SYCLOPE COOLTouch® Controller for Cooling tower managements (Part 1) Installation and starting instructions Reference: DOC0484 Rev: 1 Installation and starting instructions
General information Page 2/57 Part of the general documentation ► Part 1: Installation and starting instructions Part 2: General programming instructions Part 3: Communication programming instructions General information: SYCLOPE Electronique 2021® Manual of 25/08/2021 Rev 1 Professional controller for cooling towers. Product line COOLTOUCH® Part 1: Installation and starting instructions (Ref: DOC0484) Editor: SYCLOPE Electronique S.A.S. Z.I.
Contents Page 3/57 Contents I. Generality......................................................................................................................5 1) Scope ................................................................................................................................5 2) FCC conformity...................................................................................................................6 3) Use of the document ...................................................
Contents Page 4/57 1) Main screen display .......................................................................................................... 34 a) The upper banner.................................................................................................... 34 b) Display details of the channels ................................................................................. 37 2) “Detailed” display of a channel ...............................................................................
Generality Page 5/57 I. Generality 1) Scope The range of SYCLOPE COOLTouch® controller you have purchased is a high-tech electronic device for the complete management of cooling tower (air/water coolers) and the risks related to the legionella. Its remarkable adaptability to the various structures of cooling towers enables him to settle in all the difficult cases where the control of the process and the water treatment in a cooling tower are decisive.
Generality Page 6/57 2) FCC conformity The SYCLOPE COOLTouch® controller complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference (2) this device must accept any interference received, including interference that may cause undesired operation FCC Regulations state that unauthorized changes or modifications to this equipment may void the user’s authority to operate it.
Generality Page 7/57 3) Use of the document Please read carefully the entire document before starting the installation and the commissioning of the controller device, in order to ensure the safety of swimmers, users and equipment’s. The information provided in this document must be strictly observed. SYCLOPE Electronique S.A.S. declines all responsibility in cases where failure to comply with the instructions of this documents.
Generality Page 8/57 5) Storage and transport It is important to store and to transport the SYCLOPE COOLTOUCH controller in its original packaging in order to minimize risk of damage. Furthermore, the package must be stored in an environment that is protected against humidity and exposure to chemical products. Environmental conditions for transport and storage: Temperature: -10 °C à 70 °C Air humidity: Maximum of 90% with no condensation 6) Packaging The device is delivered without power cable.
Safety and environmental instructions Page 9/57 II. Safety and environmental instructions Please: Read this manual carefully before the unpacking, the installing or the commissioning of this equipment Take into account all the hazards and of recommended precautionary measures The failure to respect these procedures can result in serious injury to users or damaging the device.
Safety and environmental instructions Page 10/57 Take care when choosing the location for installing the controller! SYCLOPE COOLTouch® controller should not be installed in a hazardous environment and should be protected against splashing with water or chemical products. It should be installed in a dry, well-ventilated and isolated location. Make sure that the chemical sensors used with this controller correspond well to the chemicals used. Refer to the individual technical note of each sensor.
Safety and environmental instructions Page 11/57 5) Disposal and conformity The recyclable packaging of the SYCLOPE COOLTouch® equipment must be disposed of according to current regulations. Elements such as paper, cardboard, plastic or any other recyclable elements must be taken to a suitable sorting centre. According to European directive 2012/19/EC, this symbol means that as of 4 July 2012 electrical appliances cannot be thrown out together with household or industrial waste.
Technical characteristics and functions Page 12/57 III.
Technical characteristics and functions Relay outputs Analog outputs Power output Page 13/57 1 electronic relay output 50mA Max ; 48VAC Max 2 0/4…20 mA analog outputs Max ; 12VDC Max ; 500 Ω 1 24V power output ; 100mA Communication port 1 RS485 communication port 1 Ethernet output Protection of dosing outputs RS485 Ethernet Internal fuse 1 TR5 3,15 A 250 V Time delay fuses RO1 AO1 & AO2 RS485 ETH F2 Save Button cell Type BR2032 Bat1 2) Main functions Main functions Specification(s) Bleed and bioci
Technical characteristics and functions Page 14/57 0 to 2000 mg/l Active chlorine 0,02 to 2 mg/l 0,1 to 10 mg/l 0 to 2000 mg/l Total chlorine 0,01 to 0,5 mg/l 0,02 to 2 mg/l 0,05 to 5 mg/l 0,1 to 10 mg/l 0 to 2000 mg/l Chlorite 0,01 to 0,5 mg/l 0,02 to 2 mg/l 0 to 2000mg/l ClO2 (Chlorine dioxide) 0,01 to 0,5 mg/l 0,02 to 2 mg/l 0,1 to 10 mg/l 0 to 2000 mg/l H2O2 (Peroxide) 0,5 to 50 mg/l 2 to 200 mg/l 20 to 2000 mg/l 0 to 2000 mg/l BCDMH 0,02 to 2 mg/l 0,2 to 10 mg/l 0,4 to 15 mg/l 0 to 2000 mg
Technical characteristics and functions Installation and starting instructions Page 15/57
Installation and connections Page 16/57 IV.
Installation et connections Page 17/57 3) Open / Close transparent door In order to guarantee IP65 class, the transparent door must absolutely be closed after use while ensuring the quality of the closure seal. The case has a closing system with automatic locking as soon as its handling is carried out correctly.
Installation and connections Page 18/57 5) Tightening torque a) Cable gland Max cable section via cable gland. Cable gland tightening torque. 3 x (2-5mm) 1 x (9,4-12mm) 0.7 N.m 2 N.m b) Terminal blocks The tightening torque of the screws of different terminal block is 0.5 N.
Installation and connections Page 19/57 7) Changing the internal fuse of PO1 output SYCLOPE COOLTouch ® has a spare fuse located in position F5, which allows you to quickly replace a fuse if necessary. If you are led to using it, don’t forget to replace it… Cut off the power supply, before changing the fuse! Always use a fuse identical to the original one.
Installation et connections Page 20/57 Fuse F2 (TR5) Locate the fuse to be changed on the lower PCB Remove the fuse to be changed Replace the new fuse Reconnect the flat cable between the cards and reassemble the front panel using the 4 fixing screws. Don’t overtighten because the screws are fixed in the plastic case. Reconnect the flat cable and replace the front panel before switch On. 8) Primary power connections SYCLOPE COOLTouch® has a switch-mode power supply.
Installation and connections Page 21/57 9) Measurement inputs connections SYCLOPE COOLTouch® has ten inputs: 1 Input RI1 RTD isolated for (Pt100 / Pt1000) 1 Input RI2 isolated for conductivity 2 Inputs AI1 & AI2 4-20mA isolated for temperature, chlorine, bromine, etc measure 5 Inputs DI1 to DI5 digital for sensor. 1 Input SI1 serial for UART 5V TTL a) PT100 / Pt1000 input RI1 Connection of the sensor on RI1: Preferably use a shielded coaxial cable.
Installation et connections Page 22/57 c) Isolated analog inputs 4…20mA AI1 & AI2 Controller has 2 isolated analog inputs 4…20mA on which a chlorine, bromine, ozone, hydrogen peroxide, peracetic acid, dissolved oxygen or PHMB sensor can be connected.
Installation et connections Page 23/57 d) Digital inputs DI1 to DI5 Controller has 5 digital inputs on which a tank bottom, flow, R.I.C (Remote Input Control), or another sensor can be connected. 0…10m3/H Customer* • (impulsions) 0…200l/min Flow 0…50l/min 0…20l/min The definition of supported sensors is as follows: • • • (*): The scale of the customer can be defined between 0 et 2000 (L/min, L/H or m3/H) in 4…20mA or impulse input Connection of a R.I.
Installation et connections Page 24/57 Connection of a flowmeter sensor on DI3: Preferably use a two-strand cable. Connect one sensor strand to the DI3 sw (20) connection. Connect the other sensor strand to the DI3 - (21) connection. Tighten the cable gland to seal. e) Serial input SI1 Controller has 1 serial input on which a CTFS sensor can be connected. Connection of a CTFS sensor on SI1: Remove the protective sheath. Strip the wires on 7mm.
Installation et connections Page 25/57 10) Self-powered relays outputs connections PO1 The self-powered PO1 power relay output (Primary supply voltage = Voltage available on P3) can be used for dosing, alarm, timer… PO1 ► Strip the 3 wires of the power cable of the dosing device on 7mm ► Pass the 3-point cable through a cable gland ► Connect the phase on L1 (50) and the neutral on N (51) of the PO1 mains terminal block ► Connect the earth on PE (52) of the PO1 mains terminal block ► Tighten the cable gl
Installation et connections Page 26/57 FO2 ► Use a 2-wire cable with a section appropriate for the voltage and current. ► Remove the protective sheath ► Strip wires on 7mm ► Pass the cable through a cable gland ► Connect a cable on the midpoint COMMUN (45) of the terminal block ► Connect the second cable on the WORK (44) of the terminal block or on the REST (46) depending on the function to be performed ► Tighten the cable gland to seal.
Installation and connections Page 27/57 12) Electronic relay outputs connections RO1 The electronic relay output is mainly dedicated to controlling the dosing pumps in impulse mode. It can also serve as alarm relay or be controlled in timer mode according to your needs. This relay is electronic component to make contact, it is used to drive pumps by their impulse input or to control an external power relay. This relay can switch a maximum voltage of 48 VAC and a current of 50mA.
Installation and connections Page 28/57 13) 4…20mA outputs connections (AO1 to AO2) 4…20mA outputs are used to send information to a building management system or to control a dosing device via a 4…20mA signal. The analog outputs are generative and operate with an internal voltage of 12 VDC. The maximum load is 500Ω. 4…20mA outputs are fully configurable. You can assign any parameter (measured or calculated) in regulation or data transfer mode.
Installation et connections Page 29/57 14) Power supply output connection (PWR) If necessary, chlorine or bromine sensors may be used that require external power. Use a 2-wire cable. Pass the cable through a cable gland Connect the strand + of the alimentation on +24V (17) Connect the strand - of the alimentation on C (18). Tighten the cable gland to seal.
Installation and connections Page 30/57 15) RS485 communication bus connections SYCLOPE COOLTOUCH® has a RS485 communication port to connect it to a computer equipped with a 485 port and a communication software to record the measurement values, alarms and different states of the device. a) Connection to a USB port on a computer Use a 3-wire cable. Pass the cable through a cable gland. Wire AA’ (n°3) of USB/485 converter to RS485 (A) (27).
Installation and connections Page 31/57 b) Polarization and termination of the RS485 bus The bus can be polarized from your device if necessary. To do this you must switch the two microswitches (Pol. RS+ (A) and Pol. RS-(B)) of the electronic card in ON position. If your device is the last on the line on the RS485 bus you can switch the Term. RS switch on ON to activate line termination.
General use Page 32/57 V. General use SYCLOPE COOLTOUCH® is intended for measurement, regulation and treatment of swimming pool water. The installation of SYCLOPE COOLTOUCH® equipment is based on the principle of measurement and regulation on the pool filter circuit. The evaporated water from the cooling tower is supplemented by new water. A stand-alone level switch keeps the water level constant. These operations increase the mineral salt content of the circulating water.
Commissioning the Syclope COOLTOUCH Page 33/57 VI. Commissioning the SYCLOPE COOLTouch® You have just made the electrical connections and the connections of the various measurement and regulation devices. You are ready to realize the commissioning of your SYCLOPE COOLTouch®. Switch ON the device. Check that everything is good, your control panel is switched ON and other elements of your installation haven’t been disturbed.
Display mode and type Page 34/57 VII. Display mode and type SYCLOPE COOLTOUCH® regulator are fitted with a color touch screen graphic, all programming actions are realized with by pressing the screen. The touch screen is a resistive technology, you must press firmly on the screen to validate the action. Make sure that your SYCLOPE COOLTOUCH® controller is correctly programmed! An excess of product, or even a mixture, can cause harmful actions on human health and the environment.
Display mode and type Page 35/57 On/Off button Controller switched off – Press it to switch the controller ON Controller switched on – Press it to switch the controller OFF External touch button Realize the option configured in « Menu User »; « General configuration »; « Button ». Start/Stop function set as standard. See “DOC0485 - General programming instructions COOLTOUCH ENG Rev1” for more information.
Display mode and type Page 36/57 Notifications Inactive Active USB connection Wifi connection Ethernet connection GSM connection MySyclope connection No connections to MySyclope server (See. DOC0461 - Communication programming instructions COOLTOUCH for more information) USB key detected but not compatible, not readable (USB key must be formatted in FAT32) Connections to WIFI impossible (See.
Display mode and type Page 37/57 Tower indicators Manual operation Operation on timer Stop b) Display details of the channels Volume channel Type of measurement Volume 10 Measured value & Unit l Conductivity channel Type of measurement Conductivity 1111 Measured value & Unit µS/ cm Value higher the scale Value lower the scale Servitude notifications area Polarization in progress Water level Flow Timer R.I.
Display mode and type Page 38/57 Temperature channel Temperature Type of measurement 39.0 Measured value & Unit °C Value higher the scale Value lower the scale Servitude notifications area Value not displayable Polarization in progress Water level Flow Timer Empty tank R.I.C Overdose Value unmeasurable (Technical alarm) Sensor Sensor Sensor Out of order Maintenance Unstable 2) “Detailed” display of a channel a) Bleed valve To open the detailed display screen, press on of the main screen.
Display mode and type Page 39/57 b) Water flow switch To open the detailed display screen, press on of the main screen. Water flow switch Input(s) used for flow switch DI2 Last flow time 43m11s Last no flow time 24s c) Biocide Example with Biocide A To open the detailed display screen, press on of the main screen.
Display mode and type Page 40/57 d) Inhibitor / Dispersant To open the detailed display screen, press on of the main screen. FO3 : Inhibitor - INACTIVE Start biocide cycle Clear Total injection time 2m00s Tank level not empty Fill e) Dosing mode To open the detailed display screen, press on of the main screen.
Display mode and type f) Page 41/57 Tower management To open the detailed display screen, press on of the main screen.
Display mode and type Page 42/57 3) Graphical part Conductivity Press it to open following screen: Operating information Mesure information 27/08/2021 – 15:02 27/08/2021 – 15:02 Value: 1111 Setpoint: 4000 Hysteresis: 200 Parameter state: Enable Halt Polarization Circulation Sensor fault Alarm Controller state: Enable Halt Circulation Bleed state: Free Biocide A state: Free Biocide B state: Free Inhibitor state: Free Dispersant state Tank not empty Operating state: Manual ON Installation and startin
Input mode Page 43/57 VIII. Input mode The SYCLOPE COOLTOUCH® controller has a 5’’ touch screen. All orders are made by pressing areas of the screen provided. 1) Setup or Settings code entry screen This screen will appear if a Setup or Setting code is programmed. Enter the “Setup” password Numeric keypad Validate button Cancel button For more security, numbers are displayed randomly each time this screen appears. 2) Numerical value entry screen This screen will appear when entering a numeric value.
Input mode Page 44/57 « OFF » button used to deactivate a value, example, deactivate an alarm threshold. 3) Alphanumeric keyboard Entry field Delete key Validate key Shift key Caps lock key Keyboard type key Cancel key Other characters key a) « Shift » key This key switch the keyboard from lowercase to uppercase and vice versa. When this key is pressed, it will automatically switch again after pressing an alphanumeric key.
Input mode Page 45/57 d) « Other characters » key This key switch the keyboard to symbols or other characters not available in the lower and upper case. Key released lowercase uppercase mode active. => Press Key pressed other character mode active. e) « Back » key This key deletes the last character entered. Press to delete the last character. f) « Enter » key This key closes the keyboard while saving the changes. Tap to close and save.
Input mode Page 46/57 4) Main input elements a) Opening a selection list Press Open a list to open a list. b) Multi selection button Check box Press to change the state Inactive/Active Multi selection version, press the item to select State box Press Direction box Press to change the state NO / NC to change the direction c) Unique selection button Selection box Press to active state select d) Input button Numeric entry Press to open numerical keyboard.
Input mode Page 47/57 f) Selection list When an action is symbolized by this type of button, Open a list a list will open with the corresponding elements. The “simple” list offers maximum of 6 items, in the event that the list is longer, navigation buttons will appear to move through the list.
Input mode Page 48/57 g) Navigation bar In the programming menu each selection of a function adds a button in the navigation bar. It’s possible at any time to go down one or more levels in the programming by clicking on one of the menu buttons. Example: Menu number Analog input Menu Output relay Menu Output selection Menu Menu Setup Installer Menu Main Menu Menu Exit Main Menu Icons in the navigation bar correspond to the identification icons in the top left of each screen.
Annexes Page 49/57 IX. Annexes 5) “Configuration & Installation” – “Reset Factory” menu [0831] Menu Press then and SETUP to open following screen. FACTORY RESET « RESET FACTORY » menu will allow you to reset the regulator configuration by choosing some pre-set operating options.
Annexes Page 50/57 o o o o Biocide A (FO1) Biocide B (FO2) Inhibitor (FO3) Dispersant (FO4) Bleed valve (PO1) is always selected. Press « SAVE » button to validate your configuration. The following window appears asking you if you really want to clear the current configuration. The current configuration will be definitely lost.
Annexes Page 51/57 Installation and starting instructions
Annexes Page 52/57 6) « User » - « DATE & TIME » menu [0311] Menu Press then and to open following screen User DATE & TIME « DATE & TIME » menu will allow you to access the configuration of the time parameters.
Annexes Page 53/57 Automatic time change - Press the time zone map - Scroll the list up or down, remaining pressed until the desired time zone is on the centre part of the selection. - Wait for automatically shutdown to account for new time zone.
Annexes Page 54/57 7) Backup battery change Before changing the battery, switch off the power supply! Always use the same battery as the original. Open the transparent door and unscrew the 4 front screws using an appropriate screwdriver.
Annexes Page 55/57 Remove the button cell Put the new button cell Reconnect the flat cable between the cards and reassemble the front panel using the 4 fixing screws. Don’t overtighten because the screws are fixed in the plastic case. Reconnect the flat cable and replace the front panel before switching on the power supply.
SYCLOPE Electronique S.A.S. Z.I. Aéropole Pyrénées 64 230 SAUVAGNON Tel: (33) 05 59 33 70 36 Fax: (33) 05 59 33 70 37 Email: service-technique@syclope.fr © 2020 by SYCLOPE Electronique S.A.S. Subject to modification.