PHOTOELECTRONIC SMOKE DETECTOR WITH BUILT-IN WIRELESS TRANSMITTER Installation and Operation Manual 3126052 Model # SD4-MC(US) 418 MHZ TRANSMITTER Document # 108137
General Information Before installing detectors, please thoroughly read these installation instructions. For detailed information on detector spacing, placement, zoning, wiring, and special applications refer to current edition of the NFPA 72 National Fire Alarm Signaling Code. NOTICE: Do not discard this manual. Manual should be left with the owner/user of this equipment. IMPORTANT: This detector must be tested and maintained regularly following NFPA requirements. Test detector operation weekly.
General Description: The Model SD4-MC(US) photocell electronic smoke detector with builtin wireless transmitter is intended for use with the Silent Call® Mini receiver to form an alerting system. The transmitter will send alarm condition messages to the system’s receiver. The SD4-MC(US) wireless transmitter operation is to be used only with Silent Call® Medallion Series Receivers.
This includes cleaning, maintenance or screen replacement. The Model SD4-MC(US) contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. During an alarm condition, pressing the detector’s test switch will silence the piezoelectric horn for 5 minutes. The built-in Drift Compensation algorithm automatically maintains the sensitivity of the detector.
Table 1: Detector LED Modes Green LED Red LED Piezoelectric Horn Power-up Blinks every 5 sec Blinks every 5 sec Off Normal (Standby) Blinks every 10 sec Off Off Out of Sensitivity Off Blinks every 5 sec Off Smoke Alarm Off Blinks every 1 sec Temporal Pattern Low Battery Off Blinks every 45 sec Chirp every 45 sec after LED blinks for 7 days During initial power-up, the red and green LEDs will blink synchronously once every 5 seconds.
functioning normally within its listed sensitivity range, the green LED blinks once every 10 seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red LED blinks once every 5 seconds. When the alarm has been activated by smoke, the red LED blinks every 1 second. The LED indication must not be used in place of the tests specified under Testing. If the detector senses a low battery condition, the red LED blinks once every 45 seconds.
Battery Life Expectancy: Replace the battery once a year or immediately when the low battery indicator starts to blink and the horn begins to chirp. Battery Installation and Replacement: To replace the battery: 1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery and dispose of it properly. 2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery. 3.
NFPA Required Protection: This smoke detector should be installed in accordance with the National Fire Protection Association, Standard 72 (National Fire Protection Association, Quincy, MA 002269). This detector will provide maximum protection when installed in compliance with the National Fire Protection Association (NFPA). Standard NFPA 72, household fire warning equipment “For your Information, the National Fire Alarm and Signaling Code NFPA reads as follows” 11.5.
(Reprinted with permission from NFPA 72®, National Fire Alarm Code Copyright© 2007 National Fire Protection Association, Quincy MA 02269. This reprinted material is not the complete and official position of the Nation Fire Protection Association, on the referenced subject which is represented only by the standard in its entirety.) (National Fire Alarm Code® and NFPA 72® are registered trademarks of the National Fire Protection Association, Inc., Quincy, MA 02269.
Recommended Locations for Smoke Detectors: The National Fire Protection Agency (NFPA) recommends one smoke detector on every floor, in every sleeping area, and in every bedroom. In new construction, the smoke detectors must be AC powered and interconnected. For additional coverage, it is recommended that you install a smoke detector in all rooms, halls, storage areas, finished attics, and basements where temperatures normally remain between 4.4°C to 37.8°C.
• cm) from the ceiling. see figure 1. Put a smoke detector at both ends of a bedroom hallway if the hallway is more than 40 feet (12 meters) long.
Dead Air Space Best in center of ceiling No closer than 4 inch (10 cm) from side wall Mount on wall at least 4 inch (10 cm) from ceiling No more than 6 inches (15 cm) from ceiling Best location Acceptable location Figure 1.2: Recommended smoke detector mounting locations.
• In rooms with sloped, peaked, or gabled ceilings, mount detectors within 3 feet (0.9 meters) measured horizontally from the highest point of the ceiling. See figure 2. Horizontal distance from peak 3 feet (0.9 m) Figure 2: Recommended smoke detector location in rooms with sloped, gabled, or peaked ceilings.
Where Smoke Detectors Should Not Be Located: Nuisance alarms are caused by placing detectors where they will not operate properly. To avoid nuisance alarms, do not place detectors: • In or near areas where combustion particles are normally present such as kitchens, in garages where there are particles of combustion from vehicle exhausts, near furnaces, hot water heaters, or gas space heaters.
Air Flow Air Return Bath Stove Bedroom Kitchen Correct Incorrect Bedroom Living Room Figure 3: Recommended smoke detector locations to avoid air streams with combustion particles.
• In damp or very humid areas, or next to bathrooms with showers. The moisture in humid air can enter the sensing chamber as water vapor, and will cool and condense into droplets that cause a nuisance alarm. Install detectors at least 5 feet (1.5 meters) away from bathrooms. • In very dusty or dirty areas. Dust and dirt can build up on the detector sensing chamber and make it overly sensitive, or can block openings to the sensing chamber and keep the detector from sensing smoke.
• Near florescent light fixtures. Electrical “noise” from nearby florescent light fixtures may cause a nuisance alarm. Install detectors at least 10 feet (3 meters) away from such light fixtures. Limitations of Smoke Alarms • Smoke detectors will not work without power. Battery operated detectors will not work without batteries, with dead batteries, or if the batteries are not put in properly.
• • • The horn in your detector meets or exceeds current audibility requirements of Underwriters Laboratories. However, if the detector is located outside a bedroom, it may not wake a sound sleeper, especially if the bedroom door is closed or only partly open. If the detector is located on a different level of the residence than the bedrooms, it is even less likely to wake up people sleeping in the bedrooms. All types of smoke detectors have limitations.
Test Switch Green LED Red LED Figure 4: Silent Call Model #SD4-MC(US) Wireless Smoke Detector Programming The smoke detector is pre-programmed at the factory. Transmitter Setting The Silent Call® system is digitally coded. The Medallion Series SD4MC(US) Smoke Detector is set to a unique million code setting at the factory and therefore never requires the need of a different code. Transmitter operates at a frequency of 418MHz.
Mounting First, determine the best location for the smoke detector, one that provides a strong wireless transmission path and proper smoke detection. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section of this manual. To mount the detector, perform the following steps: 1.
Figure 5: Mount Detector Across Ceiling Panel Support. DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 5. Dust Covers are an effective way to limit the entry of dust into the smoke detector sensing chamber during construction. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, it is recommended that the detectors be removed before beginning construction or other dust producing activity.
Testing the Sensor Detectors must be tested after installation and following periodic maintenance. The Model #SD4-MC(US) may be tested as follows: A. Test Switch 1. A recessed test switch is located on the detector housing (see Figure 6). 2. Push and hold the recessed test switch for a minimum of 5 seconds. Use a small screwdriver or Allen key with maximum diameter of 0.18 inch (the detector will trigger and then the smoke detector will go into alarm thus sending a transmitting signal to the receiver.
Test Switch Green LED Red LED PUSH RECESSED SWITCH WITH A 0.18’ MAX DIAMETER TOOL Figure 6: Recessed Test Switch Opening B. Smoke Entry Test Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms. Canned aerosol is also an accepted method.
Testing Signal Strength A test should be performed before installation to determine a strong communication path with the receiver and after installation is complete. Also the owner/user should test the unit at least weekly. Testing Programming A test should be performed before installation to ensure the detector transmitter address is properly programmed to the receiver, and are operational as a system.
Maintenance NOTE: Power must be removed from the detector before performing maintenance of any kind by removing the detector’s battery. 1. To ensure proper power-down sequence, battery must be removed from detector for a minimum of 20 seconds before servicing. 2. Vacuum the cover or use canned air to remove any dust or debris. 3. Using a vacuum or canned air spray carefully clean any dust or debris From Smoke Detector Cover. 4. Reinstall the detector and test. (see the Testing section).
What to do in case of fire • Don’t panic; stay calm. Follow your family escape plan. • Get of the house as quickly as possible. Don’t stop to get dressed or collect anything. • Feel doors with the back of your hand prior to opening them. If a door is cool, open it slowly. Don’t open a hot door. Keep door and windows closed, unless you must escape through them. • Cover your nose and mouth with a cloth (preferably damp). Take short shallow breaths.
FCC INFORMATION NOTICE: Unauthorized changes or modifications could void the user’s authority to operate the equipment. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device.
Specifications Power Source: One 3-volt CR123A Lithium Battery (included). (Replace with Panasonic CR123A or DURACELL DL123A) These batteries are available at local retail stores. You can also order Replacement Batteries Online at www.Silentcall.com. 2.3 inches (58 mm) Height: 5.3 inches (135 mm) (with mounting base) Diameter: 8.5 oz. (241 g) (without battery) Weight: Operating Ambient Temperature Range: 40° to 100°F (4.4° to 37.
PHOTOELECTRONIC SMOKE DETECTOR WITH BUILT-IN WIRELESS TRANSMITTER Installation and Operation Manual 3126052 Model # SD4-MC 418 MHZ TRANSMITTER Document # 108125
General Information Before installing detectors, please thoroughly read these installation instructions. For detailed information on detector spacing, placement, zoning, wiring, and special applications refer to local building codes that may apply. NOTICE: Do not discard this manual. Manual should be left with the owner/user of this equipment. IMPORTANT: This detector must be tested and maintained regularly. Test detector operation weekly. The detector should be cleaned at least once a year.
General Description: The Model SD4-MC photocell electronic smoke detector with builtin wireless transmitter is intended for use with the Silent Call® Mini receiver to form an alerting system. The transmitter will send alarm condition messages to the system’s receiver. The SD4-MC wireless transmitter operation is to be used only with Silent Call® Medallion Series Receivers.
This includes cleaning, maintenance or screen replacement. The Model SD4-MC contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. During an alarm condition, pressing the detector’s test switch will silence the piezoelectric horn for 5 minutes. The built-in Drift Compensation algorithm automatically maintains the sensitivity of the detector.
Table 1: Detector LED Modes Green LED Red LED Piezoelectric Horn Power-up Blinks every 5 sec Blinks every 5 sec Off Normal (Standby) Blinks every 10 sec Off Off Out of Sensitivity Off Blinks every 5 sec Off Smoke Alarm Off Blinks every 1 sec Temporal Pattern Low Battery Off Blinks every 45 sec Chirp every 45 sec after LED blinks for 7 days During initial power-up, the red and green LEDs will blink synchronously once every 5 seconds.
functioning normally within its listed sensitivity range, the green LED blinks once every 10 seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red LED blinks once every 5 seconds. When the alarm has been activated by smoke, the red LED blinks every 1 second. The LED indication must not be used in place of the tests specified under Testing. If the detector senses a low battery condition, the red LED blinks once every 45 seconds.
Battery Life Expectancy: Replace the battery once a year or immediately when the low battery indicator starts to blink and the horn begins to chirp. Battery Installation and Replacement: To replace the battery: 1. Remove the detector from its mounting base by twisting the de tector counterclockwise. Remove the battery and dispose of it properly. 2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery. 3.
Recommended Locations for Smoke Detectors: One smoke detector on every floor, in every sleeping area, and in every bedroom. In new construction, the smoke detectors must be AC powered and interconnected. For additional coverage, it is recommended that you install a smoke detector in all rooms, halls, storage areas, finished attics, and basements where temperatures normally remain between 4.4°C to 37.8°C. Make sure no door or other obstruction could keep smoke from reaching detectors.
• top of wall-mounted detectors between 4 and 6 inches (10 and 15 cm) from the ceiling. see figure 1. Put a smoke detector at both ends of a bedroom hallway if the hallway is more than 40 feet (12 meters) long.
Dead Air Space Best in center of ceiling No closer than 4 inch (10 cm) from side wall Mount on wall at least 4 inch (10 cm) from ceiling No more than 6 inches (15 cm) from ceiling Best location Acceptable location Figure 1.2: Recommended smoke detector mounting locations.
• In rooms with sloped, peaked, or gabled ceilings, mount detectors within 3 feet (0.9 meters) measured horizontally from the highest point of the ceiling. See figure 2. Horizontal distance from peak 3 feet (0.9 m) Figure 2: Recommended smoke detector location in rooms with sloped, gabled, or peaked ceilings.
Where Smoke Detectors Should Not Be Located: Nuisance alarms are caused by placing detectors where they will not operate properly. To avoid nuisance alarms, do not place detectors: • In or near areas where combustion particles are normally present such as kitchens, in garages where there are particles of combustion from vehicle exhausts, near furnaces, hot water heaters, or gas space heaters.
Air Flow Air Return Bath Stove Bedroom Kitchen Correct Incorrect Bedroom Living Room Figure 3: recommended smoke detector locations to avoid air streams with combustion particles.
• In damp or very humid areas, or next to bathrooms with showers. The moisture in humid air can enter the sensing chamber as water vapor, and will cool and condense into droplets that cause a nuisance alarm. Install detectors at least 5 feet (1.5 meters) away from bathrooms. • In very dusty or dirty areas. Dust and dirt can build up on the detector sensing chamber and make it overly sensitive, or can block openings to the sensing chamber and keep the detector from sensing smoke.
• Near florescent light fixtures. Electrical “noise” from nearby florescent light fixtures may cause a nuisance alarm. Install detectors at least 10 feet (3 meters) away from such light fixtures. Limitations of Smoke Alarms • Smoke detectors will not work without power. Battery operated detectors will not work without batteries, with dead batteries, or if the batteries are not put in properly.
• • • The horn in your detector meets or exceeds current audibility requirements of Underwriters Laboratories. However, if the detector is located outside a bedroom, it may not wake a sound sleeper, especially if the bedroom door is closed or only partly open. If the detector is located on a different level of the residence than the bedrooms, it is even less likely to wake up people sleeping in the bedrooms. All types of smoke detectors have limitations.
Test Switch Green LED Red LED Figure 4: Silent Call Model #SD4-MC Wireless Smoke Detector Programming The smoke detector is pre-programmed at the factory. Transmitter Setting The Silent Call® system is digitally coded. The Medallion Series SD4MC Smoke Detector is set to a unique million code setting at the factory and therefore never requires the need of a different code. Transmitter operates at a frequency of 418MHz.
Mounting First, determine the best location for the smoke detector, one that provides a strong wireless transmission path and proper smoke detection. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section of this manual. To mount the detector, perform the following steps: 1.
Figure 5: Mount Detector Across Ceiling Panel Support. DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 5. Dust Covers are an effective way to limit the entry of dust into the smoke detector sensing chamber during construction. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, it is recommended that the detectors be removed before beginning construction or other dust producing activity.
Testing the Sensor Detectors must be tested after installation and following periodic maintenance. The Model #SD4-MC may be tested as follows: A. Test Switch 1. A recessed test switch is located on the detector housing (see Figure 6). 2. Push and hold the recessed test switch for a minimum of 5 seconds. Use a small screwdriver or Allen key with maximum diameter of 0.18 inch (the detector will trigger and then the smoke detector will go into alarm thus sending a transmitting signal to the receiver.
Test Switch Green LED Red LED PUSH RECESSED SWITCH WITH A 0.18’ MAX DIAMETER TOOL Figure 6: Recessed Test Switch Opening B. Smoke Entry Test Hold a smoldering punk stick or cotton wick at the side of the detector and gently blow smoke through the detector until the unit alarms. Canned aerosol is also an accepted method.
Testing Signal Strength A test should be performed before installation to determine a strong communication path with the receiver and after installation is complete. Also the owner/user should test the unit at least weekly. Testing Programming A test should be performed before installation to ensure the detector transmitter address is properly programmed to the receiver, and are operational as a system.
Maintenance NOTE: Power must be removed from the detector before performing maintenance of any kind by removing the detector’s battery. 1. To ensure proper power-down sequence, battery must be removed from detector for a minimum of 20 seconds before servicing. 2. Vacuum the cover or use canned air to remove any dust or debris. 3. Using a vacuum or canned air spray carefully clean any dust or debris From Smoke Detector Cover. 4. Reinstall the detector and test. (see the Testing section).
What to do in case of fire • • • • • • • • Don’t panic; stay calm. Follow your family escape plan. Get of the house as quickly as possible. Don’t stop to get dressed or collect anything. Feel doors with the back of your hand prior to opening them. If a door is cool, open it slowly. Don’t open a hot door. Keep door and windows closed, unless you must escape through them. Cover your nose and mouth with a cloth (preferably damp). Take short shallow breaths.
may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation of the device. This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
Specifications Power Source: One 3-volt CR123A Lithium Battery (included). (Replace with Panasonic CR123A or DURACELL DL123A) These batteries are available at many local retail stores. You can also order Replacement Batteries Online at www.Silentcall.com. 2.3 inches (58 mm) Height: 5.3 inches (135 mm) (with mounting base) Diameter: 8.5 oz. (241 g) (without battery) Weight: Operating Ambient Temperature Range: 40° to 100°F (4.4° to 37.
DÉTECTEUR DE FUMÉE PHOTO ÉLECTRONIQUE AVEC TRANSMETTEUR SANS FIL INCORPORÉ INSTRUCTIONS D’INSTALLATION ET D’EMPLOI 3126052 Modèle # SD4-MC TRANSMETTEUR 418 MHZ Document # 108125
Informations générales Avant l’installation de détecteurs, veuillez lire attentivement ces instructions d’installation. Pour des informations détaillées sur l’espacement des détecteurs, leur position, leur câblage et leurs applications spéciales, veuillez vous reporter aux codes du bâtiment locaux. REMARQUE: Ne jetez pas ce manuel. Ce manuel doit demeurer en la possession du propriétaire / de l’utilisateur de l’équipement. IMPORTANT: Ce détecteur doit être testé et entretenu.
Description générale: Le Modèle SD4-MC de détecteur de fumée électronique à cellule photoélectrique avec transmetteur sans fil incorporé doit être utilisé avec le Mini récepteur Silent Call® pour constituer un système d’alerte. Le transmetteur émettra des messages de situation d’alarme en direction du récepteur du système. Le transmetteur sans fil SD4-MC ne doit être utilisé qu’avec des récepteurs Silent Call® de la série Medallion.
séquence ANSI S3.41 temporelle en cas d’alarme. Lors d’une alarme, la pression sur l’interrupteur de test du détecteur rend l’avertisseur piézoélectrique silencieux pendant 5 minutes. L’algorithme incorporé de compensation de dérivation maintient la sensibilité du détecteur. L’installation du support de montage est simplifiée par l’incorporation de fonctionnalités compatibles avec les attaches pour cloison sèches ou autres méthodes permettant d’assujettir les détecteurs en place.
Tableau 1 : Modes du détecteur DEL Voyant DEL vert Voyant DEL rouge Avertisseur piézoélectrique Clignote toutes Clignote toutes les 5 les 5 secondes Éteint Normal (attente) Clignote toutes les 5 Éteint Éteint Plus de sensibilité Éteint Clignote toutes les 5 secondes Éteint Alarme de détection de fumée Éteint Clignote toutes les secondes Séquence temporelle Pile presque épuisée Éteint Clignote toutes les 45 secondes Émet un petit bruit toutes les 45 secondes lorsque le voyant DEL a clignot
Lorsqu’il est allumé et que le détecteur fonctionne normalement à l’intérieur de ses limites de sensibilité, le voyant vert DEL clignote une fois toutes les 10 secondes. Si le détecteur doit faire l’objet d’opérations de maintenance parce que sa sensibilité s’est déplacée hors des limites indiquées, le voyant rouge DEL clignote toutes les 5 secondes. Lorsque l’alarme a été activée par la fumée, le voyant DEL rouge clignote toutes les secondes.
Durée d’utilisation de la pile : Remplacez la pile une fois par an ou dès que l’indicateur d’épuisement de la pile commence à clignoter et lorsque l’avertisseur commence à émettre un petit bruit. Installation et remplacement de la pile : Pour remplacer la pile: 1. Retirez le détecteur de son support de montage en le faisant tourner dans le sens contraire des aiguilles d’une montre. Retirez la pile et éliminez-la comme il convient. 2.
Emplacements recommandés pour les détecteurs de fumée: Un détecteur de fumée à chaque étage, dans chaque chambre, et dans chaque endroit où l’on peut dormir. Dans une construction neuve, les détecteurs de fumée doivent être alimentés par courant électrique et interconnectés.
• • de tout mur ou coin. Voir la figure 1. Si le code du bâtiment local ou de l’état permet le montage sur le mur, placez les détecteurs muraux à entre 4 et 6 pouces (10 et 15 cm) du plafond. Voir la figure 1. Mettez un détecteur de fumée aux deux extrémités d’un couloir de chambres si celui-ci est long de plus de 40 pieds (12 mètres).
De préférence au centre du plafond Espace mort Pas plus près que 4 pouces (10 cm) du mur latéral Montage sur le mur à au moins 4 pouces (10 cm) du plafond À au plus 6 pouces (15 cm) du plafond Meilleur emplacement Emplacement acceptable Figure 1.2: emplacements recommandés pour les détecteurs de fumée.
• Dans les salles dont le plafond est incliné, pointu, ou à pignons, installez les détecteurs à un distance de moins de trois pieds (0,9 mètres) mesurés horizontalement à partir du point le plus élevé du plafond. Voir la figure 2. Distance horizontale du pic 3 pieds (0,9 m) Figure 2: Emplacement recommandé pour le détecteur de fumée dans les salles dont le plafond est incliné, pointu ou à pignons.
Ne pas installer de détecteurs de fumée dans les endroits suivants: Les alarmes intempestives sont causées par le placement de détecteurs dans des endroits où ils ne peuvent pas fonctionner correctement.
Salle de bain Flux d’air Cuisinière Retour d’air Chambre Cuisine Correct Incorrect Chambre Salle de séjour Figure 3: Emplacement recommandé pour des détecteurs de fumée pour éviter les courants d’air transportant des particules de combustion.
• Dans les endroits très humides, ou à proximité de salles de bain avec des douches. L’humidité de l’air peut pénétrer dans le compartiment du capteur sous la forme de vapeur d’eau, et se condenser en petites gouttes qui peuvent provoquer une alarme intempestive. Installez les détecteurs à au moins 5 pieds (1,5 mètre) de salles de bains. • Dans des zones très poussiéreuses ou sales.
• À proximité de lampes fluorescentes. Le « bruit » électrique provenant des lampes fluorescentes peut provoquer une alarme intempestive. Installez les détecteurs à au moins 10 pieds (3 mètres) de lampes de ce type. Limitations des détecteurs de fumée • Les détecteurs de fumée ne fonctionnent pas sans alimentation. Les détecteurs à piles ne fonctionnent pas sans pile, si leurs piles sont épuisées, ou si elles ne sont pas correctement insérées dans l’appareil.
• • • possible qu’un détecteur au deuxième étage ne décèle pas un incendie au premier étage ou au sous-sol. Des détecteurs doivent donc être disposés à chaque niveau d’une résidence ou d’un bâtiment. L’avertisseur de votre détecteur satisfait aux exigences d’audibilité de la Station d’essais-laboratoire du feu (Underwriters Laboratories) actuellement en vigueur, ou les surpasse.
Interrupteur de test Voyant DEL vert Voyant DEL rouge Figure 4: Modèle Silent Call No. SD4-MC Détecteur de fumée sans fil Programmation Le détecteur de fumée est pré-programmé en usine. Réglage du transmetteur Le système Silent Call® est à code numérique. Le détecteur de fumée de la série Medallion SD4-MC est réglé sur un code unique parmi un million en usine et n’a jamais besoin d’un code différent. Le transmetteur fonctionne à une fréquence de 418 MHz.
Installation Tout d’abord, déterminez le meilleur endroit pour le détecteur de fumée, qui doit permettre une bonne transmission sans fil et une bonne détection de la fumée. ON VÉRIFIERA QUE LE SIGNAL PEUT ÊTRE TRANSMIS À PARTIR DE L’EMPLACEMENT D’INSTALLATION PROPOSÉ AVANT DE L’INSTALLER DE MANIÈRE PERMANENTE. Pour le vérifier, procédez au test décrit dans la rubrique TEST DE LA PUISSANCE DU SIGNAL de ce manuel. Pour installer le détecteur, suivez les étapes suivantes: 1.
Figure 5: Montez le détecteur sur le support de plafond. N’ATTACHEZ PAS le détecteur à des panneaux amovibles du plafond. Attachez le détecteur sur le panneau comme le montre le Figure 5. Les housses à poussière permettent de limiter efficacement l’introduction de poussière dans le compartiment du capteur du détecteur de fumée lors de travaux. Toutefois, il est possible qu’elles n’empêchent pas complètement l’entrée dans le détecteur de particules présentes dans l’air.
Test du détecteur Les détecteurs doivent être testés après l’installation et à la suite de la maintenance périodique. Le Modèle No. SD4-MC peut être testé de la façon suivante: A. Interrupteur de test 1. Un interrupteur de test en retrait se trouve sur le boîtier du détecteur (voir la Figure 6). 2. Maintenez appuyé l’interrupteur de test en retrait pendant un minimum de 5 secondes.
Interrupteur de test Voyant DEL vert Voyant DEL rouge APPUYEZ SUR L’INTERRUPTEUR EN RETRAIT AVEC UN OUTIL D’UN DIAMÈTRE MAXIMUM DE 0,18’ Figure 6: Ouverture de l’interrupteur de test en retrait B. Test d’entrée de la fumée Tenez un bâtonnet ou une mèche de coton enflammé(e) à côté du détecteur et soufflez pour diriger la fumée dans le détecteur jusqu’à ce que l’alarme retentisse. Il est également possible de vaporiser un aérosol à proximité de l’appareil.
Test de la puissance du signal Un test doit être effectué avant l’installation pour vérifier que la communication s’effectue facilement avec le récepteur et après l’installation. Le propriétaire / utilisateur doit également tester l’appareil au moins une fois par semaine. Test de la programmation On procédera à un test avant l’installation pour vérifier que l’adresse du transmetteur du détecteur est bien programmée à celle du récepteur, et que le système est opérationnel.
Maintenance REMARQUE : Le détecteur doit être mis hors tension avant de procéder à toute opération de maintenance, en retirant la pile du détecteur. 1. Pour veiller à bien éteindre l’appareil, la pile doit être retirée du détecteur pendant un minimum de 20 secondes avant la maintenance. 2. Passez le couvercle à l’aspirateur ou servez-vous d’air en aérosol pour retirer toute poussière ou tout débris. 3.
Que faire en cas d’incendie • • • • • • • • Ne paniquez pas ; restez calme. Suivez le plan d’évacuation de la famille. Sortez de la maison le plus rapidement possible. Ne vous arrêtez pas pour vous habiller ou ramasser quoi que ce soit. Touchez les portes avec le dos de votre main avant de les ouvrir. Si une porte est froide, ouvrez-la lentement. N’ouvrez pas une porte brûlante. Gardez la porte et les fenêtres fermées, à moins que vous deviez vous échapper par celles-ci.
brouillage nuisible, et (2) cet appareil doit accepter toute interférence reçue, y compris les interférences pouvant entraîner un fonctionnement indésirable du dispositif. Cet équipement a été testé et déclaré conforme aux limites d’un appareil numérique de classe B, conformément à l’article 15 des règlements FCC. Ces limites sont conçues pour fournir une protection raisonnable contre les interférences nuisibles dans une installation résidentielle.
Spécifications Source d’alimentation: Une pile au lithium de 3 volts CR123A (livrée avec l’appareil). (Remplacez-la par une pile Panasonic CR123A ou Duracell DL123A). Ces piles peuvent être achetées dans de nombreux magasins de détail locaux. Vous pouvez également commander des piles de rechange en ligne à www.Silentcall.com. 2,3 pouces (58 mm) 5,3 pouces (135 mm) (avec support de montage) Poids 8,5 oz.