SAVE VTR 250/B ceiling mounting kit Installation instructions Document in original language | 211891 · A001 GB
11891 | A001
Contents 1 2 3 4 5 Warnings.......................................................1 Included screws and washers.............................1 Dimensions (mm)............................................1 Installation options ..........................................2 4.1 Fitting with battens.................................2 4.2 Fitting to concrete with threaded rods (accessory, art. no. 134014) .....................3 4.3 Fitting with anti-vibration mount (accessory, art. no. 134009) ....................
Warnings | 1 Warnings Warning • Consider the unit weight when mounting! Important • Beware of sharp edges during mounting and maintenance. Use protective gloves. • This product must only be operated by a person which has suitable knowledge or education within this field or carried out with the supervision of a suitably qualified person. • If cooker hood option is not used, cover the cooker hood duct with an outside fitting end cap.
2 | Installation options 4 Installation options 4.1 Fitting with battens 2x Batten (minimum 45 x 45 mm) Battens (E) should be tightened to the ceiling mounting kit from inside. Battens can be attached from the front and the rear or from both sides with added selftapping screws (A) and washers (B). Tighten battens with a ceiling mounting kit to the main ceiling. These screws are not included. Choose them based on your ceiling structure.
Installation options | 4.2 Fitting to concrete with threaded rods (accessory, art. no. 134014) 4x Drop-in anchor M10 (12 mm x 32 mm) 4x Threaded rod M10 (1 m) 8x Hex flange nut M10 Use a 12 mm drill to make 4 holes in the ceiling with a depth of 40 mm. Distance between holes is shown in dimensions drawing. Install drop-in anchors (1) and attach threaded rods (2). Use hex flange nuts (3) to mount ceiling mounting kit on threaded rods.
4 | Installation options 4.3 Fitting with anti-vibration mount (accessory, art. no. 134009) 2x Anti-vibration bracket 8x Hex bolt M6 x 12 8x M6 washer 8x Hex nut M6 Anti-vibration brackets (1) should be tightened to the ceiling mounting kit from the front and the rear or from both sides with added hex bolts (2) then tightened with washers (3) and hex nuts (4) as shown in the illustration. Tighten anti-vibration brackets with the ceiling mounting kit to the main ceiling.
Mounting the unit | 5 Mounting the unit Important If cooker hood option is not used, cover the cooker hood duct with an outside fitting end cap. Remove screw (1) and washer (2) then pull a lock mechanism to detach side bracket. Repeat this step for the other bracket. Keep removed screws and washers for later use as they will be needed to tighten lock mechanisms back. Loosen ten M5 screws (1) on both sides of the unit.
6 | Mounting the unit Warning Consider the weight of the unit when mounting! Before lifting and hanging the unit make sure that all accessories are installed and cables are lead through the holes on top of ceiling mount kit for easy connection to the connection box which is located on top of the unit. Lift the unit and press it to the ceiling mounting kit. Lock hooks (X) should go through holes in brackets. Pull out the lock mechanism (Y) if needed.
211891 | A001
Phone +370 340 60165 Fax +370 340 60166 www.systemair.com SAVE VTR 250/B ceiling mounting kit · Installation instructions · 211891 · en_GB · 2017-12-14 · A001 Systemair UAB Linų st.