VTR 200 Ceiling mounting kit Installation instructions Document in original language 210647-EN_GB 2016-03-22 A001
Contents 1 Warnings................................................................................................................................... 2 Included items ........................................................................................................................... 3 Dimensions (mm)....................................................................................................................... 4 Installation options ............................................................
1 Warnings Warning • Consider the unit weight when mounting! Important • Beware of sharp edges during mounting and maintenance. Use protective gloves. • This product must only be operated by a person which has suitable knowledge or education within this field or carried out with the supervision of a suitably qualified person.
Installation options 4.1 Fitting with battens 2x Batten (minimum 45 x 45 mm) Battens (F) should be screwed to the ceiling mounting kit from inside of both sides with added self-tapping screws (C) and washers (D). Screw battens with a ceiling mounting kit to the main ceiling. These screws are not included. Choose them based on your ceiling structure. Leave at least a 4 mm gap between ceiling mounting kit and false ceiling to prevent vibration noises.
4.2 Fitting to concrete with threaded rods (accessory, art. no. 134014) 4x Drop-in anchor M10 (12 mm x 32 mm) 4x Threaded rod M10 (1 m) 8x Hex flange nut M10 Use a 12 mm drill to make 4 holes in the ceiling with a depth of 40 mm. Distance between holes is shown in dimensions drawing. Install drop-in anchors (1) and attach threaded rods (2). Use hex flange nuts (3) to mount ceiling mounting kit on threaded rods.
4.3 Fitting with anti-vibration mount (accessory, art. no. 134009) 2x Anti-vibration bracket 6x Hex bolt M6 x 12 6x M6 washer 6x Hex nut M6 Anti-vibration brackets (1) should be screwed to the ceiling mounting kit from both sides with added hex bolts (2) and tightened with washers (3) and hex nuts (4). Screw anti-vibration brackets with a ceiling mounting kit to the main ceiling. Use included screws (C).
5 Mounting the unit Loosen 8 M5 screws (1) on both sides of the unit. Attach side brackets (2) that came with ceiling mounting kit and secure them with the same screws (1) and included washers (E). Warning Consider the unit weight when mounting! The cabling on the top of the unit have to be led through a hole in the ceiling mounting kit. Then lift the unit and press it to the ceiling mounting kit.
Lock hooks (X) should go through brackets. Pull out the lock mechanism (Y) if needed. Screw the locking mechanism on both sides using the screws (A) and washers (B).
lastpage Systemair Sverige AB reserves the right to make changes and improvements to the contents of this manual without prior notice. Systemair UAB Linų st. 101 LT–20174 Ukmergė, LITHUANIA Phone +370 340 60165 Fax +370 340 60166 www.systemair.