Condensate pump Topvex Installation instructions Document in original language | 133579 · A002 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 3 4 General .........................................................1 Installation.....................................................1 2.1 Connecting the tubing .............................1 Wiring...........................................................1 Configuration (Corrigo) .....................................
General | 1 General Silent running centrifugal pump with 1,5 m power cable. To be used if the air handling unit is installed in a tight area with no room for a drain trap. The pump can be installed in a location with some distance to the unit. 2 Installation The pump should be installed in a way that it can be removed easily for cleaning purposes, min. space above the pump is 160 mm. The pump must be mounted in level and the inlet must be below the lowest drain. 2.
2 DIxx Bl R Ref W | Configuration (Corrigo) W=white, Bl=black, R=Red The pump are provided with 1,5 m power cable, connect the cable to main supply. 4 Configuration (Corrigo) Setup a free digital input (DI), configure the digital input as an extra alarm 2, normally open (NO). The alarm text in the display will be shown as Condensate pump. Log on as Administrator code: 3333.