User Manual

4/18/2011 Page 1 of 8
SignalFire Telemetry - Rev 5.0
SFRSS Modbus-in-a-Stick Instruction Sheet
The SignalFire Modbus-in-a-Stick has the following features:
RS485 connection to Modbus devices
Wide range DC power input. 6 to 40VDC
Configurable check-in period and Network address
Configurable Modbus register polling and/or transparent register mode
Modbus register writes to remote nodes
Full time mesh node can forward messages from other SignalFire devices
including sleeping nodes.
Sends data to a SignalFire Modbus Gateway
Integrated 500mW FHSS 900MHz ISM band radio and high gain antenna
Modbus-in-a-Stick Connections
The Modbus- in-a-stick is supplied with a 6 conductor cable. The connections are as
follows:
Wire Color Connection
RED
Positive Power (6 to 40 VDC)
BLACK
Ground
GREEN
RS-485 “A”, 9600 Baud default
BROWN
RS-485 “B”, 9600 Baud default
ORANGE
RS-232 Debug/Programming TX, 9600 Baud
YELLOW
RS-232 Debug/Programming RX, 9600 Baud
Status LED
The Modbus- in-a-stick has one LED available for field diagnostics.
LED Description
Slow Flash (3 second pause)
System is running and in communication with radio network
Fast Flash (0.5 second pause)
System is running but no network found
Solid On
System Fault, needs service.