User's Manual

Table Of Contents
SITRANS LR250 (FOUNDATION FIELDBUS)
Operating Instructions, 01/2014, A5E32221411-AB
129
Parameter reference
8
Note
See
Enter PROGRAM
mode under LCD Display (Page 39) for detailed instructions.
To view a particular parameter in AMS, see Operating via AMS Device Manager
(Page 63).
Do not use the handheld programmer at the same time as AMS Device Manager, or
erratic operation may result.
For Quick Access to parameters via the handheld programmer, press
Home
, then
enter the menu number, for example:
2.2.1.
to access parameter
Hardware Revision
(2.2.1.)
.
In Navigation mode
, ARROW keys ( )
navigate the menu in the direction of
the arrow.
Press
RIGHT arrow
to open
Edit
Mode, or to save a modification.
Parameters are identified by name and organized into function groups. Menus arranged on up to
four levels give access to associated features and options. See LCD menu structure (Page 255)
for a chart.
Parameters noted as
Read Only
in this section of the manual can not be written via the LUI,
however they may be accessible via other tools. For those accessible via AMS Device Manager,
directions are shown in section
Operating via AMS Device Manager
on the pages referenced.
Quick Start Wizard
The Quick Start Wizard groups together all the settings you need to configure a device for a
simple application. You can access it either via AMS Device Manager or via the handheld
programmer.
Do not use the Quick Start Wizard via the handheld programmer to modify individual
parameters. (Perform customization only after the Quick Start has been completed.)
Each time the Quick Start Wizard is initiated via the handheld programmer, the startup
settings are factory defaults. The Wizard will not recall previous user-defined settings. (Note:
Values set using the Quick Start Wizard via AMS Device Manager are saved and recalled
each time it is initiated.)
When using AMS Device Manager, the Resource and LTB Blocks must be set to Out of
Service mode before any configuration changes (changes to parameters affecting block
output) can be written. The blocks do not need to be set to Out of Service when the Quick
Start Wizard is initiated via the handheld programmer.

Summary of content (142 pages)