Hawair 1.8 to 5.5kW Chilled Water Wall Mounted Units Models HAW 007-009-018-022 1.3 to 4.
Hawair Specifications The Hawair chilled water wall mounted units offer several advantages for air-conditioning applications in residential, hotel and small service Controls RC-08A IR remote control supplied with IR version. sectors : Very compact line. Esthetic that blends in with the decor. Silent unit for optimum acoustic comfort. Infrared remote control. Motorized and adjustable discharge louver. Compact and light for easy installation. Washable air filter easily accessible for maintenance.
2 Hawair Technical Data Hawair 2-pipe - With and without IR - Without valve Hawair HAW007 HAW009 HAW018 HAW022 capacities Total cooling capacity (1) - LS W 1340 1490 1710 2790 Total cooling capacity (1) - MS W 1540 1680 2160 3210 Total cooling capacity (1) W 1710 1870 2400 3570 Total cooling capacity (1) - HS W 1730 2180 2810 3780 Total cooling capacity (1) W 1920 2420 3120 4200 Sensible capacity - LS W 1000 1100 1190 1970 Sensible capacity - MS W 1210 1320 167
Hawair Technical Data (continued) Hawair 2-pipe - With IR - With valve Hawair HAW007 HAW009 HAW018 HAW022 capacities Total cooling capacity (1) - LS W - 960 - 2390 Total cooling capacity (1) - MS W - 1200 - 2250 Total cooling capacity (1) - HS W - 1500 - 2810 Sensible capacity - LS W - 680 - 1850 Sensible capacity - MS W - 960 - 1540 Sensible capacity - HS W - 1120 - 2030 Water pressure drop - LS kPa - 31.5 - 84.3 Water pressure drop - MS kPa - 37.4 - 96.
4 Hawair Cooling Capacities Hawair Water in/out 6 / 11 °C 7 / 12 °C 8 / 13 °C 10 / 15 °C Entering air temperature HAW007 HAW009 HAW018 HAW022 Air flow (m3/h) Air flow (m3/h) Air flow (m3/h) Air flow (m3/h) LS MS HS LS MS HS LS MS HS LS MS HS 252 288 306 243 369 459 450 522 581 531 612 729 27 °C Total capcity W 1820 2100 2410 1900 2250 3250 3215 3610 4000 3800 4390 5190 47% Sensible capacity W 1450 1745 1900 1600 1800 2550 2500 2750 3100 2950
Hawair Heating Capacities Hawair Water in/out Entering air temperature 40 °C 19 °C Heating capacity W 45 °C 19 °C Heating capacity 50 °C 19 °C Heating capacity HAW007 HAW009 HAW018 HAW022 Air flow (m3/h) Air flow (m3/h) Air flow (m3/h) Air flow (m3/h) LS MS HS LS MS HS LS MS HS LS MS HS 252 288 306 243 369 459 450 522 581 531 612 729 1090 1250 1450 1050 1200 1890 1950 2150 2450 2250 2550 3000 W 1780 2030 2150 1840 2180 2710 2130 2980 3500 33
6 Hawair Dimensions and Weight B C A Hawair HAW007 HAW009 HAW018 HAW022 A (mm) 845 845 940 940 B (mm) 180 180 200 200 C (mm) 275 275 298 298 Weight (kg) 11 11 13 13
Hawair Notes 7
8 Hawair Notes
Systemair AC SAS · route de Verneuil, 27570 Tillières-sur- Avre · Tél. 02 32 60 61 00 · Fax 02 32 32 55 13 Systemair · EDM HAW-S-2GB/04.16 - Supersedes EDM HAW-S-1GB/09.14 As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos. www.systemair.