Case study ICF

We are very pleased
with the installation. During
the winter half of the year,
the ceiling fans raise the
temperature close to the
floor by 2 - 3 ºC.
Mindaugas Martišius
Managing Director, Systemair LT.
Warm air is lighter than cold air and therefore rises. Consequently, in
premises with high ceilings a cushion of warm air easily forms up under the
ceiling. This overheated air results in large and unnecessary energy losses.
In Systemairs plant in Lithuania, the installation of ceiling fans has ensured
that energy costs are kept down while creating a comfortable working envi-
ronment for the employees.
CASE STUDY Systemair factory, Lithuania
95 ceiling fans
over 7,260 m
2
Systemair is a leading ventilation
company with operations in 49
countries around the world manu-
facturing and marketing high-quality
ventilation products. The Group's
main factory and logistics centre for
smaller housing units is located in
Ukmerge, Lithuania.
The building’s total volume is
15,500 m
2
, divided into manufactur-
ing, warehouse and offices.
Case Study: Systemair Lithuania
Industrial ceiling fan ICF
Significantly reduced energy costs
and improved working environment
Large savings with short payback period
Building footprint: 7,260 m
2
Building height: 8 m
Installed ICF: 95 units
Installation cost: SEK 190,000
Output calculation
Yearly average temperature: 6 °C
Energy price: SEK 1/kWh
The plant is heated by SWH fan heaters
with air curtains installed over all doors
to the exterior. To improve the working
environment for employees and save
energy, 95 ICF ceiling fans were installed.
The ceiling fans force warm air downwards
into the occupied zone, evening out the
temperature difference between the ceiling
and floor.
Thanks to energy-efficient heating
combined with ceiling fans, energy costs
are lower and the work environment has
improved.
Without ceiling fans:
Temperature gradient: 2.5 °C/m
Total energy requirement: 1,246
MWh/year
Annual cost: SEK 1,246,000
With ceiling fans:
0.25 °C/m
1,029 MWh/year
*(including ceiling fans)
SEK1,029,000
Savings: > SEK 200,000/year
Payback period less than 1 year
The calculator is available at www.frico.co.uk and takes into account the area and
height of the building, ventilation and infiltration, R-values and any additional heat
sources. Frico AB is not liable for any errors in the calculation attributable to infor-
mation provided by the customer, the lack of such information, or the use of fictional
standard values.