User Manual

Receptacle Tester w/GFCI SKY24021
Operating Instructions
Warning: Always test on a known live circuit before use to ensure proper
operation.
Wiring Configuration Testing
Tests for correct wiring, open ground, reverse polarity, open hot, open neutral and
hot/ground reversed.
1. Plug tester into receptacle under test.
2. Verify proper wiring configuration by noting the bulbs lit on the tester.
3. Compare the bulbs lit to the legend on the product label to determine the
wire condition.
4. If a miswired condition is found, stop any further testing and consult a
qualified electrician to rectify the problem.
GFCI Testing
1. Consult the GFCI device manufacturer’s instructions to determine that the GFCI
is installed in accordance with the manufacturer’s specifications.
2. Check for correct wiring of the receptacle and all remotely connected receptacles
on the branch circuit.
3. Operate the test button on the GFCI installed in the circuit. The test light will
turn on, indicating the activation of the GFCI test. If the GFCI does not trip,
consult a qualified electrician. If it does trip, reset the GFCI.
4. Insert the 61-501 into the receptacle under test. The middle/right bulbs should
be lit indicating correct wiring configuration. If the tester trips the GFCI protection
on the circuit, then nuisance tripping is occurring due to additional leakage
to ground or the GFCI trip level on the device is set too low.
5. Depress the GFCI test button on the tester. The wiring indicator bulbs should
go out, indicating a properly functioning GFCI. Reset the GFCI device.
6. If the tester fails to trip the GFCI, it suggests: (a) a wiring problem with a totally
operable GFCI, or (b) proper wiring with a faulty GFCI. Consult with an
electrician to check the condition of the wiring and the GFCI.
Note:
1. All appliances or equipment on the circuit being tested should be unplugged to
help avoid erroneous readings.
2. Not a comprehensive diagnostic instrument but a simple instrument to detect
nearly all common improper wiring conditions.
3. Refer all indicated problems to a qualified electrician.
4. Will not indicate quality of ground.
5. Will not detect two hot wires in a circuit.
6. Will not detect a combination of defects.
7. Will not detect reversal of grounded and grounding conductors