Air Conditioning R32 SYSHP MINI SPLIT 06-16 + HYDRO Mini Heat Pump Split Series Engineering Data Manual 7,0 to 14,0 kW 6,35 to 16,0 kW
CONTENTS Part 1 General Information......................................................................................3 Part 2 Engineering Data.........................................................................................19 Part 3 Installation and Field Settings .....................................................................
2
Part 1 General Information 1 Air-to-Water HP Split System ............................................................................4 2 Unit Capacities .................................................................................................6 3 Nomenclature ..................................................................................................7 4 System Design and Unit Selection .....................................................................9 5 Typical Applications.......
1 Air-to-Water HP Split System 1.1 System Schematic Figure 1-1.1: System schematic Hydronic Box Fan Coil Units Under-floor Heating Loops M-Thermal Split outdoor unit Distributor By-pass Valve 3Way Valve Collector Cold Water Inlet DHWTank It is an integrated air-to-water heat pump split system which is one-stop solution for space heating, space cooling and domestic hot water.
1.2 System Configurations It can be configured to run with the electric heater either enabled or disabled and can also be used in conjunction with an auxiliary heat source such as a boiler. The chosen configuration affects the size of heat pump that is required. Three typical configurations are described below. Refer to Figure 1-1.2. Configuration 1: Heat pump only ▪ The heat pump covers the required capacity and no extra heating capacity is necessary.
2 Unit Capacities 2.1 Outdoor unit Table 1-2.
3 Nomenclature 3.
3.
4 System Design and Unit Selection 4.
4.2 Heat Pump Leaving Water Temperature (LWT) Selection The recommended design LTW ranges for different types of heat emitter are: ▪ For floor heating: 30 to 35⁰ C ▪ For fan coil units: 30 to 45⁰ C ▪ For low temperature radiators: 40 to 50⁰ C 4.
5 Typical Applications 5.1 Space Heating Only The room thermostat is used as a switch. When there is a heating request from the room thermostat, the unit operates to achieve the target water temperature set on the user interface. When the room temperature reaches the thermostat’s set temperature, the unit stops. Figure 1-5.
5.2 Space Heating and Domestic Hot Water The room thermostats are not connected to the hydronic box but to a motorized valve. Each room’s temperature is regulated by the motorized valve on its water circuit. Domestic hot water is supplied from the domestic hot water tank connected to the hydronic box. A bypass valve is required. Figure 1-5.
5.3 Space Heating, Space Cooling and Domestic Hot Water Floor heating loops and fan coil units are used for space heating and fan coil units are used for space cooling. Domestic hot water is supplied from the domestic hot water tank connected to the hydronic box. The unit switches to heating or cooling mode according to the temperature detected by the room thermostat. In space cooling mode, the 2-way valve is closed to prevent cold water entering the floor heating loops. Figure 1-5.
5.4 Space Heating and Domestic Hot Water (Bivalent) 5.4.1 Auxiliary heat source provides space heating only Figure 1-5.
5.4.2 Auxiliary heat source provides space heating and domestic hot water Figure 1-5.
5.4.3 Auxiliary heat source provides additional heating If the unit’s outlet temperature is too low, the auxiliary heat source provides additional heating to raise the water temperature to the set temperature. An additional 3-way valve is required. When the unit’s outlet temperature is too low, the 3-way valve is open and the water flows through the auxiliary heat source. When the unit’s outlet temperature is high enough, the 3-way valve is closed. Figure 1-5.
5.5 Space Heating Through Floor Heating Loops and Radiators The floor heating loops and radiators require different operating water temperatures. To achieve these two set points, a mixing station is required. Room thermostats for each zone are optional.With the help of hydronic adapter board(optional), maximum 8 thermostats for 8 rooms are available to control heat pump, which greatly improves the operation convenience. Figure 1-5.7: Space heating through floor heating loops and radiators RAD. 1 RAD.
5.6 Space Heating, Space Cooling and Domestic Hot Water Compatible with Solar Water Heater Floor heating loops and fan coil units are used for space heating and fan coil units are used for space cooling. Domestic hot water is supplied from the domestic hot water tank connected to both the hydronic box and solar water heater. Solar water pump is controlled by Tsolar temperature sensor. Balance tank temperature sensor is used to control on/off of heat pump.
Part 2 Engineering Data 1 Specifications .................................................................................................20 3 Piping Diagrams .............................................................................................27 4 Wiring Diagrams ............................................................................................29 5 Capactiy Tables ..............................................................................................33 6 Operating Limits..
1 Specifications 1.1 Outdoor Unit Table 2-1.1: SYSHP MINI SPLIT 04, 06, 08, 10 specifications1 Model name SYSHP MINI SPLIT ODU 04 Q Compatible hydronic box SYSHP MINI Power supply SPLIT ODU 06 Q kW 4.25 6.20 8.30 10.0 Rated input kW 0.82 1.24 1.60 2.00 5.20 5.00 5.20 5.00 Capacity kW 4.35 6.35 8.20 10.0 Rated input kW 1.14 1.69 2.08 2.63 3.80 3.75 3.95 3.80 COP Heating4 Capacity kW 4.40 6.00 7.50 9.50 Rated input kW 1.49 2.00 2.36 3.06 2.95 3.00 3.18 3.
Table 2-1.1: SYSHP MINI SPLIT 12, 14, 16 Q specifications1 Model name SYSHP MINI SPLIT ODU 12 Q Compatible hydronic box SYSHP MINI Power supply Heating2 V/Ph/Hz 12.1 14.5 16.0 Rated input kW 2.44 3.09 3.56 4.95 4.70 4.50 Capacity kW 12.3 14.2 16.0 Rated input kW 3.24 3.89 4.44 3.80 3.65 3.60 Capacity kW 12.0 13.8 16.0 Rated input kW 3.87 4.60 5.52 3.10 3.00 2.90 COP Cooling5 Capacity kW 12.00 13.50 14.90 Rated input kW 3.00 3.75 4.38 4.00 3.60 3.
Table 2-1.1: SYSHP MINI SPLIT 12, 14, 16 R specifications1 Model name SYSHP MINI SPLIT ODU 12 R Compatible hydronic box SYSHP MINI V/Ph/H Capacity Rated input 12.1 14.5 16.0 kW 2.44 3.09 3.56 4.95 4.70 4.50 Capacity kW 12.3 14.2 16.0 Rated input kW 3.24 3.89 4.44 3.80 3.65 3.60 COP Heating 4 Capacity kW 12.0 13.8 16.0 Rated input kW 3.87 4.60 5.52 3.10 3.00 2.90 COP Cooling5 Capacity kW 12.00 13.50 14.90 Rated input kW 3.00 3.75 4.
1.2 Hydronic Box Table 2-1.
2 Dimensions and Center of Gravity 2.1 Outdoor Unit SYSHP MINI SPLIT ODU 04, 06 Q Figure 2-2.1: SYSHP MINI SPLIT ODU 04, 06 Q dimensions and center of gravity (unit: mm) SYSHP MINI SPLIT ODU 08, 10 Q Figure 2-2.
SYSHP MINI SPLIT ODU 12, 14, 16 Q Figure 2-2.2: SYSHP MINI SPLIT ODU 12, 14, 16 Q dimensions and center of gravity (unit: mm) SYSHP MINI SPLIT ODU 12, 14, 16 R Figure 2-2.
2.2 Hydronic Box Figure 2-2.
3 Piping Diagrams 3.1 Outdoor Unit Figure 2-3.1: Outdoor unit piping diagram Air side heat exchanger Legend 1 Compressor 7 Electronic expansion valve 2.1 Discharge pipe temperature sensor 8 Stop valve (liquid side) 2.2 Outdoor ambient temperature sensor 9 Stop valve (gas side) 2.3 Air side heat exchanger refrigerant outlet temperature sensor 10 Pressure sensor 2.4 Suction pipe temperature sensor 11 Separator 3 4-way valve 12.1 Low pressure switch 4 Air side heat exchanger 12.
3.2 Hydronic Box Figure 2-3.
4 Wiring Diagrams 4.1 Outdoor Unit SYSHP MINI SPLIT ODU 04, 06, 08, 10 Q Figure 2-4.
SYSHP MINI SPLIT ODU 12, 14, 16 Q Figure 2-4.
SYSHP MINI SPLIT ODU 12, 14, 16 R Figure 2-4.
4.2 Hydronic Box SYSHP MINI SPLIT HYDRO 06, 10, 16 Q Figure 2-4.
5 Capactiy Tables 5.1 Heating Capacity Tables (Test standard: EN14511) Table 2-5.1: Heating capacity for SYSHP MINI SPLIT 04 Q DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 2.05 3.09 3.60 4.17 4.92 4.99 5.41 5.99 6.58 6.37 6.03 5.86 5.70 5.78 5.85 6.30 6.57 25 PI 1.18 1.31 1.19 1.22 1.33 1.24 1.07 1.03 0.99 0.95 0.90 0.81 0.72 0.69 0.65 0.58 0.54 COP 1.74 2.36 3.03 3.40 3.69 4.
Table 2-5.2: Heating capacity for SYSHP MINI SPLIT 06 Q DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 2.57 3.64 4.43 5.75 6.55 6.54 6.49 7.04 7.58 7.43 7.17 6.93 6.69 6.74 6.79 7.26 7.54 25 PI 1.49 1.56 1.49 1.69 1.77 1.64 1.34 1.31 1.28 1.21 1.13 0.97 0.80 0.71 0.66 0.64 0.63 COP 1.72 2.34 2.97 3.41 3.71 3.98 4.85 5.37 5.90 6.12 6.35 7.15 8.32 9.53 10.3 11.4 12.0 HC 2.25 3.34 4.
Table 2-5.3: Heating capacity for SYSHP MINI SPLIT 08 Q DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 4.45 5.68 6.90 7.45 7.64 8.05 8.24 8.86 9.51 10.1 9.86 9.65 9.42 9.18 9.55 10.0 10.3 25 PI 1.98 2.03 2.07 2.02 2.03 2.00 1.73 1.49 1.45 1.35 1.12 0.95 0.90 0.83 0.84 0.87 0.84 COP 2.25 2.80 3.34 3.68 3.76 4.02 4.77 5.95 6.54 7.44 8.79 10.1 10.4 11.0 11.3 11.6 12.3 HC 4.00 5.09 6.
Table 2-5.4: Heating capacity for SYSHP MINI SPLIT 10 Q DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 4.68 5.98 7.26 8.37 8.72 8.80 9.03 9.94 10.5 11.2 11.4 10.8 9.94 9.77 10.2 10.7 11.0 25 PI 2.06 2.12 2.15 2.33 2.29 2.14 1.83 1.73 1.77 1.59 1.41 1.19 1.04 0.96 0.95 0.93 0.91 COP 2.27 2.82 3.37 3.60 3.81 4.12 4.94 5.75 5.94 7.04 8.10 9.05 9.59 10.2 10.7 11.5 12.0 HC 4.21 5.35 6.
Table 2-5.5: Heating capacity for SYSHP MINI SPLIT 12 Q/R DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 6.03 7.65 8.90 11.0 12.3 12.4 12.5 14.6 15.5 15.0 15.1 14.6 14.4 14.6 15.2 15.7 16.2 25 PI 2.78 3.00 3.12 3.47 3.52 3.33 2.87 2.66 2.57 2.40 1.97 1.66 1.55 1.45 1.39 1.41 1.35 COP 2.17 2.55 2.85 3.17 3.49 3.71 4.35 5.49 6.00 6.22 7.67 8.76 9.31 10.1 10.9 11.1 12.0 HC 6.26 7.
Table 2-5.6: Heating capacity for SYSHP MINI SPLIT 14 Q/R DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 6.60 8.26 9.61 11.9 13.7 13.9 14.3 15.4 16.3 15.5 15.3 14.9 14.9 15.3 16.0 16.2 16.5 25 PI 3.09 3.22 3.40 3.81 4.02 3.78 3.40 2.93 2.81 2.28 2.01 1.78 1.64 1.55 1.45 1.40 1.36 COP 2.14 2.57 2.82 3.12 3.41 3.68 4.21 5.25 5.80 6.81 7.62 8.35 9.08 9.82 11.1 11.6 12.2 HC 6.76 8.
Table 2-5.7: Heating capacity for SYSHP MINI SPLIT 16 Q/R DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 DB -25 -20 -15 -10 -7 -5 0 5 7 10 15 20 25 30 35 40 43 HC 7.69 9.57 11.8 13.4 14.3 14.6 15.1 16.8 17.5 18.0 18.9 16.7 16.2 15.6 16.3 16.9 17.2 25 PI 4.03 3.94 4.37 4.51 4.59 4.27 3.49 3.25 3.16 3.01 2.76 2.08 1.83 1.55 1.50 1.47 1.46 COP 1.91 2.38 2.71 2.97 3.13 3.47 4.33 5.19 5.53 6.02 6.84 8.03 8.86 10.1 10.8 11.5 11.8 HC 7.99 9.
5.2 Cooling Capacity Tables (Test standard: EN14511) Table 2-5.8: SYSHP MINI SPLIT 04 Q cooling capacity Maximum LWT DB 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER -5 / / / / / / 4.76 0.46 10.30 5.47 0.55 10.01 6.09 0.48 12.66 0 / / / / / / 4.54 0.57 8.03 5.25 0.65 8.08 5.87 0.55 10.70 5 / / / / / / 4.04 0.67 6.07 4.75 0.75 6.34 5.37 0.65 8.28 10 / / / / / / 6.06 1.06 5.71 6.44 1.01 6.40 7.11 0.85 8.
Table 2-5.9: SYSHP MINI SPLIT 06 Q cool ing capacity Maximum LWT DB -5 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER / / / / / / 5.27 0.59 8.93 6.38 0.55 11.53 6.77 0.64 10.62 0 / / / / / / 5.05 0.69 7.28 6.16 0.66 9.39 6.55 0.74 8.85 5 / / / / / / 4.55 0.79 5.74 5.66 0.76 7.48 6.05 0.84 7.20 10 / / / / / / 6.32 1.13 5.61 6.90 1.01 6.83 7.45 0.95 7.88 15 / / / 5.89 1.10 5.33 8.09 1.46 5.55 8.
Table 2-5.10: SYSHP MINI SPLIT 08 Q cool ing capacity Maximum LWT DB 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER -5 / / / / / / 6.39 0.63 10.07 8.21 0.76 10.82 8.74 0.71 12.31 0 / / / / / / 6.17 0.71 8.69 7.26 0.74 9.76 7.76 0.70 11.05 5 / / / / / / 5.96 0.82 7.30 6.30 0.72 8.69 6.78 0.69 9.78 10 / / / / / / 6.29 0.74 8.54 7.91 0.84 9.45 8.30 0.79 10.53 15 / / / 5.97 0.87 6.84 7.33 0.99 7.
Table 2-5.11: SYSHP MINI SPLIT 10 Q cooling capacity Maximum LWT DB 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER -5 / / / / / / 6.83 0.69 9.92 8.79 0.82 10.66 9.35 0.77 12.13 0 / / / / / / 6.61 0.77 8.56 7.76 0.81 9.61 8.30 0.76 10.88 5 / / / / / / 6.38 0.89 7.19 6.74 0.79 8.56 7.25 0.75 9.63 10 / / / / / / 6.55 0.75 8.73 8.17 0.80 10.18 8.80 0.86 10.22 15 / / / 6.30 1.07 5.89 7.61 1.03 7.35 9.
Table 2-5.12: SYSHP MINI SPLIT 12 Q/R cooling capacity Maximum LWT DB -5 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER / / / / / / 9.55 1.27 7.50 10.39 1.41 7.37 11.39 1.36 8.35 7.92 0 / / / / / / 9.33 1.57 5.93 10.90 1.49 7.32 11.89 1.50 5 / / / / / / 9.12 1.71 5.32 11.41 1.57 7.27 12.38 1.64 7.57 10 / / / / / / 10.81 2.05 5.27 13.14 1.92 6.85 14.18 1.94 7.32 15 / / / 10.51 2.32 4.53 12.50 2.33 5.
Table 2-5.13: SYSHP MINI SPLIT 14 Q/R cooling capacity Maximum LWT DB -5 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER / / / / / / 10.0 1.32 7.57 10.9 1.47 7.44 12.0 1.42 8.43 0 / / / / / / 9.80 1.67 5.87 11.4 1.58 7.24 12.5 1.59 7.84 5 / / / / / / 9.57 1.76 5.44 12.0 1.61 7.43 13.0 1.68 7.73 10 / / / / / / 11.3 2.18 5.21 13.1 1.92 6.85 14.2 1.94 7.32 15 / / / 11.0 2.32 4.60 13.1 2.32 5.45 15.
Table 2-5.14: SYSHP MINI SPLIT 16 Q/R cooling capacity Maximum LWT DB -5 5 10 15 20 25 CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER / / / / / / 10.0 1.32 7.57 10.9 1.47 7.44 12.0 1.42 8.43 0 / / / / / / 9.80 1.67 5.87 11.4 1.58 7.24 12.5 1.59 7.84 5 / / / / / / 9.57 1.76 5.44 12.0 1.61 7.43 13.0 1.68 7.73 10 / / / / / / 11.3 2.18 5.21 13.1 1.92 6.85 14.2 1.94 7.32 15 / / / 11.4 2.43 4.67 13.5 2.44 5.53 16.
6 Operating Limits Figure 2-6.1: Heating operating limits1 Figure 2-6.2: Cooling operating limits Figure 2-6.3: Domestic hot water operating limits1 Abbreviations: T4: Outdoor temperature (°C) T1: Leaving water temperature (°C) Notes: 1. If IBH/AHS setting is valid, only IBH/AHS turns on; If IBH/AHS setting is invalid, only heat pump turns on 2. Water flow temperature drop or rise interval 3.
7 Hydronic Performance Provide outside pressure (KPa) Figure 2-7.1: SYSHP MINI SPLIT HYDRO 06, 10 Q hydronic performance Water flow (m3/h) Provide outside pressure (KPa) Figure 2-7.
8 Sound Levels 8.1 Overall Table 2-8.1: Sound pressure levels1 Model name dB SYSHP MINI SPLIT ODU 04 Q 44 SYSHP MINI SPLIT ODU 06 Q 45 SYSHP MINI SPLIT ODU 08 Q 46 SYSHP MINI SPLIT ODU 10 Q 49 SYSHP MINI SPLIT ODU 12 Q 50 SYSHP MINI SPLIT ODU 14 Q 51 SYSHP MINI SPLIT ODU 16 Q 55 SYSHP MINI SPLIT ODU 12 R 50 SYSHP MINI SPLIT ODU 14 R 51 SYSHP MINI SPLIT ODU 16 R 55 Notes: 1.
8.2 Octave Band Levels Figure 2-8.2: SYSHP MINI SPLIT ODU 04 Q octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C Outdoor air temperature 35⁰C DB; EWT 23⁰C, LWT 18⁰C Octave band center frequency (Hz) Figure 2-8.
Figure 2-8.4: SYSHP MINI SPLIT ODU 08 Q octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C Outdoor air temperature 35⁰C DB; EWT 23⁰C, LWT 18⁰C Octave band center frequency (Hz) Figure 2-8.5: SYSHP MINI SPLIT ODU 10 Q octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.
Figure 2-8.5: SYSHP MINI SPLIT ODU 12 Q octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C Outdoor air temperature 35⁰C DB; EWT 23⁰C, LWT 18⁰C Octave band center frequency (Hz) Figure 2-8.5: SYSHP MINI SPLIT ODU 14 Q octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.
Figure 2-8.5: SYSHP MINI SPLIT ODU 12 R octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰ Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C Outdoor air temperature 35⁰C DB; EWT 23⁰C, LWT 18⁰C Octave band center frequency (Hz) Figure 2-8.5: SYSHP MINI SPLIT ODU 14 R octave band levels Octave band sound pressure level ( dB(A) Outdoor air temperature 7⁰C DB, 85% R.H.
9 Accessories 9.1 Outdoor Unit Table 2-9.1: Outdoor unit accessories Name Shape Quantity Outdoor unit installation and owner’s manual 1 Technical data manual 1 Water outlet connection pipe assembly 1 Energy lable 1 9.2 Hydronic Box Table 2-9.
Part 3 Installation and Field Settings 1 Preface to Part 3 .............................................................................................56 3 Refrigerant Pipework .....................................................................................65 4 Water Pipework .............................................................................................78 6 DIP Switch Settings .........................................................................................
1 Preface to Part 3 1.1 Notes for Installers Boxes The information contained in this Engineering Data Book may primarily be of use during the system design stage of a Air‐to‐Water Heat Pump Split project. Additional important information which may primarily be of use during field installation has been placed in boxes, such as the example below, titled “Notes for installers”.
2 Installation 2.1 Acceptance and Unpacking Notes for installers ▪ When units are delivered check whether any damage occurred during shipment. If there is damage to the surface or outside of a unit, submit a written report to the shipping company. ▪ Check that the model, specifications and quantity of the units delivered are as ordered. ▪ Check that all accessories ordered have been included. Retain the Owner’s Manual for future reference. 2.
2.3 Outdoor unit 2.3.1 Placement Considerations Placement of the outdoor unit should take account of the following considerations: ▪ Outdoor units should not be exposed to direct radiation from a high-temperature heat source. ▪ Outdoor units should not be installed in positions where dust or dirt may affect heat exchangers. ▪ Outdoor units should not be installed in locations where exposure to oil or to corrosive or harmful gases, such as acidic or alkaline gases, may occur.
▪ Fix the unit securely to foundation by means of the Φ10 expansion bolt. It is best to screw in the foundation bolts until their length is 20 mm from the foundation surface. Figure 3-2.3: Outdoor unit fixing Φ10 Expansion bolt Rubber shocking proof mat Solid ground or roofing Concrete basement h≥100mm (unit: mm) 2.3.
Figure 3-2.5: 8-16kW models drainage hole Drain hole This drain hole is covered by rubber plug. If the small drain hole can not meet the drainage requirements, the big drain hole can be used at the same time. 2.3.7 Transportation support For 12/14/16kW model, there is a transportation support which is used to protect tubes from breaking during transportation and this support should be taken off before turning on the heat pump. Figure 3-2.6: 12-16kW models 2.3.
Stacked installation Figure 3-2.8: Installation with obstacles in front of the unit Table 3-2.1: Minimum spacing from obstacles in front of the unit Model name A (mm) All models 4‐16kW 2000 Figure 3-2.9: Installation with obstacles behind the unit Installation in Rows Figure 3-2.
Table 3-2.2: Single row installation spacing requirements Model name A (mm) B1 (mm) B2 (mm) C (mm) All models 4‐16kW ≥3000 ≥2000 ≥150 ≥600 Figure 3-2.11: Multi-row installation Table 3-2.
2.4 Hydronic box 2.4.1 Placement Considerations ▪ Hydronic box should be installed in positions that are as close as possible to the heat emitters. ▪ Hydronic box should be installed in positions that are sufficiently close to the desired position of the wired controller that the controller’s wiring length limitation will not be exceeded.
2.4.3 Service space requirement The service space requirements refer to Figure 3-2.15. Figure 3-2.15: Service space requirement (unit:mm) 2.4.4 Drainage The drainage connections of hydronic box refer to Figure 3-2.16. Figure 3-2.
3 Refrigerant Pipework 3.1 Permitted Piping Length and Level Difference The piping length and level difference limitations that apply are summarized in Table 3-3.1. Before installation, it is necessary to check if the piping length and height difference are meeting the requirements. Table 3-3.1: Permitted Piping Length and Level Difference Models 4-16kW Max. piping length 30m Max. difference in height 20m Figure 3-3.1: Connect method Outdoor Unit Indoor Unit max.
3.3 Procedure and Principles 3.3.1 Installation procedure Notes for installers Installation of the refrigerant piping system should proceed in the following order: Pipe insulation Pipe brazing and installation Pipe flushing Gas tightness test Joint insulation Vacuum drying Note: Pipe flushing should be performed once the brazed connections have been completed with the exception of the final connections to the indoor units.
3.4 Storing Copper Piping 3.4.1 Pipe delivery, storage and sealing Notes for installers ▪ Ensure that piping does not get bent or deformed during delivery or whilst stored. ▪ On construction sites store piping in a designated location. ▪ To prevent dust or moisture entering, piping should be kept sealed whilst in storage and until it is about to be connected. If piping is to be used soon, seal the openings with plugs or adhesive tape.
3.5.3 Expanding copper piping ends Notes for installers ▪ Ends of copper piping can be expanded so that another length of piping can be inserted and the joint brazed. ▪ Insert the expanding head of the pipe expander into the pipe. After completing pipe expansion, rotate the copper pipe a few degrees to rectify the straight line mark left by the expanding head. Caution ▪ Ensure that the expanded section of piping is smooth and even. Remove any burrs that remain after cutting. Figure 3-3.
3.5.5 Bending piping Bending copper piping reduces the number of brazed joints required and can improve quality and save material. Notes for installers ▪ Piping bending methods ▪ Hand bending is suitable for thin copper piping (Ф6. 35mm - Ф12. 7mm). ▪ Mechanical bending (using a bending spring, manual bending machine or powered bending machine) is suitable for a wide range of diameters (Ф6. 35mm - Ф54.0mm). Figure 3-3.
3.7 Brazing Care must be taken to prevent oxide forming on the inside of copper piping during brazing. The presence of oxide in a refrigerant system adversely affects the operation of valves and compressors, potentially leading to low efficiency or even compressor failure. To prevent oxidation, during brazing nitrogen should be flowed through the refrigerant piping.
… box continued from previous page Piping orientation during brazing Brazing should be conducted downwards or horizontally to avoid filler leakage. Figure 3-3.7: Piping orientation during brazing Braizing Braizing Braizing Piping overlap during brazing Table 3-3.5 specifies the minimum permissible piping overlap and the range of permissible gap sizes for brazed joints on piping of different diameters. Refer also to Figure 3-3.8. Figure 3-3.
3.8 Pipe Flushing 3.8.1 Purpose To remove dust, other particles and moisture, which could cause compressor malfunction if not flushed out before the system is run, the refrigerant piping should be flushed using nitrogen. As described in Part 3, 3.3.1 “Installation procedure”, pipe flushing should be performed once the piping connections have been completed with the exception of the final connections to the hydronic box.
3.9 Gastightness Test 3.9.1 Purpose To prevent faults caused by refrigerant leakage, a gastightness test should be performed before system commissioning. 3.9.2 Procedure Notes for installers Warning Only dry nitrogen should be used for gastightness testing. Oxygen, air, flammable gases and toxic gases must not be used for gastightness testing. Use of such gases may result in fire or explosion.
3.9.3 Leak detection Notes for installers The general methods for identifying the source of a leak are as follows: 1. Audio detection: relatively large leaks are audible. 2. Touch detection: place your hand at joints to feel for escaping gas. 3. Soapy water detection: small leaks can be detected by the formation of bubbles when soapy water is applied to a joint. Figure 3-3.
3.10.2 Procedure Notes for installers During vacuum drying, a vacuum pump is used to lower the pressure in the piping to the extent that any moisture present evaporates. At 5mmHg (755mmHg below typical atmospheric pressure) the boiling point of water is 0°C. Therefore a vacuum pump capable of maintaining a pressure of -755mmHg or lower should be used. Using a vacuum pump with a discharge in excess of 4L/s and a precision level of 0.02mmHg is recommended.
3.11 Charging Refrigerant 3.11.1 Calculating additional refrigerant charge Calculate the added refrigerant according to the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit connection. If the length of the liquid side pipe is less than 15 meters it is no need to add more refrigerant, so calculating the added refrigerant the length of the liquid side pipe must subtract 15 meters. Table 3-3.
… box continued from previous page Step 4 ▪ Open the three valves on the pressure gauge to begin charging refrigerant. ▪ When the amount charged reaches R (kg), close the three valves. If the amount charged has not reached R (kg) but no additional refrigerant can be charged, close the three valves on the pressure gauge, run the outdoor unit in cooling mode, and then open the yellow and blue valves.
4 Water Pipework 4.1 Water Circuit Checks Hydronic box are equipped with a water inlet and outlet for connection to a water circuit. Heat Pump Split units should only be connected to closed water circuits. Connection to an open water circuit would lead to excessive corrosion of the water piping. Only materials complying with all applicable legislation should be used. Before continuing installation of the unit, check the following: ▪ ▪ ▪ ▪ ▪ ▪ The maximum water pressure ≤ 3 bar.
4.3 Water Circuit Connection Water connections must be made correctly in accordance with the labels on the hydronic box, with respect to the water inlet and water outlet. If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit: ▪ Use clean pipes only. ▪ Hold the pipe end downwards when removing burrs ▪ Cover the pipe end when inserting it through a wall to prevent dust and dirt entering.
Uninhibited glycol will turn acidic under the influence of oxygen. This process is accelerated by presence of copper and at higher temperatures. The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe damage to the system. It is of extreme importance: ▪ That the water treatment is correctly executed by a qualified water specialist. ▪ That a glycol with corrosion inhibitors is selected to counteract acids formed by the oxidation of glycols.
5 Electrical Wiring 5.1 General Notes for installers Caution ▪ All installation and wiring must be carried out by competent and suitably qualified, certified and accredited professionals and in accordance with all applicable legislation. ▪ Electrical systems should be grounded in accordance with all applicable legislation. ▪ Overcurrent circuit breakers and residual-current circuit breakers (ground fault circuit interrupters) should be used in accordance with all applicable legislation.
5.4 Wiring Overview Figure 3-5.
Table 3-5.
6 DIP Switch Settings DIP switch S1,S2 is located on the hydraulic module main control board and allows configuration of additional heating source thermistor installation, the second inner backup heater installation, etc. Refer to Table 3-6.1 and to the Heat Pump Split Service Manual, Part 4, 2.2 “Main PCB for Hydronic System”. Table 3-6.
8 User Interface Field Settings 8.1 Introduction During installation, the Heat Pump settings and parameters should be configured by the installer to suit the installation configuration, climate conditions and end-user preferences. The relevant settings are accessible and programmable through the FOR SERVICEMAN menu on the Heat Pump user interface. The user interface menus and settings can be navigated using the user interface’s touch-sensitive keys, as detailed in Table 3-8.1. Figure 3-8.
8.
8.3 FOR SERVICEMAN Menu FOR SERVICEMAN allows installers to input the system configuration and set the system parameters. To enter FOR SERVICEMAN, go to MENU > FOR SERVICEMAN. Figure 3-8.2: FOR SERVICEMAN password screen Enter the password, using ◄ ► to navigate between digits and using ▼ ▲ to adjust the numerical values, and then press OK. The password is 234. Refer to Figure 3-8.2 Then the following pages will be displayed after putting the password. Refer to Figure 3-8.3 Figure 3-8.
Only when the space heating/cooling is OFF will the heat pump operate to heat domestic water. DHW PUMP sets whether or not the DHW pump is controlled by the Heat Pump Split unit. If the DHW pump is to be controlled by the Heat Pump Split, select YES. If the DHW pump is not to be controlled by the Heat Pump Split unit, select NON. DHW PUMP PRIORITY TIME SET set the operation time of DHW during DHW PRIORITY mode.
t_INTERVAL_DHW sets the DHW mode compressor re-start delay. When the compressor stops running, it will not re-start until at least t_INTERVAL_DHW minutes have elapsed. dT5_TBH_OFF sets the temperature difference between the DHW set temperature (T5S) and the DHW tank water temperature (T5) below which the immersion is not used. When T5 > Min(T5Stop+dT5_TBH_OFF, 65°C), the immersion heater is off. T4_TBH_ON sets the ambient temperature above which the immersion heater will not be used.
PUMP RUNNING TIME sets the length of time the pump runs for at each of the user-specified start times on the DHW PUMP tab on the DOMESTIC HOT WATER (DHW) menu, if TIMER RUNNING is enabled. DHW PUMP DI RUN sets wether or not the DHW pump (field supply) operates during the disinfection mode. 8.5 COOL MODE SETTING Menu MENU > FOR SERVICEMAN > COOL MODE SETTING Figure 3-8.10: COOL MODE SETTING menu In COOL MODE SETTING the following parameters should be set. COOL MODE enables or disables cooling mode.
T1SetC1 sets the temperature 1 of automatic setting curve for cooling mode. T1SetC2 sets the temperature 2 of automatic setting curve for cooling mode. T4C1 sets the ambient temperature 1 of automatic setting curve for cooling mode. T4C2 sets the ambient temperature 2 of automatic setting curve for cooling mode. ZONE1 C-EMISSION sets the emission type of zone1 for cooling mode. ZONE2 C-EMISSION sets the emission type of zone2 for cooling mode. 8.
dTSH sets the temperature difference between the actual room temperature (Ta) and set room temperature (TS) above which the heat pump provides heated water to the space heating terminals. When TS – Ta ≥ dTSH the heat pump provides heated water to the space heating terminals and when Ta ≥ TS the heat pump does not provide heated water to the space heating terminals. Refer to Figure 3-8.23. dTSH is only relevant if YES is selected for ROOM TEMP in the TEMP. TYPE SETTING menu. Refer to Part 3, 8.8 “TEMP.
8.8 TEMP. TYPE SETTING Menu MENU > FOR SERVICEMAN > TEMP. TYPE SETTING Figure 3-8.19: TEMP. TYPE SETTING menu The TEMP. TYPE SETTING is used for selecting whether the water flow temperature or room temperature is used to control the ON/OFF of the heat pump. When ROOM TEMP. is enabled, the target water flow temperature will be calculated from climate-related curves (refer to “9.1 Climate related curves ”).
If set DOUBLE ZONE to YES and set ROOM TEMP. to NON, meanwhile set WATER FLOW TEMP. to YES or NON, the following pages will be displayed. In this case, the setting value of zone 1 is T1S, the setting value of zone 2 is T1S2. Figure 3-8.23: Set DOUBLE ZONE to YES and set ROOM TEMP. to NON; Set WATER FLOW TEMP. to YES or NON Homepage (zone 1) Addition page (zone 2) If set DOUBLE ZONE and ROOM TEMP. to YES, meanwhile set WATER FLOW TEMP. to YES or NON, the following page will be displayed.
8.10 OTHER HEATING SOURCE Menu 8.10.1 OTHER HEATING SOURCE menu overview MENU > FOR SERVICEMAN > OTHER HEATING SOURCE Figure 3-8.26: OTHER HEATING SOURCE menu In OTHER HEATING SOURCE the following parameters should be set. Backup electric heater is optional. dT1_IBH_ON sets the temperature difference between the heat pump’s leaving water set temperature (T1S) and the heat pump’s leaving water temperature (T1) above which the backup electric heater heating element(s) are on.
8.11 HOLIDAY AWAY SETTING Menu MENU > FOR SERVICEMAN > HOLIDAY AWAY SETTING The HOLIDAY AWAY SETTING menu settings are used to set the outlet water temperature to prevent water pipes freezing when away from home in cold weather seasons. In HOLIDAY AWAY SETTING the following parameters should be set. Figure 3-8.29: HOLIDAY AWAY SETTING menu T1S_H.A._H sets the heat pump’s leaving water set temperature for space heating mode when in holiday away mode. T5S_H.A.
8.14 TEST RUN 8.14.1 TEST RUN Menu overview MENU > FOR SERVICEMAN > TEST RUN TEST RUN is used to check that the valves, air purge function, circulation pump, space cooling mode, space heating mode and DHW mode are all operating correctly. Figure 3-8.32: TEST RUN start screen and TEST RUN menu During test run, all buttons except OK are invalid. If you want to turn off the test run, please press OK.
8.14.3 AIR PURGE operation MENU > FOR SERVICEMAN > TEST RUN > AIR PURGE Once installation is complete it is important to run the air purge function to remove any air which may be present in the water piping and which could cause malfunctions during operation. Figure 3-8.35: AIR PURGE operation The AIR PURGE operation is used to remove air from the water piping. Before running AIR PURGE mode, make sure that the air purge valve is open.
8.14.6 HEAT MODE RUNNING operation The HEAT MODE RUNNING operation is used to check the operation of the system in space heating mode. Figure 3-8.38: HEAT MODE RUNNING display During the HEAT MODE RUNNING operation the Heat Pump Split unit leaving water set temperature is 35°C. The current actual leaving water temperature is displayed on the user interface. When the HEAT MODE RUNNING operation starts, the heat pump first runs for 10 mins.
8.15 SPECIAL FUNCTION Figure 3-8.40: Special functions menu 8.15.1 SPECIAL FUNCTION menu overview MENU > FOR SERVICEMAN > SPECIAL FUNCTION SPECIAL FUNCTION is used to pre-heating floor and drying up floor once installation is complete or the first time start up the unit or restart the unit after a long time stop. 8.15.
Figure 3-8.43: Preheating for floor screens 8.15.3 FLOOR DRYING UP MENU > FOR SERVICEMAN > SPECIAL FUNCTION > FLOOR DRYING UP Figure 3-8.44: FLOOR DRYING UP menu For newly-installed under-floor heating systems, floor drying up mode can be used to remove moisture from the floor slab and subfloor to prevent warping or rupture of the floor during floor heating operation.
8.16 AUTO RESTART Figure 3-8.47: AUTO RESTART menu MENU > FOR SERVICEMAN > AUTO RESTART AUTO RESTART sets whether or not the unit re-applies the user interface settings when the power returns following a power failure. Select YES to enable auto restart or NON to disable auto restart. If the auto restart function is enabled, when the power returns following a power failure, the unit re-applies the user interface settings from before the power failure.
8.19 CASCADE SET (Not available for Heat PumpSplit Series) MENU > FOR SERVICEMAN > CASCADE SET Figure 3-8.51:CASCADE SET 8.20 HMI ADDRESS SET MENU > FOR SERVICEMAN > HMI ADDRESS SET Figure 3-8.52: HMI ADDRESS SET HMI SET sets the wired controller is master or slave. (0=MASTER, 1=SLAVE) When HMI SET is set to SLAVE, the controller can only switch the operation mode, turn on or off, set the temperature, and cannot set other parameters and functions. HMI ADDRESS FOR BMS sets the HMI address code for BMS.
9 Operation parameter MENU > OPERATION PARAMETER This menu is for installer or service engineer reviewing the operation parameters. There are nine pages for the operating parameter as following Figure 3-9.
10 Network Configuration Guidelines The wired controller realizes intelligent control with a built-in WIFI module, which receives control signal from the APP. Before connecting the WLAN, please check for it if the router in your environment is active and make sure that the wired controller is well-connected to the wireless signal. When the product is connected to the network, please make sure that the phone is as close as possible to the product. It only supports 2.4GHz band routers at present.
Click on Sign Up and create a new ac have never created an account of MSmartLi before . If you have already create before, login with the email and password. 10.3 Add device and login to home Wi- Fi Click on Add Device to add your Heat Pump Water Heater This page would be displayed. Click on “Ready” .
Select the Central Water Heater Select the Wi-Fi in your home and type in the password for this Wi-Fi The App will automatically find out the controller, here the controller is KJRH-120F Check the Operation Completed and cli “Next” 107
10.4 Wired Controller Setting Go to “MENU”> “WLAN SETTING”> “AP MODE”. Press “OK” to activate the WLAN, refer to Figure 3-8.1. Select YES, press OK to select AP mode. Select AP Mode correspondingly on the mobile device and continue the follow-up settings according to the APP prompts. During the Wireless distribution process, the LCD icon flashes to indicate that the network is being deployed. After the process is completed, the icon will be constantly on. This icon will flash 10.4.
Go Back to the App , it will take some time for the app to finish up Click on “Complete” , once the Account binding is finished 10.4.2 Finishing up It will show the Status as Online.
11 USB Function Guidelines 11.1 Parameters setting transfer between wired controllers Installer can quickly copy the wired controller parameter settings from unit A to unit B via USB disk, which save the time of on-site installation. Steps are as follows: Step 1: Plug U disk into the port of hydronic PCB of A unit. “USb” appears on digital display Wired controller interface automatically changes USB port Step 2: Select “READ SET PARAMETER” and press “OK” button then rate of progress will appear.
11.2 Convenient program upgrade for unit There is no need to carry any heavy equipment but only USB disk can realize program upgrade. Steps are as follows: Step 1: Copy new program in U disk root directory where other files in bin format are not allowed in Step 2: Power on and make sure communication is normal. Step 3: Plug U disk into the port of hydronic PCB.
12 Climate Related Curves The climate related curves can be selected in the user interface, MENU > PRESET TEMPERATURE > WEATHER TEMP. SET. Figure 3-12.1: WEATHER TEMP.SET menu The curves for heating mode and ECO heating mode are the same but the default curve is curve 4 in heating mode, while in ECO mode, the default curve is curve 6. The default curves for cooling mode is curve 4. Once the curve is selected, the leaving water set temperature (T1s) is determined by the outdoor temperature.
Leaving water set temperature (⁰C ) Figure 3-12.3: High temperature curves for heating mode1 Notes: 1. It only has the curves of the high temperature setting for heating, if the high temperature is set for heating. 2. Curve 4 is default in high temperature heating mode and curve 6 is default in ECO mode. Leaving water set temperature (⁰C ) Figure 3-12.4: Low temperature curves for cooling mode1 Notes: 1.
Leaving water set temperature (⁰C ) Figure 3-12.5: High temperature curves for cooling mode1 Notes: 1. It only has the curves of the high temperature setting for cooling, if the high temperature is set for cooling. 2. Curve 4 is default in high temperature cooling mode. Figure 3-12.6: Automatic setting curve for heating mode Figure 3-12.7: Automatic setting curve for cooling mode The setting of T1SETH1, T1SETH2, T4H1, T4H2 refer to Part 3, 8.
13 Error Code Table Table 3-13.
Table 3-13.
Tel. +39 0362 680 1 Fax +39 0362 680 693 www.systemair.com Systemair · EDM SYSHP MINI SPLIT+HYDRO S-2GB/12.21 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.