CAR 15 FORWARD AUTOMATIC 3 2 1 4 5 6 7 8 9 0 REVERSE SE ... 2 GB ...
GB CAR 15 CAR15 ~ 230V~ 1 2 5 L N 1 2 5 Connections: L LF LR N N PE PE PE 1 2 3 4 5 6 7 8 = Phase in. = Regulated voltage to fan motor for forward rotation. (FORWARD) = Regulated voltage to fan motor for backward rotation (REVERSE). = Neutral in. = Neutral out. = Ground for phase in. = Ground for LF or LR out. = Ground for control signals. = Temp. sensor ceiling + (top). = Temp. sensor ceiling - (top). = Temp. sensor room/floor + (bottom). = Temp. sensor room/floor - (bottom).< = 0 to +10VDC in.
CAR 15 Operation: CAR15 adapts the fan speed according to the temperaure difference between two temperature sensors. The room sensor is placed in a representative location in the occupied zone, approx. 0,5 m above the floor level. The ceiling sensor is placed on to the ceiling, preferably higher than the fans, but not directly above. Up to 15 pcs of ceiling fans (Frico ICF) can be connected to the CAR15 .