Quick Installation Guide

Sensors
EasySense
Fixture-Mount
Philips EasySense Quick Installation Guide
Commercial Product Name Order Code
EasySense Fixture-Mount Sensor SNS210
Connection Color
Green Ground
White Neutral
Black Line
LED Drivers
Sensor Part Number
Driver Model Number Description
XI040C110V054VPT2 Xitanium 40W 0.1-1.1A 27-54V 120-277V SR
XI075C200V054VPT1 Xitanium 75W 0.1-2.0A 27-54V 120-277V SR
Specications available at www.philips.com/XitaniumSR.
* Wiring diagram for 40W driver shown. Other drivers have dierent wiring diagrams.
Consult datasheet for driver for applicable wiring diagram.
Note: Below data applicable for SNS210..
XITANIUM SR
LED DRIVER
EASYSENSE
LED+
LED+
LED-
LED-
DA+
DA–
Connectors
SR
SR
LINE
NEUTRAL
GROUND
NC
Connectors
(non-polarized)
Use 18AWG solid copper wire,
rated >=600V/90C.
Strip wire to 3/8”.
Electrical Information
Input Voltage Powered by SR driver low-voltage interface
Current Consumption 11mA
Nominal Power Consumption 130mW
Standby Power < 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type Passive infrared (PIR)
Enable/Disable Default enabled
Detection O/Auto-on; Red LED indicates “on
Eco On Level 0-100%
Hold Time 0.5-60 minutes
Viewing Angle X=72°, Y = 86° ( See detection pattern)
Background Light Level 0-100%
Prolong Time 0 minutes - innity
Grace Fading 0-25 sec
Response Time/Fading to Switch On/O 0.7Sec
Daylight Sensing
Enable/Disable Default enabled
Auto-calibration Upon power-up
Viewing Angle 40° (half value sensitivity); 2% cut-o point at 75°
Task Tuning
Full Light Setting 0-100%
Environment & Approbation
Operating Ambient Temperature Range 0°C to 55°C
Operating Humidity 0–95% non condensing
Storage Temperature -25°C to 85°C
Storage Humidity 0-95% non condensing
Max Case Temperature (Tcase) 55°C
Agency Approbations UL, CSA; FCC; Tested and approved for use in plenums
Certication California Title 20
Limited Warranty 5 years
Digital Interface Xitanium SR
Other
Status Indicators Red, Yellow. Yellow LED on: Vacancy & Sensor is functional;
Red LED on: Motion is detected
No. Drivers per Sensor Four (max)
Field Conguration Parameters set via MasterConnect app for Android and iPhone phones
using Bluetooth Low Energy (Bluetooth LE).
© 2019 Signify Holding. All rights reserved. The information
provided herein is subject to change, without notice. Signify
does not give any representation or warranty as to the accuracy
or completeness of the information included herein and shall
not be liable for any action in reliance thereon. The information
presented in this document is not intended as any commercial
oer and does not form part of any quotation or contract,
unless otherwise agreed by Signify. Philips and the Philips
Shield Emblem are registered trademarks of Koninklijke Philips
N.V. All other trademarks are owned by Signify Holding or their
respective owners.
philips.com/easysense
Signify North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873
Tel. 855-486-2216
Signify Canada Ltd.
281 Hillmount Rd,
Markham, ON, Canada L6C 2S3
Tel. 800-668-9008
PLt-19041QG_EasySense SNS210 QIG 10/19 page 1 of 2
Document #: 4435 631 00371 REV. E
Operation and Conguration via Mobile App
EasySense operates immediately upon installation and energization without further commissioning. If changes from default settings
are desired, EasySense (SNS210) can be congured via MasterConnect app through Bluetooth LE. For a complete description of the
features and default settings—as well as details on the app—refer to www.philips.com/easysense.
FCC and IC Statement
This device complies with part 15 of the FCC rules for the United States and Industry Canada (IC) license-exempt RSS standard(s).
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation. Any changes or modications not expressly
approved by Signify could void the user’s authority to operate this equipment. This product is intended for commercial use only.
This equipment should be installed and operated with a minimum distance of 20cm between the radiator and your body.
Déclaration De Conformité À La Fcc/Ic
Ce dispositif est conforme à la partie 15 des règles de la Federal Communications Commission (FCC) des États-Unis et d’Industrie
Canada (IC) exempts de licence RSS norme(s). Son fonctionnement est assujetti aux deux conditions suivantes : (1) Ce dispositif ne
doit pas provoquer de brouillage préjudiciable, et (2) il doit accepter tout brouillage reçu, y compris le brouillage pouvant entraîner
un mauvais fonctionnement. Tous les changements ou modications non expressément approuvés par Signify, sont susceptibles
d’annuler le droit de l’utilisateur à se servir de cet équipement. Ce produit est exclusivement destiné à un usage commercial.
Cet équipement doit être installé et utilisé avec une distance minimale de 20 cm entre le radiateur et votre corps.
Connection Color
Purple DA+
Brown DA-
Red LED+
Blue LED-
Wiring Diagram*