENE GLYCOL) → refer to Table 2 KcP : Capacity corrective factor according to glycol percentage (PROPYLE
SyScroll 20-35 Air | Table 2 0% 10% 20% 30% 35% 40% Freezing point (*) °C 0 -4 -10 -10 -21 -21 Minimum leaving water temperature allowed °C 6 2 -2 -2 -8 -8 Capacity corrective factor (**) KcE 1 0,995 0,985 0,985 0,963 0,963 Absorbed power corrective factor (**) KiE 1 0,998 0,995 0,995 0,983 0,983 Flow rate corrective factor KfE 1 1,015 1,050 1,050 1,123 1,123 Pressure drop corrective factor (***) KpE 1 1,070 1,160 1,160 1,283 1,283 Ethylene Glycol Perce
| SyScroll 20-35 Air Technical data - SyScroll 20-35 Air CO Model 20 25 30 35 Data @ Eurovent LCP/W/P/C AC conditions (1) Cooling Capacity (2) kW 20,4 23,9 27,7 33,2 Cooling Capacity (3) kW 20,8 24,4 28,2 33,7 Input Power (2) kW 7,12 7,88 9,47 12,0 Input Power (3) kW 6,67 7,41 8,97 11,5 EER 100% (2) kW/kW 2,87 3,03 2,93 2,77 EER 100% (3) kW/kW 3,12 3,29 3,14 2,93 A A A B EUROVENT CLASS EER 75% (3) kW/kW 3,48 3,67 3,59 3,32 EER 50% (3) kW/kW 3,70 3,9
SyScroll 20-35 Air | Technical data - SyScroll 20-35 Air HP Model 20 25 30 35 Data @ Eurovent LCP/W/P/C AC conditions (1) Cooling Capacity (2) kW 19,8 23,4 26,9 32,9 Cooling Capacity (3) kW 20,2 23,9 27,4 33,4 Input Power (2) kW 7,36 8,11 9,77 12,0 Input Power (3) kW 6,91 7,65 9,27 11,5 EER 100% (2) kW/kW 2,69 2,89 2,75 2,74 EER 100% (3) kW/kW 2,92 3,12 2,96 2,90 B A B B EUROVENT CLASS EER 75% (3) kW/kW 3,28 3,53 3,36 3,31 EER 50% (3) kW/kW 3,48 3,76 3
| SyScroll 20-35 Air Electrical Data - SyScroll 20-35 Air Compressor Data 400V/3/50Hz NOMINAL MAXIMUM PNOM-CPS INOM-CPS PMAX-CPS IMAX-CPS FLA ISTARTUP-CPS LRA Size kW A kW A A PFC (NOM) PFC* 20 6,3 12 8,6 16 25 7,1 13 10,2 21 101 0,78 > 0.90 111 0,80 30 8,7 15 11,9 > 0.90 22 118 0,83 35 11,3 19 14,8 > 0.90 31 140 0,85 > 0.
SyScroll 20-35 Air | Cooling Capacities - Syscroll 20-35 Air CO OAT (°C) Model LWT °C 25 SYSCROLL 25 CO SYSCROLL 30 CO SYSCROLL 35 CO 32 35 38 40 42 45 48 50 PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* PCOOL PABS* kW SYSCROLL 20 CO 30 kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 5 22,1 4,87 20,8 5,34 20,2 5,56 19,3 5,90 18,3 6,25 17,6 6,50 16,9 6,78 15,7 7,21 14,5 7,64 13,8 7,92 7 23,3 4,98 2
| SyScroll 20-35 Air Cooling Capacities - Syscroll 20-35 Air HP OAT (°C) Model SYSCROLL 20 HP SYSCROLL 25 HP SYSCROLL 30 HP SYSCROLL 35 HP LWT °C 25 PCOOL 30 PABS* PCOOL 32 PABS* PCOOL 35 PABS* PCOOL 38 PABS* PCOOL 40 PABS* PCOOL 42 PABS* PCOOL 45 PABS* PCOOL 48 PABS* PCOOL PABS* kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 5 21,5 5,11 20,2 5,60 19,6 5,80 18,8 6,13 17,7 6,56 16,9 6,85 16,2 7,10 15,4 7,41 14,5 7,72 7,57 17,1
SyScroll 20-35 Air | Heating Capacities - Syscroll 20-35 Air HP OAT (°C) Model SYSCROLL 20 HP LWT °C -7 PHEAT -5 PABS* PHEAT -3 PABS* PHEAT 0 PABS* PABS* PHEAT PABS* PHEAT 15 PABS* PHEAT PABS* kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW 4,20 15,8 4,21 16,8 4,23 18,4 4,25 21,2 4,30 22,3 4,33 24,2 4,38 27,8 4,49 4,95 35 14,4 4,67 15,3 4,69 16,4 4,72 18,0 4,75 21,0 4,81 22,0 4,83 23,9 4,86 27,4 40 14,3 5,30 15,1 5,31 16,1 5,33 17,8 5,
| SyScroll 20-35 Air Pump Available Static Pressure 220 200 180 P (kPa) 160 20-25 140 30-35 120 100 80 60 40 20 0,00 0,25 0,50 0,75 1,00 1,25 1,75 2,00 2,25 2,50 1,50 1,75 2,00 2,25 2,50 1,50 1,75 2,00 2,25 2,50 1,50 G (l/s) Water Circuit Pressure Drop 70 60 P (kPa) P (kPa) 50 70 40 60 30 50 20-25 30-35 20-25 30-35 20 40 10 30 0 20 0,00 0,25 0,50 0,75 1,00 10 1,25 G (l/s) 0 35 0,50Drop 0,75 Water0,00 Filter*0,25 Pressure 1,00 30 1,25 G (l/s) P (kPa) 25 35
SyScroll 20-35 Air | Dimensions SyScroll 20-35 Air F G F Front view Side view Rear view G E 147 D C 352 426 LIFTø30 1183 A 147 38 352 147 B E A LIFTø30 31 LIFTø30 LIFTø30 31 D C 426 1615 1615 B 147 1183 38 172 172 P1 457 26 508 P3 NOTES A Water inlet ø 1 1/4” MGT B Water outlet ø 1 1/4” MGT C Auxiliary lines D Electrical power supply E Gauge kit (optional) F Main switch G Control keypad/display P4 1441 1477 P2 26 457 508 1441 1477 18 P2 26 18 31 P4 P1 31 P
| SyScroll 20-35 Air Dimensions Hydrokit 20-35 F G Front view Side view Rear view E 1615 B B D C 14775 1183 292 A 860 352 LIFTø30 31 426 2005 10 LIFTø30 A 147 172 38 250 1480 305 D 186 390 C 92 287 P3 P1 P4 60 NOTES A Water inlet ø 1 1/4” MGT B Water outlet ø 1 1/4” MGT C Tank fill ø 1 1/2” MGT D Water drain ø 3/8” MGT 1441 1477 1360 1480 457 509 P2 26 P4 918 P2 60 26 18 P1 457 508 26 P3 26 Top view 31 22
SyScroll 20-35 Air | Weight Distribution Weight distribution Model SYSCROLL 20-35 Air CO SYSCROLL 20-35 Air HP SYSCROLL 20-35 Air CO + Hydrokit SYSCROLL 20-35 Air HP + Hydrokit Size P1 P2 P3 P4 Operating weight Shipping weight kg kg kg kg kg kg P1-P4 coordinates CG coordinates a b x y mm mm mm mm 20 54 59 64 69 248 254 457 1.441 264 680 25 62 65 74 77 279 285 457 1.441 260 676 30 62 66 76 79 283 289 457 1.