Installation, Operation and Maintenance instruction ZRS Smoke gas fan EN
Table of content 1 Introduction .......................................................... 1 1.1 Product description ...................................... 1 1.2 Intended use .............................................. 1 1.3 Document description................................... 1 1.4 Product overview......................................... 1 1.5 Name plate ................................................ 1 1.5.1 Type designation ............................. 2 1.6 Product liability...................
1 Introduction 1.1 Product description The product is not applicable for transportation of air that contains explosive, flammable or aggressive media. The product is not applicable for locations where there is a risk of explosion. The product is a smoke gas fan with an AC motor. 1.3 The product is not supplied with an external speed control or power switch. 1.2 This document contains instructions for installation, operation and maintenance of the product.
Note: 2 Safety The data on the name plate applies to “standard air” that is specified in the standard ISO5801. 2.1 Safety definitions Warnings, cautions and notes are used to point out specially important parts of the manual. 1.5.1 Type designation Warning Product name ZRS Dimension 170 If you do not obey these instructions, there is a risk of death or injury. 180 Motor type 1.
• Read this manual and make sure that you understand the instructions before you do work on the product. • Obey local conditions and laws. • The ventilation contractor and the operator are responsible for correct installation and intended use. • Keep this manual at the location of the product. • Do not install or operate the product if it is defective. • Do not remove or disconnect safety devices. • Make sure that you can read all warning signs and labels on the product when it is installed.
4 Installation 4.1 To do before the installation of the product 2 Cut a hole in the insulation carpet. Make sure that the hole has the same dimension as the inlet cone of the fan. 3 Install the 4 adjustable steering rods in the holes in the bottom plate of the fan. Use the supplied screws and nuts. • Use installation material with fire resistance rating for the installation location. • Examine the packaging for transportation damage and remove the packaging from the product carefully.
4 Push the fan and steering rods into the chimney. It is not necessary to attach the fan with screws in the chimney, the steering rods keeps the fan in position. 5 Electrical connection 5.1 To do before the electrical connection • Make sure that the electrical connection agrees with the product specification on the motor name plate. • Make sure that the environment for electrical connection is clean and dry.
6 Commissioning Caution • If strong vibrations occur during commissioning, immediately increase or decrease the fan speed until the vibrations are decreased. Continuous strong vibrations can cause damage to components. • Do not increase the fan speed to a higher rpm value than the maximum value that is given on the name plate. 7 Operation 7.1 To start a product with an AC motor 1 Set the installed safety switch in the ON position. 2 Install the external speed controller.
8 Maintenance Warning Set the installed safety switch in the OFF position before you do the maintenance unless the instructions tell you differently. Make sure that the safety switch is not accidentally set in the ON position. 8.1 Maintenance schedule The intervals are calculated from continuous operation of the product. Maintenance task Usual operation conditions Each 6 months Each year Unusual operation conditions.
9 Troubleshooting Note: If you cannot find a solution to your problem in this section, speak to Systemair technical support. Problem Cause Solution The fan impeller is not correctly balanced. Speak to Systemair technical support. There is dirt on the fan impeller. Clean the fan impeller carefully. Refer to 8.2 To clean the product page 7. The fan impeller has damages or deformations because the transported air contains aggressive media. Speak to Systemair technical support.
Problem Cause Solution The fan impeller does not turn in the correct direction. Make sure that the electrical connection is correctly done. A phase loss occurred. If the motor is a 3-phase motor, make sure that no phase is missing. Note: This is not applicable for EC motors. The motor is overheated. Thermal contacts, PTC or resistors are released. • Do a check of the motor cooling impeller. • If it is possible, measure the resistance to do a check of the motor winding.
10 Disposal The product follows the WEEE directive. This symbol on the product or the packaging of the product shows that this product is not domestic waste. The product must be recycled at an approved disposal location for electrical and electronic equipment. 11 Warranty For warranty claims, send a written maintenance plan and the commissioning report to Systemair. The warranty is only applicable for these conditions: • The product is correctly installed and operated. • Motor protection is used.
12 Technical data 12.1 Technical data overview Max. temperature of transported air, °C 200 Max. ambient temperature, °C Refer to the data sheet in the online catalogue at www.systemair.com. Sound pressure, dB IP class Voltage, current, frequency, enclosure class, weight Motor data 12.2 Refer to the name plate. Refer to 1.5 Name plate page 1 for more information. Refer to the motor name plate or the technical documentation from the motor manufacturer.
12.3 Wiring diagrams Abbreviation in wiring diagram Cable colour RD Red YE Yellow BU Blue WH White GN Green BN Brown BK Black GR Grey GY Green/Yellow 12.3.1 Wiring diagrams for ZRS fans ZRS fans 1–phase 230 V ZRS 170–180 N L 12.3.2 GY BK BU BN C Wiring diagrams for speed controller for AC motors Note: The selection of electrical accessories must be done in line with the technical parameters of the product. RE Manual 5-step transformer.
REE — Thyristor REE 1 and REE 2 - Surface mounting or with flush mounting casing included. REE 4 - Surface mounting. N Note: Starting currents must be considered when you select the speed controller type. Products that are used with this speed controller must have a built-in overheating protection and must be designed for thyristor speed control. N L (L) N N N L (L) N M M • L: the connection with cutting function on the speed control. • (L): the connection without cutting function.
A. Relay connection. There is always 230 V between ~ and N when the transformer knob is in one of the positions 1–5. B. Mains supply C. Earth D. Fan E. Thermostat F. Motor protection. If the motor protection is not in use, Tk must be looped together. FRQ5S-E-6A Frequency converter with built-in all-pole sine filter and 5-step switch. FRQ5S-E-6/10A 0 5 N N U1 U1 U2 U2 21 24 D1 A2 E1 TB D1 GND GND BU Digital In 1 22 K2 01 D PE L1 B N PE U1 U2 TB TB M 1~ q C A.
RTRD A 3-phase transformer that controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by using the control knob on the front of the unit. RTRD2-7 N L L RT RT FS FS TK TK A A B N L1 L2 L3 N L1 L2 L3 U V W A 230 V AC PE U W TB TB C D A. If the function is not necessary, the terminals must be bridged B. Contact rating, 230 V AC/maximum 1 A PE M 3~ E 01 V Y/ F C. OFF/ON D. OFF/ON (only by reset) E.
RTRDU Manual 5–step transformer with motor protection — a 3–phase transformer that controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by using the control knob on the front of the unit. RTRDU A 0 B 0 5 15 4 24 3 1 1 2 3 2 3 N L L RT RT FS FS TB TB A A N L1 L2 L3 PE N L1 L2 L3 U V W A 230 V AC max. 1 A 230 V AC U F B 01 TB TB C D A. If the function is not necessary, the terminals must be bridged B.
13 EU Declaration of Conformity We, the manufacturer Manufacturer Systemair Sverige AB Address Industrivägen 3 739 30 Skinnskatteberg Sweden declare under our sole responsibility that the products Type/Model ZRS fulfils the relevant provisions of following directives and standards Machinery Directive 2006/42/EC EN ISO 12100:2010 Safety of machinery – General principles for design - Risk assessment and risk reduction EN ISO 13857:2019 Safety of machinery – Safety distances to prevent hazard zones bei
14 UK Declaration of Conformity We, the manufacturer Manufacturer Systemair Sverige AB Address Industrivägen 3 SE-73930 Skinskatteberg Sweden declare under our sole responsibility that the products Type/Model ZRS fulfils the relevant provisions of following directives and standards Supply of Machinery (Safety) Regulations 2008 EN ISO 12100:2010 Safety of machinery – General principles for design - Risk assessment and risk reduction EN ISO 13857:2019 Safety of machinery – Safety distances to prevent
19
last page Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg +46 222 440 00 mailbox@systemair.com www.systemair.com © Copyright Systemair AB All rights reserved EOE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.