User Manual

Table Of Contents
Configuring the operating system
6.10 Enabling PROFINET IO
Mobile Panel 277F IWLAN
Operating Instructions, 12/2007, A5E01003940-01
165
Procedure
Proceed as follows:
1. If you wish the HMI device to load the PROFIsafe address set in the Control Panel, enter
a value between 1 and 65,534 in the "Address:" text box.
2. If you wish the HMI device to load the PROFIsafe address set in the project, enter a value
between the invalid PROFIsafe address 65,535 in the "Address:" text box.
Result
The PROFIsafe address is set.
6.10 Enabling PROFINET IO
PROFINET IO
Function keys or buttons can be configured as PROFINET IO direct keys. If PROFINET IO
direct keys are used in the project, they must be enabled.
Requirements
You have opened the "PROFINET" dialog with the "PROFINET" icon.
Check box to enable or block PROFINET IO direct keys
Group for communications link
Text box for the device name

Summary of content (183 pages)