Topvex FC, CAV conversion (Flow control) Installation instructions Document in original language 128300-EN_GB 04-05-2015 A001
Contents 1 Warnings................................................................................................................................... 2 Install the pressure transmitter .................................................................................................... 3 Wiring ....................................................................................................................................... 4 Configuration (Corrigo).......................................................
1 Warnings Danger • Make sure that the Mains supply to the unit is disconnected before performing any maintenance or electrical work! • All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations. • Beware of sharp edges during mounting. 2 Install the pressure transmitter Remove the supply air fan (figure 1). Caution If the unit is already installed in false ceiling, make sure that the fan does not fall down when removing the supply air fan.
Fig. 2 Mount the enclosed CAV pressure transmitter (PTS) in the pre-punched holes (figure 2, pos 1). Pos 2 only used for units with built-in electrical heater e.g. Topvex FC04 EL.
3 Wiring Convert Topvex FC to a CAV unit by connecting CAV pressure transmitter (PTS) to the pre-wired tubes and electrical cables. For units with electrical heater (EL) the tube from the Flow guard (AFS) to the Supply fan (SF) inlet cone must be cut and connected to the new CAV Pressure transmitter (PTS) by the enclosed Y-connector. Terminals in the unit are addressed to following terminals in the actual pressure transmitter (see wiring diagram/wiring chart for actual unit).
4 Configuration (Corrigo) Log on to Administrator level with password 3333.
Sensor setting. Set the adjusted working range for the added CAV pressure transmitter in menu Configuration/Sensor setting. Adjust SAF (supply air fan) and EAF (extract air fan) actual pressure range at 10,0 V. Example Topvex FC02: If pressure transmitter is set to 0...1000 Pa set: 0,0 V: 0,0 Pa and 10,0 V : 1000,0 Pa. Filter factor is not to be changed.
6 Topvex FC External connections Table 1: Connections to external functions Terminal block Description Remark PE Ground N N Earthed neutral (supply voltage) L1 L1 Phase (supply voltage) Used for phase 230V 1~ if the unit has this mains supply 400V 3~ L2 L2 Phase (supply voltage) 400V 3~ L3 L3 Phase (supply voltage) 400V 3~ 1 G Mains supply (Water valve actuator) 24V AC 2 G0 Reference (Water valve actuator mains supply) 24V AC 10 DO ref DO reference G (24V AC) 121 DO 2 Outdo
Connections to external functions cont'd Terminal block 763 DI 6 Description Remark External stop Normally open contact Use terminal 4 as reference 90 Agnd AO Reference neutral 93 AO 3 Control signal, Heating 0–10V DC 94 AO 4 Control signal, Cooling 0–10V DC 1. 2. 3.