Rapid Shutdown Kit Manual

Rapid Shutdown Kit Installation - MAN-01-00186-1.6
1
Rapid Shutdown Kit - Installation and Configuration
(Single Phase Inverters)
This document describes how to install the rapid shutdown kit in the SolarEdge Safety Switch, and how to enable the rapid
shutdown feature in the inverter in order to provide the functionality described in the Rapid Shutdown clause of NEC2014
690.12 (1) through (4).
Kit Contents
§ Rapid shutdown cables
§ (Optional - For older inverters only) Micro-SD card and SD card adapter with firmware files (Note: DO NOT THROW AWAY
THE CARD AND THE ADAPTER; keep them for installation of other rapid shutdown kits)
Cable Installation
Perform this procedure before connecting the strings to the Safety Switch [Chapter 4: Connecting the AC and the Strings to the
Safety Switch in the SolarEdge Installation Guide].
1 Turn the inverter ON/OFF switch to OFF. If installing the kit in an inverter that is already operating, wait until the LCD
indicates that the DC voltage is safe (<50V), or wait five minutes before continuing to the next step.
2 Turn the Safety Switch and the AC switch on the main circuit board to OFF.
WARNING!
If you cannot see the inverter panel, or if a malfunction is indicated on the LCD panel, wait five minutes for the input
capacitors of the inverter to discharge.
3 Loosen the four Allen screws on the front cover of the Safety Switch, and open the cover.
4 Carefully disconnect the two DC cables from the left side of the switch and from the DC connection spring clamp terminals,
as illustrated below
1
. Use a standard straight-bladed screwdriver to disconnect the cables from the terminals.
Figure 1: Inside the AC/DC Safety Switch
1
The internal components may vary depending on the Safety Switch model; the figures in this documents show the AC/DC Safety Switch for single phase
7.6-11.4 kW inverters.
DC connection terminals
Disconnect here
Disconnect here
Switch terminal block