Installing Water heating battery SAVE VTR 700 Installation instructions Document in original language | 211599 · A001 GB
© Copyright Systemair UAB All rights reserved E&OE Systemair UAB reserves the rights to change their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications. Systemair is not liable or bound by the warranty if these instructions are not adhered to during installation or service.
Contents 1 2 3 4 Information....................................................1 Installation.....................................................1 2.1 Open the front hatch...............................1 2.2 Remove cover lids ..................................1 2.3 Mount the water heating battery ...............2 Connections ...................................................3 3.1 Water system........................................3 3.2 Actuator for valve control.........................
Information | 1 Information A water heating battery, frost protection sensor (already mounted) and instruction are included in this kit. After unpacking, check the contents. If any part is missing or damaged, please contact your place of purchase. Note: Size and design of the water heating battery are different for each SAVE model. 2 Installation 2.
2 | Installation 2.3 Mount the water heating battery Fig. 2 The water heating battery 1. Outlet 2. Inlet 3. Remove plug and add the frost protection sensor. Tread seal the sensor. 4. Drain screw 5. Bleed screw Installation 1. Pull out inner and outer rubber grommets. Fig. 3 Remove grommets 2. Remove 3 knobs that will be used to secure water heater in place. 3. Mount the water heater. Be careful not to damage the thin fins on the heater.
Connections | Fig. 4 Install the water heating battery 4. Secure the water heater with three previously removed knobs (pos. 1). Lead the frost protection sensor wires through holes in the compartment walls (pos. 2) to the electrical connections compartment. 5. Connect the frost protection sensor to any free analog input on the main circuit board. Black wire should be connected to ground (GND), red wire to any analog input (for example AI4). 3 Connections 3.
4 | Configuration Max. operating pressure: 0,8 MPa (8 Bar) Important If the water in the water heating battery, then it can burst. If this happens water may leak from the system and cause water damage. If there is a risk of frost the heater must be installed with a circulation pump in a secondary circuit to ensure that a constant flow is achieved in the heater. It's strongly recommended to install an outdoor air damper with a spring return actuator. 3.
Configuration | 3. Activate the actuator. Go to Components menu, select Heater menu and select type as Water. Choose actuator voltage type. Do advanced settings if necessary. 4. Configure connection of the actuator. Go to Service menu. Select Output menu. In next menu select ANALOG tab. Select the analog output to which the actuator is connected. Example if it is connected to AO3 on the connection board, then select ANALOG OUTPUT 3 and select Y1 Heating from the output type list. 5.