Instruction Manual February 2006 Draft Manual 02/13/2006 sitrans LR 460
Safety Guidelines: Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed. Qualified Personnel: This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
Table of Contents Part I: SITRANS LR 460 (all versions) .................................. 1 SITRANS LR 460 ...................................................................................................................2 System Implementation .........................................................................................................................3 Typical PLC/mA configuration with HART.............................................................................
Table of Cotents mmmmm Hazardous area installations .............................................................................................................22 Product Nameplate .....................................................................................................................22 Instructions specific to hazardous area installations ........................................................22 EU Equivalency ................................................................................
LCD menu structure ..........................................................................................................37 Part III: SITRANS LR 460 PROFIBUS PA version.............. 45 Remote operation via PROFIBUS PA .............................................................................46 SIMATIC PDM ........................................................................................................................................46 Device Description ......................................
Table of Cotents mmmmm Measuring Limits....................................................................................................................... 64 Detailed Setup ........................................................................................................................... 65 Output ....................................................................................................................................................72 AIFB1...........................................
Safety Notes Special attention must be paid to warnings and notes highlighted from the rest of the text by grey boxes. WARNING: relates to a caution symbol on the product, and means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage. WARNING: means that failure to observe the necessary precautions can result in death, serious injury, and/or considerable material damage.
The Manual Notes: • Please follow the installation and operating procedures for a quick, trouble-free installation and to ensure the maximum accuracy and reliability of your SITRANS LR 460. This manual applies to the SITRANS LR 460 only. This manual will help you set up your SITRANS LR 460 for optimum performance.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
SITRANS LR 460 mmmmm Short form Long Form Description Units (cont’d) µF microFarad 10-6 Farad µs microsecond 10-6 Second PA Process Automation (PROFIBUS) PDM Process Device Manager (SIMATIC) PED Pressure Equipment Directive safety approval pF pico Farads 10-12 ppm parts per million PSIA pounds/square inch absolute PV Primary Value1 RH relative humidity SCFM standard cubic feet/minute Farad measured value SELV Safety extra low voltage SV Secondary Value1 TB Transducer
SITRANS LR 460 – INSTRUCTION MANUAL Page I-1 mmmmm 7ML19985JM01 SITRANS LR 460 Part I: SITRANS LR 460 (all versions)
SITRANS LR 460 SITRANS LR 460 mmmmm SITRANS LR 460 is a long-range FMCW radar level transmitter for level measurement of solids. It can be used in high pressure applications or applications requiring gas safety approvals. The Easy Aimer design makes it easy to set up the device even in conditions of extreme dust. The narrow antenna beam creates a sharp emission cone, which makes the LR 460 quite insensitive to vessel interferences.
System Implementation SITRANS LR 460 supports HART communication protocol, and SIMATIC PDM software. Typical PLC/mA configuration with HART PLC with mA input card HART PC/laptop with HART modem running PDM S ITR A N S LR 4 00 SITRANS LR 460 Note: A 250 ohm loop resistor may be required, depending on PLC input resistance.
mmmmm SITRANS LR 460 Page I- 4 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
Specifications Note: Siemens Milltronics makes every attempt to ensure the accuracy of these specifications, but reserves the right to change them at any time. SITRANS LR 460 Power Power Supply (HART) • 100 to 230 V AC, ±15%, 50/60 Hz, 6 W (12VA) • 24 V DC, +25/-20%, 6 W • Power failure: bridge of at least 1 mains period (> 20 ms) • Fuse (AC ) SI1 Fast acting ceramic, 4 x 20 mm, 1 A, 250 V AC SI2 Slow-Blow, 4 x 20 mm, 0.
Long-term stability Update time at 4mA Beam angle ≤ ± 1 mm/year mA output and loop display is updated once per second 3" horn: 11° at –3 dB boundary 4" horn: 8° at –3 dB boundary Memory • non-volatile EEPROM • no battery required Interface Analog output (Not applicable to PROFIBUS PA option) • signal range 4 to 20 mA upper limit 20 to 22.5 mA adjustable • fail signal 3.6 mA; 22 mA; 24 mA or last value • load Max. 600 Ω; for HART1 communication min.
• • • • • ambient temperature: interface: power: weight: color: −20 to 40 °C (−5 to 104 °F) proprietary infrared pulse signal 3 V lithium battery 150 g (0.3 lb) black Mechanical Wetted parts (in contact with the process) Process Connection • universal flanges Stainless steel flange and horn; PTFE emitter 2"/50 mm, 3"/80 mm, 4"/100 mm, 6"/150 mm (See page 11 for flange dimensions.) Pressure (vessel) 0.5 bar (7.
Environmental1 • • • • • • • location altitude ambient temperature2 relative humidity installation category pollution degree Perm.
Approvals (verify against device nameplate) • Hazardous areas • General • Radio FM/CSA Class II, Div.
SITRANS LR 460 Dimensions 1 2 connection cover 204 mm (8.0") electronics cover SITRANS LR 400 Easy Aimer ball locking bolts 278 mm (10.94") universal slotted flange (see page 11 for details) reference point 165.5 mm (6.5") 228.3 mm (9.0") 291.2 mm (11.5") 100 mm (3.94") Specifications mmmmm horn extension (optional) horn antenna 50 mm (1.97") 75 mm (2.95") 100 mm (3.94") 1. Consult factory when using horn extension in applications subject to shock and vibration. 2.
Flange Dimensions Pipe Size Flange O.D. 2" or 50 mm 3" or 80 mm 4" or 100 mm 6" or 150 mm 7.87" (200 mm) 7.87" (200 mm) 9.00" (229 mm) 11.22" (285 mm) ThickBolt Hole Bolt Hole ness (s) Circle Max Ø Circle Min Ø Bolt Hole radius 0.38" (9.65 mm) 0.38" (9.65 mm) 0.38" (9.65 mm) 0.38" (9.65 mm) 0.38" (9.5 mm) 0.38" (9.5 mm) 0.38" (9.5 mm) 0.45" (11.5 mm) 4.92" (125 mm) 6.30" (160 mm) 7.52" (191 mm) 9.53" (242 mm) 4.72" (120 mm) 5.91" (150 mm) 6.89" (175 mm) 9.45" (240 mm) No.
Purged LR 460 version Requirements for effective cleaning Recommended pressure Recommended inlet flow 90 to 110 psi 10 SCFM 1 Note: Short bursts of high pressure periodically are more effective for purging than continuous low pressure. 1 purged process connection with factory-installed 1/2" NPT plug Specifications mmmmm alignment markings 1. SCFM: standard cubic feet/minute referenced to 14.
Installation WARNINGS: • SITRANS LR 460 is to be used only in the manner outlined in this manual, otherwise protection provided by the equipment may be impaired. • Installation shall only be performed by qualified personnel and in accordance with local governing regulations. • Improper installation may result in loss of process pressure Notes: • Installation must be according to ETSI EN 302372. • Refer to device nameplate for approval information.
Precautions • • • Do not mount in direct sunlight without the use of a sun shield. Avoid interference to emission cone from obstructions or from fill path. Avoid central locations on vessel. ambient temperature 65 °C (149 °F) max. Warning: Internal temperature must not exceed 85 °C (185 °F)! internal enclosure temperature flange temperature handheld programmer process temperature WARNING: For vessels with conical or parabolic tops, avoid mounting the unit at the center.
Beam Width Keep the emission cone free of obstructions. 11° 8° 3" horn 4" horn Installation in Mounting Nozzle The bottom edge of the antenna must project into the vessel to avoid reflective interference at the wall of the nozzle. If the process nozzle diameter is greater than 6", the antenna does not need to project beyond the nozzle unless the emission cone touches the nozzle wall.
Easy Aimer Installation Easy Aimer ball locking bolts top clamping plate (upper socket) bottom clamping plate (lower socket) customer gasket as required [recommended thickness 1.5 to 1.8 mm (0.06 to 0.07")] 0.38" (10 mm) customer mounting plate, as required ø 4" (102 mm) min., central opening 2" horn: 6.5" (165.5 mm) 3" horn: 9.0" (228.3 mm) 4" horn: 11.5" (291.2 mm) 30° max.
Notes SITRANS LR 460 – INSTRUCTION MANUAL Page 17 mmmmm Installation 7ML19985JM01
mmmmm Installation Page 18 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
Wiring WARNINGS: • • • • • • Turn off power to the device before unscrewing the housing cover in a hazardous area. All field wiring must have insulation suitable for at least 250 V. DC input terminals shall be supplied from an SELV source in accordance with IEC 1010-1 Annex H The equipment must be protected by a 15A fuse or circuit breaker in the building installation.
AC version 12 HART wiring1 PROFIBUS wiring2 earth terminal cable clamp 3 4 5 6 7 8 1 2 Rated temperature of connection cables must exceed maximum ambient temperature by at least 15 K mA earth terminal cable clamp 3 4 5 6 7 8 1 2 L1 L2 PROFIBUS PA N Rated temperature of connection cables must exceed maximum ambient temperature by at least 15 K L1 L2 N DC version PROFIBUS wiring2 HART wiring1 earth terminal cable clamp 3 4 5 6 7 8 mA 3. 4. 5. mmmmm Wirng 6.
7. Connect the external earth terminal located between the cable glands to a ground connection at your vessel. Use a cable with a diameter of 2.5 mm2.or greater. cable glands SIEMENS For error-free communication via the HART protocol, a load of at least 230 Ω must be available in the signal circuit.
Hazardous area installations Product Nameplate Instructions specific to hazardous area installations (Reference European ATEX Directive 94/9/EC,Annex II, 1/0/6) 1. For use and assembly, refer to the main instructions. 2. The equipment is certified for use as Category 1/2 D equipment. The Essential Health and Safety Requirements are assured by compliance with EN 50281-1-1:1998; Dust Explosion Protection. 3. The equipment may be used with dust and fibers with apparatus temperature class T.
• • • Permitted ambient temperature at the horn antenna (Category 1D): - 20 °C ≤ Tamb ≤ +200 °C Permitted ambient temperature at the electronic enclosure (Category 2D): -20 °C ≤ Tamb ≤ +65 °C Maximum permitted temperature within electronic enclosure (Category 1D): 85 °C Ambient temperature at the horn antenna (Category 1D) Maximum surface temperature at the horn antenna (Category 1D) - 20 °C ≤ Tamb ≤ + 60 °C 72 °C 70 °C at Tamb ≤ 65 °C in Category 2 - 20 °C ≤ Tamb ≤ + 100 °C 112 °C 100 °C independe
mmmmm Wirng Page 24 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
7ML19985JM01 SITRANS LR 460 (4-20 mA) – INSTRUCTION MANUAL Page II-25 mmmmm mA: Startup Part II: SITRANS LR 460 4-20 mA version
mA: Startup mmmmm 4-20 mA Start Up Only two steps are necessary for a Quick Setup (see page 29 for detailed instructions): 1. 2. Use the handheld programmer to set the PROFIBUS address locally. Use SIMATIC PDM to calibrate the four set points: High and Low Calibration Point, and High and Low Level Point. SITRANS LR 460 automatically starts up in RUN mode and detects the material level.
Programming SITRANS LR 460 To activate PROGRAM mode, point the handheld programmer at the display (from a maximum distance of 600 mm [2 ft.]), and press the Mode key . display max. 600 mm (2 ft.) handheld programmer function Keys 1 2 3 4 5 6 7 8 9 0 numeric keys C The handheld programmer has two modes of operation: 1. Navigation Mode • In this mode, the rightmost digit of the menu number flashes (the Edit Mode icon is not visible). • Press Up or Down arrow to change the menu number.
2. Edit Mode mA: Startup mmmmm Note: only parameter items can be in Edit mode. • • • In this mode, the Edit Mode icon appears and flashes. Pressing a number key enters parameter data. In the case of read-only parameters, no change is permitted. PROGRAM Mode Display Note: SITRANS LR 460 continues to monitor In and Out values even when the device is in PROGRAM mode. 1 – Menu level 2 – Parameter name 3 – Edit Mode indicator 4 – Value of current parameter 1 2 3 1.3.1 SOFT REV 0.01.
Write locking How to do a Master Reset Open the menu Device– Master Reset to access the reset options, including Factory Reset. Fault Reset This resets the Fault message after an active fault has occurred and been corrected. A manual reset is required only for certain faults, identified by an asterisk (*) in the table General Fault Codes on page 88. To reset, key in the value of the fault code in question.
1 2 3 4 , , , .,, Sensor Reference Point1 Sensor Offset2 mA: Startup mmmmm Near Range High Level Point (default: 100%) Sensor Value3 tank reference point High Calibration Point Level4 Low Level Point (default: 0%) Level Offset Low Calibration Point Secondary Value 1 Far Range Calibration – steps 1 to 7 1. 2. 3. 4. 5. 6. 7. Open the menu Device – Sensor Calibration and select the button Dry Calibration. (Click on Additional Information to see the schematic showing the PROFIBUS parameters.
Level application example Sensor Units: Sensor Reference Point1 Sensor Offset Near Range High Level Point = 100% Sensor Value SV2 High Calibration Point = 3 m Level Low Level Point = 0% Level Offset (if any) Low Calibration Point = 5 m Secondary Value 1 Far Range 1. For standard configuration reference point, seeSITRANS LR 460 Dimensions on page 10.
mmmmm mA: Startup Page II-32 SITRANS LR 460 (4-20 mA) – INSTRUCTION MANUAL 7ML19985JM01
Local Operation • • For the complete list of parameters, see Appendix A: Parameter Descriptions on page 58. LCD menu structure on page 37 gives a list of all parameters accessible via the handheld programmer, preceded by the menu number. Parameter Menu Structure The parameters are organized into function groups, and arranged in a 4-level menu structure. For example: 1. Identification 1.2. Configuration 1.2.2. Remote Lock.
C: Local Operation mmmmm Using the handheld programmer Note: For Quick Access to parameters via the handheld programmer, press the mode key to activate PROGRAM mode, then key in the menu number. Detailed instructions on using the handheld programmer start on page 25, and on doing a Quick Setup start on page 27. The following pages give details on how to programme some of the more complex SITRANS LR 460 parameters via the handheld programmer.
How to do a Master Reset 1 Values Reset all parameters (except PROFIBUS address) to PROFIBUS PA profile default values 2506 Warm Start: restart the device (this option is rarely used) 2712 Reset PROFIBUS address to 126 32768 Reset to manufacturer’s default values (factory settings)1 Example: do a Profile reset 1. Go to Reset: 1. Identification Menu 1. 2. Configuration 1.2.3. Reset 2. 3. Press the Right ARROW key to open Edit mode.
C: Local Operation mmmmm 4. Press the Right ARROW key Navigation mode. again, to accept the change and return to Device calibration Only four settings are required for a Quick Setup: High Calibration Point, Low Calibration Point, High Level Point, and Low Level Point. (For an illustration, see Calibration on page 28.) 2.3. Sensor Calibration: 2.3.1. Sensor Units (default meters) 2.3.2. Calibration Type. Values 0 1 * "Dry" calibration "Wet" calibration (not recommended for SITRANS LR 460) 2.3.3.
LCD menu structure FOR PLACEMENT ONLY - TO BE REPLACED WITH FLIPOUT PAGE 1. Identification Identification Configuration 2. Configuration 3. Device 4. Statistics 1. 2. 3. 4. 5. Address Remote Lockout Factory Reset Reset Fault Menu Timeout Device Statistics 1. Powered Hours 2. Powered Resets Input 2. Input 1. 2. 3. 4. 5. 6. Reset Filter Standard Setup Sensor Calibration’ Measuring Limits Linearization Detailed Setup Operation 1. Temperature Unit 2. PV Unit 3. Sensor Units Standard Setup 1.
FOR PLACEMENT ONLY - TO BE REPLACED WITH FLIPOUT PAGE Input Detailed Setup 1. Failsafe 2. Volume 3. Echo select 4. Echo sampling 5. Range 6. TVT setup 7. TVT shaper 8. Rate E: LCD menus mmmmm 8. Detailed Setup Failsafe 1. LOE Timer Volume Table A 1. Level 1 2. Volume 1 3. Level 2 4. Volume 2 5. Level 3 6. Volume 3 7. Level 4 8. Volume 4 Table B 1. Level 5 2. Volume 5 3. Level 6 4. Volume 6 5. Level 7 6. Volume 7 7. Level 8 8. Volume 8 Table C 1. Level 9 2. Volume9 3. Level 10 4. Volume 10 5.
3. Output Output AIFB1 1. AIFB1 2. AIFB2 3. mA Output 4. Relay Config 1. Target Mode 2. Unit 3. Filter Time Constant 4. Channel 5. Batch Information 6. Process Value Scale 7. Output Scale 8. Output Limits 9. Failsafe Mode A. Interface Batch Information 1. Batch ID 2. Batch Unit 3. Batch operation 4. Batch Phase Process Value Scale 1. Lower Value 2. Upper Value Output Scale 1. Lower Value 2. Upper Value Output Limits 1. Failsafe Mode 2. Failsafe Value Interface AIFB2 1. Target Mode 2. Unit 3.
5. Maintenance settings Maintenance settings Remaining Device Lifetime 1. Remaining Device Lifetime 2. Remaining Sensor Lifetime 3. Service Interval 4. Calibration Interval 1. 2. 3. 4. 5. 6. 7. 8. 9. Total Device Operating Time Remaining Device Lifetime Maintenance Required Limit Maintenance Demanded Limit Maintenance Alert Activation Total Expected Device Life Maintenance Status Acknowledge Status Acknowledge 1. 2. 3. 4. 5. 6. 7. 8. 9.
HART Communications Highway Addressable Remote Transducer, HART, is an industrial protocol that is superimposed on the 4-20 mA signal. It is an open standard, and full details about HART can be obtained from the HART Communication Foundation at www.hartcomm.org SITRANS LR 460 can be configured over the HART network using either the HART Communicator 275 by Fisher-Rosemount, or a software package. There are a number of different software packages available.
Sensor Lifetime Total Sensor Operating Time Remaining Sensor Lifetime Maintenance Required Limit Maintenance Demanded Limit Maintenance Alert Activation Total Expected Sensor Life Units Maintenance Status Acknowledge Status Acknowledge Service Interval D: HART Communications mmmmm Time Elapsed Since Last Service Maintenance Required Limit Maintenance Demanded Limit Maintenance Alert Activation Total Service Interval Units Maintenance Status Acknowledge Status Acknowledge Calibration Interval Time Elaps
Universal and Common Practice Commands For details on the Universal and Common Practice Commands, please contact the HART Communication Foundation. Device Specific Commands For a document containing the Device Specific Commands, please contact Siemens Milltronics at techpubs.smpi@siemens.com.
D: HART Communications mmmmm Notes Page 44 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
SITRANS LR 460 (PROFIBUS PA) – INSTRUCTION MANUAL Page III-45 mmmmm 7ML19985JM01 PA: Remote Operation Part III: SITRANS LR 460 PROFIBUS PA version
Remote operation via PROFIBUS PA SITRANS LR 460 is a Class B, Profile Version 3.0, PA device. It supports Class 1 Master for cyclic and acyclic data exchange, and Class 2 for acyclic services. The full range of SITRANS LR 460 functions is available only over a PROFIBUS PA network. PA: Remote Operation mmmmm PROFIBUS PA is an open industrial protocol. Full details about PROFIBUS PA can be obtained from PROFIBUS International at www.profibus.com.
Configuration To configure a PROFIBUS PA Class 1 Master (for example, a PLC), you will need a GSD file. The GSD file The GSD file SIEM810F.gsd is available from the SITRANS LR 460 product page on our web site. Go to https://pia.khe.siemens.com/index.asp?Nr=7427 and click Downloads. Download the DeviceInstall, and run it from your computer. This will install the GSD file into your system (as long as you are using SIMATIC software). separately, and import it with the software you are using.
Cyclic Data When you configure SITRANS LR 460 on the PROFIBUS PA bus, there are two slots available for modules. Note: Each of the slots has to have a module defined in it. PA: Remote Operation mmmmm Slot 0 always transmits AIFB1 information1; slot 1 defaults to Free Place, but can be changed to AIFB2 information. If you do not wish to have data transmitted, then you must use a Free Place module in that slot.
Status Codes for Bad Quality Values in hex notation 0x01 0X1F 0xC4 0XDE Status Codes for Uncertain Quality Values in hex notation Description 0x4B 0x4C/0x4F 0x47 Value is a substituted value (normally used in Failsafe). Initial value. Last usable value. Diagnostics All diagnostic information shown below is viewable via PDM. Diagnosis reply (applies only to cyclic masters) This is a response to a GET-DIAG message.
Acyclic Diagnostics PA: Remote Operation mmmmm This consists of four bytes.
Acyclic Extended Diagnostics (General Fault Codes) In addition to the extended diagnostics available by cyclic data exchange (shown above), further extended diagnostics are available via acyclic communications. This consists of six bytes. See Appendix B: Asynchronous Communications Data Map on page 58 , for the location of Extended Diagnostics For a table listing the fault codes, meanings, and suggested corrective action to take, see General Fault Codes on page 88.
PROFIBUS PA Profile Structure PROFIBUS Level Device Design The device follows the profile block model and is implemented as a Profile 3.0, Class B, PA device. Standard profile parameters are used to program the level transducer block. Block Model for recording and processing measured values The functions of the device are divided into blocks for different areas of responsibility. They can be parameterized by acyclic data transfer via PDM.
Description of the blocks Transducer block function groups The figure below shows the signal flow of measured values from the sensor through the Transducer block into the output value (Primary Value/ Level or Volume; Secondary Value 1 / Level; Secondary Value 2 /Distance 1; or Secondary Value 3 / Distance 2). The Level TB implements all of the basic parameters (see parameter diagram on page 54), including level to volume calculation, if that option has been selected.
2. Level Calibration is a linear transfer function that converts a sensor value to a level value. The level value is used for volume calculation, if that function is enabled.1 Level 4.5 High Level Point 4 3.5 3 Level Value 2.5 2 1.5 Low Level Point 1 0.
Electronics temperature The transducer block also monitors the internal temperature of the device electronics. If the temperature exceeds permitted limits, it does not change the sensor value, but it does change the status.The permitted limits correspond to those of the permitted ambient temperature. If a temperature limit is exceeded, the status changes. Peak indicators1 allow you to check the maximum and minimum temperatures that have occurred.
How the AIFBs work The Analog Input Function Blocks allow you to control modifications to the output value (PROFIBUS cyclic data). Output Conversion Values transmitted by the Level TB have a status attached. The decision on what to do with each value is made by the Analog Input Function Block. Device/ Input Simulation The input can be a simulated value instead of a TB OUT value. This allows the AI block to be tested independently of the characteristics of the environment.
2. The scaling output is applied. For example: Process Variable range (typical Input (0 to 100%) AIFB2 3. 4. 5. 6. Out (or AIFB2 Out) 5 4 3 2 straight to LCD (same values displayed on LCD as PLC) 1 0 1 2 3 4 5 Output range: This value is filtered using a first order filter based on a time constant provided by the user. The status of the Process Variable (input value) is checked. If the status is Bad, a Failsafe condition occurs. The output is determined by the Failsafe Mode of the block.
IQ300IX.
Appendix A: Parameter Descriptions SITRANS LR 460: parameter menus The parameters are grouped in menus according to function. Submenus, arranged on four levels, give access to associated features and options. Some menus are accessible in PDM only via pull-down menus: in those cases, directions are given beside the individual parameter. Not all menus are accessible via the handheld programmer.
1.2.4. Master Reset Note: Following a Master Reset, complete reprogramming is required. 1 Reset all parameters (except PROFIBUS address) to PROFIBUS PA profile default values 2506 Warm Start: restart the device (this option is rarely used) 2712 Reset PROFIBUS address to 126 32768 Reset to manufacturer’s default values (factory settings) Values 1.2.5. Reset Fault Resets the Fault message after an active fault has occurred and been corrected.
1.3.3. Hardware Revision Corresponds to the electronics hardware of the Field Device. Profile Revision PROFIBUS PA Profile standard that this device conforms to. Static Revision No. The revision level of the static data associated with the Physical Block. The Static Revision No. is updated whenever a standard profile configuration parameter is changed. 1.3.4. PROFIBUS Ident Number Identifies the device on the network.
1.4. Statistics1 1.4.1. Powered Hours Number of hours the unit has been powered up since manufacture. 1.4.2. Poweron Resets The number of power cycles that have occurred since manufacture. 2. Input Static Revision Number The revision level of the static data associated with the Transducer Block, updated whenever a standard profile configuration parameter is changed. Class Indicates the Level Transducer Block as per PROFIBUS PA PRofile specifications. 2.1. Reset Filter Resets the rate filter.
2.2.2. Response Rate Sets the reaction speed of the device to measurement changes in the target range.12 Related parameters Response LOE Timer1 Fill Rate Rate (minutes) 1 * Values Empty Rate slow 100 0.1 m/minute 0.1 m/minute 2 medium 10 1 m/minute 3 fast 1 10 m/minute 10 m/minute 1 m/minute Echo Lock2 2 material agitator Note: Changing Response Rate resets the following parameters: LOE Timer, Fill Rate, Empty Rate, and Echo Lock.
2.3. Sensor Calibration123 Sensor Reference Point1 (flange face) Sensor Offset High Level Point (default: 100%) tank reference point High Calibration Point Sensor Value2 Level3 Low Level Point (default: 0%) Low Calibration Point Level Offset Secondary Value 1 2.3.1. Sensor Units Whatever units the sensor is measuring in. 2.3.2. Calibration Type In "Dry" calibration, the user enters all four calibration values: High and Low Level Points, and High and Low Calibration Points.
2.3.5. Unit (Level) Selected engineering units for Level (PV). • • • Referenced from Low Level Point (plus level offset, if any) Default % Can be any linear measurement 2.3.6. Low Level Point The level when the material is at Low Calibration Point. The unit is defined in Level units. (In PDM, go to Device menu > Sensor Calibration, then click on More Information to see an illustration.) 2.3.7. High Level Point The level when the material is at High Calibration Point. The unit is defined in Level units.
2.4.5. Process Temperature Min. The minimum recorded temperature of the internal electronics. Open the menu View – Peak Values and select the tab Temperature. If necessary, click on the reset button, and download to the device. 2.4.6. Process Temperature Max. The maximum recorded temperature of the internal electronics. Open the menu View – Peak Values and select the tab Temperature. If necessary, click on the Reset button, and download to the device. 2.5. Detailed Setup 2.5.1. Failsafe 2.5.1.1.
2.5.3. Echo Sampling 2.5.3.1. Sampling up1 Once echo is outside the window, a specified number of consecutive echoes must appear above the echo locked onto, before measurement is accepted as valid. 2.5.3.2. Sampling down1 Once echo is outside the window, a specified number of consecutive echoes must appear below the echo locked onto, before measurement is accepted as valid. 2.5.3.3. Window1 A "distance window" centered on the echo, used to derive the reading.
2.5.4.2. Far Range (HI RANGE) Note: Far Range can extend beyond the bottom of the tank. Maximum distance from the reference point2, within which an echo should be considered valid. Range: 0 to 20 m Values Default: Low Calibration Point Echo Profile Echo Confidence Measures echo reliability. It displays the echo confidence of the measurement echo from the last shot. Confidence Threshold defines the minimum criterion for echo confidence.
2.5.5. TVT (Auto False Echo Suppression) setup Note: The Auto False Echo Suppression parameters are for authorized Siemens Milltronics Service personnel or technicians familiar with Siemens Milltronics echo processing techniques. View the echo profile first, before attempting to modify these parameters. First SITRANS LR 460 learns the echo profile. Then the learned profile, or part of the learned profile, is used to screen out false echoes. 2.5.5.1.
Display before Auto False Echo Suppression Window Level (db) Default TVT TVT Hover Level Echo Marker Distance (meters) Example after Auto False Echo Suppression Liquid level Level (db) TVT curve (Learned) False echo Distance (meters) Curves to be updated to SITRANS LR 460 curves. Adjusts the TVT curve at a specified range. Parameters mmmmm 2.5.5.8.
2.5.6. TVT shaper A breakpoint on the TVT curve, normalized to 0. 2.5.6.1. Shaper A (1-9) 2.5.6.2. Shaper B (10-18) 2.5.6.3. Shaper C (19-27) 2.5.6.4. Shaper D (28-36) 2.5.6.5. Shaper E (37 - 40) 2.5.7. Rate 2.5.7.1. Fill Rate Defines the maximum rate at which the reported sensor value is allowed to increase.Allows you to further adjust the LR 460 response to increases in the actual material level (or an advance to a higher Failsafe Material Level, P071).
2.5.7.2. Empty rate Defines the maximum rate at which the reported sensor value is allowed to decrease.Adjusts the LR 460 response to decreases in the actual material level. Empty Rate is automatically updated whenever Response Rate is altered. Range: 0.0000 to 99999 m / min. Values Factory setting: 0.1 Altered by Response Rate Related Units (Level) High Level Point Enter a value slightly greater than the vessel’s maximum emptying rate, in Sensor Units per minute.
3. Output 3.1. AIFB1 Static Revision No. The revision level of the static data associated with Analog Input Function Block 1. The Static Revision No. is updated whenever a standard profile configuration parameter is changed. 3.1.1. Target Mode Used to request an operating mode from the Function Block.
3.1.6. Process Value Scale 3.1.6.1. Lower Value Defines the operational lower range value of the input value (Process Value Scale) in engineering units. Process Value Scale normalizes the input value to a customer-defined range. 3.1.6.2. Upper Value Process Value Scale (typical Input (0 to 100%) Defines the operational upper range value of the input value (Process Value Scale) in engineering units. Process Value Scale normalizes the input value to a customer-defined range.
3.1.8.5. Limit Hysteresis Hysteresis is used to adjust the sensitivity of the trigger for alarm messages. It is used to compensate when a process variable fluctuates around the same value as a limit. A high level alarm occurs when a value exceeds an upper limit. The alarm’s status remains true until the value drops below the limit minus the alarm hysteresis. The directions are reversed for low limit detection. Enter a value for the hysteresis here, to be used for all warnings and alarms.
Certificates and Approvals Device Certification 5. Maintenance settings 5.1. Remaining Device Lifetime 5.1.1. 5.1.2. 5.1.3. 5.1.4. 5.1.5. 5.1.6. 5.1.7. 5.1.8. 5.1.9. 5.1.10. Total Device Operating Time Remaining Device Lifetime Maintenance Required Limit Maintenance Demanded Limit Maintenance Alert Activation Total Expected Device Life Units Maintenance Status Acknowledge Status Acknowledge 5.2. Remaining Sensor Lifetime 5.2.1. 5.2.2. 5.2.3. 5.2.4. 5.2.5. 5.2.6. 5.2.7. 5.2.8. 5.2.9. 5.2.10.
5.4. Calibration Interval 5.4.1. 5.4.2. 5.4.3. 5.4.4. 5.4.5. 5.4.6. 5.4.7. 5.4.8. 5.4.9. Time Elapsed Since Last Calibration Maintenance Required Limit Maintenance Demanded Limit Maintenance Alert Activation Total Calibration Interval Units Maintenance Status Acknowledge Status Acknowledge 6. Condensed Status Setup 6.1. Condensed Status Mode Event Index Event Status Event Diagnosis 6.1.1. Loss of Echo S0 (Status; Diagnosis) 6.1.2. Cable Fault S1 (Status; Diagnosis) 6.1.3.
mmmmm Parameters Page 81 SITRANS LR 460 – INSTRUCTION MANUAL 7ML19985JM01
SITRANS LR 460 is a long range FMCW (Frequency Modulated Continuous Wave) radar transmitter. Radar level measurement uses the time of flight principle to determine distance to a material surface. The transmit time is directly proportional to the distance to the material. FMCW radar transmits a continuous wave. The frequency of the wave is constantly increasing: this is known as the sweep.
F: Technical Reference mmmmm Echo Lock When the echoes are received, the relevant echo algorithm is applied to determine the true material echo. If the selected echo is within the window, the window is then centered about the echo. Otherwise the window widens with each successive shot until the selected echo is within the window, which then returns to its normal width.
Failsafe Mode Failsafe mode may be triggered by a loss of echo, a bad configuration, or certain device faults. You can select can select one of three possible values to be reported when a Failsafe mode occurs: • • • Default value (Failsafe value) used as output value. Store last valid output value. Calculated output value is incorrect. Failsafe value Failsafe value is a user-defined value. This allows you to enter the safest output value for your application.
F: Technical Reference mmmmm When you set Auto False-Echo Suppression to Learn, the instrument learns the echo profile at that moment1. Then it uses the learned profile instead of the default TVT curve, for the distance set in Auto False Echo Suppression Distance. The learned profile (learned TVT curve) follows the echo profile, so that no large false echoes rise above the learned TVT curve. From the end of the Auto False-Echo Suppression Distance, the default TVT curve is used.
460 information. . Ambient Temperature (oC) Maximum Flange and Process Temperatures versus Allowable Ambient for Polypropylene Rod or Flange Adaptor versions of SITRANS LR 200 polypropylene rod temperature (no flange) flange temperature process temperature Process Flange Surface Temperature (oC) • The chart does not represent every possible process connection arrangement.
Appendix C: Troubleshooting 1. Check the following: • • • G: Troubleshooting mmmmm • There is power at the instrument. The LCD shows the relevant data. Check whether any fault codes are being displayed (see Acyclic Extended Diagnostics (General Fault Codes) on page 51 for a detailed list). The device can be programmed using the handheld programmer. 2. Verify that the wiring connections are correct. 3. Check the PROFIBUS address and make sure all devices are at unique PROFIBUS addresses. 4.
General Fault Codes Note: Some faults cause the device to go to Failsafe mode (Fault 52). These are indicated with an asterisk (*). LCD display The device was unable to get a measurement within the Failsafe timer period. Possible causes: faulty installation, material buildup,and/or presence of foam. Ensure installation details are correct. Ensure no material buildup. Adjust process conditions to minimize foaming. If problem persists, contact your local Siemens representative.
G: Troubleshooting mmmmm LCD display Page 89 Meaning (cont’d) Byte Bit (cont’d) Corrective Action S:8 Service interval as defined in Perform service. Maintenance Required Limit has expired. 0 S:9 Service interval as defined in Perform service. Maintenance Demanded Limit has expired. 1 S:10 Input parameters High Calibration Point and Low Calibration Point are the same. Check calibration settings of device. Ensure settings for High Calibration Point and Low Calibration Point are different.
LCD display Byte Bit (cont’d) Meaning (cont’d) Corrective Action S: 17 Calibration interval as defined in Maintenance Required Limit has expired. Perform calibration. S: 18 Calibration interval as defined in Maintenance Perform calibration. Demanded Limit has expired. S:28 Repair required: contact your Internal device failure caused local Siemens by a memory error. representative. 4 S:29 EEPROM damaged. Repair required: contact your local Siemens representative. 5 S:30 EEPROM corrupt.
G: Troubleshooting mmmmm LCD display Page 91 Byte Bit (cont’d) Meaning (cont’d) Corrective Action S:34 Factory calibration for the device has been lost. Repair required: contact your local Siemens representative. 2 S:35 Factory calibration for the device has been lost. Repair required: contact your local Siemens representative. 3 S:36 Unable to start microwave module. Reset power. If error persists, contact your local Siemens representative. S:37 Unable to collect profile.
Appendix D: Maintenance SITRANS LR 460 requires no maintenance or cleaning under normal operating conditions. Under severe operating conditions, the antenna may require periodic cleaning. If cleaning becomes necessary: • Note the antenna material and the process medium, and select a cleaning solution that will not react adversely with either. • Remove the instrument from service and wipe the antenna clean using a cloth and suitable cleaning solution.
Appendix E: Software Revision History Software Rev. DD Rev. Date Changes • • • • • N: sorftware rev.
Glossary accuracy: degree of conformity of a measure to a standard or a true value. agitator: mechanical apparatus for mixing or aerating. A device for creating turbulence. algorithm: a prescribed set of well-defined rules or processes for the solution of a problem in a finite number of steps. ambient temperature: the temperature of the surrounding air that comes in contact with the enclosure of the device.
confidence: describes the quality of an echo. HIgher values represent higher quality. Confidence threshold defines the minimum value. damping: term applied to the performance of an instrument to denote the manner in which the measurement settles to its steady indication after a change in the value of the level. dB (decibel): a unit used to measure the amplitude of signals. derating: to decrease a rating suitable for normal conditions according to guidelines specified for different conditions.
frequency: the number of periods occurring per unit time. Frequency may be stated in cycles per second. hertz (Hz): unit of frequency, one cycle per second. 1 Gigahertz (GHz) is equal to 109 Hz. horn antenna: a conical, horn-shaped antenna which focuses microwave signals. The larger the horn diameter, the more focused the radar beam. inductance: the property of an electric circuit by virtue of which a varying current induces an electromotive force in that circuit or in a neighboring circuit.
radar: radar is an acronym for RAdio Detection And Ranging. A device that radiates electromagnetic waves and utilizes the reflection of such waves from distant objects to determine their existence or position. range: distance between a transmitter and a target. range extension: the distance below the zero percent or empty point in a vessel. relative permittivity: see dielectric constant. repeatability: the closeness of agreement among repeated measurements of the same variable under the same conditions.
acyclic extended diagnostics 51 fault reset 29 Index G GSD file 47 A abbreviations list 3 accuracy 5 acyclic diagnostics fault codes 50 address 58 agitator blade detection avoiding 62 agitators 62 approvals 9 Auto False-Echo Suppression 84 B beam spreading 15 blanking see Near Range 84 bus address (device address) 47 bus termination 47 C I local operation enable 28, 34 LOE timer 83 loss of echo 83 M maintenance cleaning 92 maintenance settings 41, 75 master reset 29 material mixers 62 measurement re
P power consumption 47 primary region PROGRAM mode 28 RUN mode 26 Primary Value 55 process temperature maximum 86 Process Variable 55 PROFIBUS address 58 setting 47 program mode icon 28 R remote operation enable 28 repair cautions 92 excluded liability 92 resetting a parameter to factory setting 35 Index mmmmm S safety marking symbols 1 safety notes 1 secondary region PROGRAM mode 28 Secondary Value 55 security 28 SIMATIC PDM overview 46 specifications 5 approvals 9 communication 8 performance 5 power 5
www.siemens.com/processautomation Siemens Milltronics Process Instruments Inc. 1954Technology Drive, P.O. Box 4225 Peterborough, ON, Canada K9J 7B1 Tel: (705) 745-2431 Fax: (705) 741-0466 Email: techpubs.smpi@siemens.com Siemens Milltronics Process Instruments Inc. 2006 Subject to change without prior notice *7ml19985JM01* Printed in Canada Rev. 1.