TECHNICAL DATA
Switch difference (temperature) 2K (±1K tolerance) at +25°C (+77°F), 50% RH
Switch difference (humidity) 4% RH (±1% tolerance) at +25°C (+77°F), 50% RH
Reaction time (humidity) approx. 5 sec.
Contact type change-over contact (relay)
Service life VDE: NO/NC > 15,000 cycles
UL: NO/NC > 30,000 cycles
Max. switching capacity (relay output) 240VAC, 10 (1.6) A
60VDC, 0.6A¹
Max. inrush current 30AAC for 10 sec.
Optical indicator LED
Connection
5-pole terminal, clamping torque 0.5Nm max.: rigid wire 2.5mm²
stranded wire (with wire end ferrule) 1.5mm²
Mounting clip for 35mm DIN rail, EN 60715
Casing plastic according to UL94 V-0, light grey
Dimensions 77 x 60 x 43mm
Weight approx. 0.2kg
Fitting position vertical
Operating/Storage temperature -40 to +60°C (-40 to +140°F)
Operating/Storage humidity max. 95% RH (non-condensing)
Protection type IP20
Approvals VDE, UL File No. E164102, GOST-R
¹ not UL confirmed
The electronic hygrotherm senses the ambient temperature and relative humidity in an enclosure with electric/
electronic components and turns on a heater (or alternatively a fan) at either set point, helping prevent the for-
mation of condensation in the enclosure. Due to its wide voltage range the hygrotherm can be utilised anywhere
in the world. The LED integrated in the adjustment knob on the active controller is lit when the connected
device is in operation.
> Temperature and humidity adjustable
> Wide voltage range
> Operating temperature down to -40°C
> High switching capacity
> Status indicator (LED)
Connection diagram
Example of connection
Heater
Hygrotherm
ETF 012
Heater
ELECTRONIC HYGROTHERM
ETF 012
Art. No. Operating voltage Setting range temperature Setting range humidity
01230.0-00 100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC) 0 to +60°C 50 to 90% RH
01230.9-00 100-240VAC, 50/60Hz (min. 90VAC, max. 265VAC) +32 to +140°F 50 to 90% RH
01230.1-00 24-48VDC (min. 20VDC, max. 60VDC) 0 to +60°C 50 to 90% RH
TECHNICAL DATASHEET