Radar Transmitters SITRANS LR250 (Foundation Fieldbus) Operating Instructions 01/2014 SITRANS
Safety Guidelines Warning notices must be observed to ensure personal safety as well as that of others, and to protect the product and the connected equipment. These warning notices are accompanied by a clarification of the level of caution to be observed. Qualified Personnel This device/system may only be set up and operated in conjunction with this manual. Qualified personnel are only authorized to install and operate this equipment in accordance with established safety practices and standards.
SITRANS LR250 (FOUNDATION 1 ___________________ Introduction FIELDBUS) 2 ___________________ Safety notes 3 ___________________ Description SITRANS 4 ___________________ Installing/mounting Radar Transmitters SITRANS LR250 (FOUNDATION FIELDBUS) 5 ___________________ Connecting Operating Instructions 7 ___________________ Remote operation 6 ___________________ Commissioning 8 ___________________ Parameter reference 9 ___________________ Service and maintenance Diagnosing and 10 ___________________
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 2 3 4 5 Introduction ............................................................................................................................................. 9 1.1 The manual .................................................................................................................................... 9 1.2 Firmware revision history .............................................................................................................10 Safety notes .............
Table of contents 6 7 5.3.3 5.3.4 Non-sparking wiring .................................................................................................................... 35 Non-incendive wiring (US/Canada only) ..................................................................................... 35 5.4 Instructions specific to hazardous area installations ................................................................... 36 Commissioning .............................................................
Table of contents 7.1.11.1 7.1.11.2 7.1.11.3 7.1.12 7.1.12.1 7.1.12.2 7.1.12.3 7.1.12.4 7.1.12.5 7.1.12.6 7.1.13 7.1.13.1 7.1.13.2 7.1.14 7.1.14.1 7.1.15 7.1.15.1 7.1.16 7.1.16.1 7.1.16.2 7.1.17 7.1.18 7.1.18.1 7.1.19 8 Parameter reference ........................................................................................................................... 129 8.1 9 10 11 Identification (DIAG) ........................................................................................................
Table of contents 12 A 11.6 Process ..................................................................................................................................... 202 11.7 Approvals .................................................................................................................................. 203 11.8 Programmer (infrared keypad) .................................................................................................. 204 Dimension drawings .......................
Table of contents B Appendix B: Communications via Foundation Fieldbus........................................................................ 249 B.1 C Field Communicator 375 (F375) ................................................................................................249 Appendix C: Certificates and support .................................................................................................. 251 C.1 Certificates ..................................................................
Table of contents SITRANS LR250 (FOUNDATION FIELDBUS) 8 Operating Instructions, 01/2014, A5E32221411-AB
Introduction 1.1 1 The manual This manual will help you set up your radar device for optimum performance. For other Siemens Milltronics level measurement manuals, go to: Siemens level (http://www.siemens.com/level) Follow these operating instructions for quick, trouble-free installation, and maximum accuracy and reliability of your device. We always welcome suggestions and comments about manual content, design, and accessibility. Please direct your comments to: Technical publications (mailto:techpubs.
Introduction 1.2 Firmware revision history 1.2 Firmware revision history This history establishes the correlation between the current documentation and the valid firmware of the device. The documentation of this edition is applicable for the following firmware: Firmware rev. PDM EDD rev. Date Changes 1.01.00 1.01.00 25 Feb 2010 • Initial release. 1.01.04 1.01.00 2 Aug 2011 • Threaded PVDF antenna supported. 1.01.05 1.01.00 31 Oct 2012 • Antenna parameter removed.
2 Safety notes 2.1 Safety marking symbols In manual On product Description (Label on product: yellow background.) WARNING: refer to accompanying documents (manual) for details. 2.2 FCC Conformity US Installations only: Federal Communications Commission (FCC) rules WARNING Changes or modifications not expressly approved by Siemens Milltronics could void the user’s authority to operate the equipment.
Safety notes 2.3 CE Electromagnetic Compatibility (EMC) Conformity 2.
3 Description 3.1 SITRANS LR250 overview WARNING SITRANS LR250 is to be used only in the manner outlined in this manual, otherwise protection provided by the device may be impaired. SITRANS LR250 is a 2-wire 25 GHz pulse radar level transmitter for continuous monitoring of liquids and slurries in storage vessels including high pressure and high temperature, to a range of 20 meters (66 feet). It is ideal for small vessels and low dielectric media.
Description 3.2 Programming 3.2 Programming This device is very easy to install and configure via a graphical local user interface (LUI). You can modify the built in parameters either locally via the Siemens infrared handheld programmer, or from a remote location using one of the following options: ● FF host system ● AMS Device Manager 3.3 Applications ● liquids and slurries ● bulk storage vessels ● simple process vessels 3.
Installing/mounting 4 WARNING • Installation shall only be performed by qualified personnel and in accordance with local governing regulations. • Handle the device using the enclosure, not the process connection tag, to avoid damage. • Take special care when handling the threaded PVDF and Flanged encapsulated antennas. Any damage to the antenna surface, particularly to the tip/lens, could affect performance.
Installing/mounting 4.1 Pressure applications 4.1 Pressure applications WARNING Pressure applications • Never attempt to loosen, remove, or disassemble process connection or device housing while vessel contents are under pressure. • The user is responsible for the selection of bolting and gasket (except for Flanged encapsulated antenna) materials which will fall within the limits of the process connection and its intended use and which are suitable for the service conditions.
Installing/mounting 4.2 Mounting location 4.2 Mounting location Note • Correct location is key to a successful application. • Avoid reflective interference from vessel walls and obstructions by following the guidelines below: 4.2.1 Nozzle design Threaded PVDF antenna Stainless steel horn antenna Flanged encapsulated antenna ① Minimum clearance: 10 mm (0.4") ② Minimum diameter: 50 mm (2") ③ Maximum nozzle length: 500 mm (20") ● The end of the antenna must protrude a minimum of 10 mm (0.
Installing/mounting 4.2 Mounting location 4.2.2 Nozzle location ● Avoid central locations on tall, narrow vessels ● Nozzle must be vertical Preferred Undesirable Environment ● Provide an environment suitable to the housing rating and materials of construction. ● Provide a sunshield if the device will be mounted in direct sunlight.
Installing/mounting 4.2 Mounting location Beam angle Note • Beam width depends on antenna size: see below. • For details on avoiding false echoes, see Auto False Echo Suppression (Page 236). ● Beam angle is the width of the cone where the energy density is half of the peak energy density. ● The peak energy density is directly in front of and in line with the antenna. ● There is a signal transmitted outside the beam angle, therefore false targets may be detected.
Installing/mounting 4.2 Mounting location 4.2.3 Orientation in a vessel with obstructions Polarization reference point For best results on a vessel with obstructions, or a stillpipe with openings, orient the front or back of the device toward the obstructions. For an illustration, see Device orientation (Page 21). ① ② ③ 4.2.
Installing/mounting 4.2 Mounting location 4.2.5 Stillpipe or Bypass Pipe requirements ● The pipe diameter must be matched with the antenna size. Use the largest antenna size that will fit the stillpipe/bypass pipe1). See Threaded Horn dimensions (Page 205) or Raised-Face Flange per EN 1092-1 (Page 222). ● One continuous length of metallic pipe is preferred, without joints. Bad joints create reflections. ● Joints (if unavoidable) must be machined to ± 0.25 mm (± 0.
Installing/mounting 4.3 Installation instructions 4.3 Installation instructions WARNING For pressure applications, it will be necessary to use PTFE tape or other appropriate thread sealing compound, and to tighten the process connection beyond hand-tight. (The maximum recommended torque for Threaded versions is 40 N-m (30 ft.lbs.) See Flange bolting, Flanged encapsulated antenna only (Page 23) for FEA recommended torque values.
Installing/mounting 4.4 Flange bolting, Flanged encapsulated antenna only 4.4 Flange bolting, Flanged encapsulated antenna only Note • Use spring washers • Do not use additional gasket • Use recommended torque values for tightening bolts Flange bolting: recommended torque Pressure class ASME B16.
Installing/mounting 4.4 Flange bolting, Flanged encapsulated antenna only Recommendations for flange bolting: ● Use cross-pattern sequence as shown ● Check uniformity of the flange gap ● Apply adjustments by selective tightening if required ● Torque incrementally until desired value is reached ● Check/re-torque after 4 to 6 hours ● Check bolts periodically, re-torque as required ● Use new lens, O-ring and spring washers after removal from installation.
5 Connecting 5.1 Power WARNING The DC input terminals shall be supplied from a source providing electrical isolation between the input and output, in order to meet the applicable safety requirements of IEC 61010-1. Note All field wiring must have insulation suitable for rated voltages.
Connecting 5.2 Connecting SITRANS LR250 5.2 Connecting SITRANS LR250 WARNING • Check the nameplate on your device, to verify the approval rating. • Use appropriate conduit seals to maintain IP or NEMA rating. • See Wiring setups with Foundation Fieldbus for hazardous areas (Page 30). Note • Separate cables and conduits may be required to conform to standard instrumentation wiring practices or electrical codes.
Connecting 5.2 Connecting SITRANS LR250 Wiring instructions 1. Strip the cable jacket for approximately 70 mm (2.75") from the end of the cable, and thread the wires through the gland. (If cable is routed through conduit, use only approved suitablesize hubs for waterproof applications.) 2. Connect the wires to the terminals as shown: the polarity is identified on the terminal block. 3. Ground the device according to local regulations. 4. Tighten the gland to form a good seal. 5.
Connecting 5.2 Connecting SITRANS LR250 5.2.
Connecting 5.
Connecting 5.3 Wiring setups with Foundation Fieldbus for hazardous areas 5.3 Wiring setups with Foundation Fieldbus for hazardous areas There are three wiring options for hazardous area installations: ● Intrinsically safe wiring (Page 32) ● Non-sparking wiring (Page 35) ● Non-incendive wiring (US/Canada only) (Page 35) In all cases, check the nameplate on your instrument, confirm the approval rating, and perform installation and wiring according to your local safety codes. 5.3.
Connecting 5.
Connecting 5.3 Wiring setups with Foundation Fieldbus for hazardous areas 5.3.2 Intrinsically safe wiring Device nameplate (ATEX/IECEx/C-TICK) ① ATEX certificates The ATEX certificates listed on the nameplate can be downloaded from our website: Product page (http://www.siemens.com/LR250) Go to Support > Approvals / Certificates. The IECEx certificate listed on the nameplate can be viewed on the IECEx website. Go to: IECEx (http://iecex.iec.
Connecting 5.3 Wiring setups with Foundation Fieldbus for hazardous areas Entity concept: The Entity Concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in such combination.
Connecting 5.3 Wiring setups with Foundation Fieldbus for hazardous areas FISCO Concept Note For complete details and instructions regarding the FISCO Concept The FM/CSA connection drawing number A5E02358161 can be downloaded from our website at: Product page (http://www.siemens.com/LR250) Go to Support > Installation Drawings > Level Measurement > SITRANS LR250. The FISCO Concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in such combination.
Connecting 5.3 Wiring setups with Foundation Fieldbus for hazardous areas 5.3.3 Non-sparking wiring The ATEX certificate listed on the nameplate can be downloaded from our website: ① ATEX certificate Product page (http://www.siemens.com/LR250) Go to: Support > Installation drawings > Level measurement > SITRANS LR250. ● For wiring requirements follow local regulations. ● Approved dust-tight and water-tight conduit seals are required for outdoor NEMA 4X / type 4X / NEMA 6, IP67, IP68 locations. 5.3.
Connecting 5.4 Instructions specific to hazardous area installations 5.4 Instructions specific to hazardous area installations (Reference European ATEX Directive 94/9/EC, Annex II, 1/0/6) The following instructions apply to equipment covered by certificate number SIRA 06ATEX2353X and 09ATEX4354X: 1. For use and assembly, refer to the main instructions. 2. The equipment is certified for use as Category 1GD equipment per SIRA 06ATEX2353X, and Category 3G equipment per SIRA 09ATEX4354X. 3.
6 Commissioning 6.1 Operating via the handheld programmer 6.1.1 Power up Power up the device. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed. SITRANS LR250 automatically starts up in Measurement mode. The first time the device is configured, you will be prompted to select a language (English, German, French, Spanish or Chinese).To change the language again, see Language (7.).
Commissioning 6.1 Operating via the handheld programmer 6.1.2 Handheld programmer functions The radar device carries out its level measurement tasks according to settings made via parameters. The settings can be modified locally via the Local User Interface (LUI) which consists of an LCD display and a handheld programmer. A Quick Start Wizard provides an easy step-by-step procedure to configure the device for a simple application.
Commissioning 6.1 Operating via the handheld programmer 6.1.2.
Commissioning 6.1 Operating via the handheld programmer PROGRAM mode display Navigation view ① ② ③ Current menu Menu bar ④ ⑤ Current item number Current item Item band ● A visible menu bar indicates the menu list is too long to display all items. ● A band halfway down the menu bar indicates the current item is halfway down the list. ● The depth and relative position of the item band on the menu bar indicates the length of the menu list, and approximate position of the current item in the list.
Commissioning 6.1 Operating via the handheld programmer 6.1.2.2 Handheld programmer (Part No. 7ML1930-1BK) The programmer is ordered separately. Key functions in measurement mode Key Function Result Updates internal enclosure temperature reading. Updates echo confidence value. New value is displayed in LCD secondary region. Updates distance measurement. Mode opens PROGRAM mode.
Commissioning 6.1 Operating via the handheld programmer 6.1.3 Programming Note • While the device is in PROGRAM mode the output remains active and continues to respond to changes in the device. • The device automatically returns to Measurement mode after a period of inactivity in PROGRAM mode (between 15 seconds and 10 minutes, depending on the menu level). Change parameter settings and set operating conditions to suit your specific application.
Commissioning 6.1 Operating via the handheld programmer 1. Enter PROGRAM mode ● Point the programmer at the display from a maximum distance of 300 mm (1 ft). ● RIGHT arrow ● Mode activates PROGRAM mode and opens menu level 1. opens the menu level last displayed in PROGRAM mode within the last 10 minutes, or menu level 1 if power has been cycled since then.
Commissioning 6.1 Operating via the handheld programmer 2. Navigating: key functions in Navigation mode Note • In Navigation mode ARROW keys move to the next menu item in the direction of the arrow. • For Quick Access to parameters via the handheld programmer, press Home , then enter the menu number, for example: Volume (2.4.1.), press 2.4.1.
Commissioning 6.1 Operating via the handheld programmer 3. Editing in PROGRAM mode 1. Navigate to the desired parameter. 2. Press RIGHT arrow to open parameter view. 3. Press RIGHT arrow again to open Edit mode. The current selection is highlighted. Scroll to a new selection. 4. Press RIGHT arrow to accept it. The LCD returns to parameter view and displays the new selection.
Commissioning 6.1 Operating via the handheld programmer Changing a numeric value 1. Navigate to the desired parameter. 2. Press RIGHT arrow to open parameter view. The current value is displayed. 3. Press RIGHT arrow again to open Edit mode. The current value is highlighted. 4. Key in a new value. 5. Press RIGHT arrow to accept it. Press RIGHT arrow to accept it.The LCD returns to parameter view and displays the new selection.
Commissioning 6.1 Operating via the handheld programmer Key functions in edit mode Key Name Function UP or DOWN arrow Selecting options Numeric editing RIGHT arrow Selecting options Numeric editing LEFT arrow: Scrolls to item.
Commissioning 6.1 Operating via the handheld programmer 6.1.3.1 Quick Start Wizard via the handheld programmer_note Note • A reset to factory defaults should be performed before running the Quick Start Wizard if the device has been used in a previous application. See Master Reset (4.1.). • The Quick Start wizard settings are inter-related and changes apply only after you select Finish in the Wizard Complete step.
Commissioning 6.1 Operating via the handheld programmer Material Selects the appropriate echo processing algorithms for the material [see Position Detect (2.5.7.2.) for more detail]. Options * LIQUID LIQUID LOW DK a) (low dielectric liquid – CLEF algorithm enabled) a) dK < 3.0 Response rate Sets the reaction speed of the device to measurement changes in the target range. Use a setting just faster than the maximum filling or emptying rate (whichever is greater). Options * Response rate (2.3.8.1.
Commissioning 6.1 Operating via the handheld programmer Units Sensor measurement units. Options m, cm, mm, ft, in Default: m Operation Operation Description NO SERVICE Measurement and associated loop current are not updated, and the device defaults to Fail-safe mode a).
Commissioning 6.1 Operating via the handheld programmer ① ② ③ ④ ⑤ ⑥ Space Level Distance High calibration point (process full level) Sensor reference point a) Low calibration point (process empty level) The point from which High and Low Calibration points are referenced: see Dimension drawings (Page 205). a) Low calibration point Distance from Sensor Reference to Low Calibration Point: usually process empty level. (See Operation for an illustration.) Values Range: 0.00 to 20.
Commissioning 6.1 Operating via the handheld programmer Wizard complete Options BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wiz menu when Quick Start is successfully completed.) Press DOWN arrow (Finish). Then press LEFT arrow to return to Measurement mode. SITRANS LR250 is now ready to operate. 6.1.3.2 Auto False Echo Suppression If you have a vessel with known obstructions, we recommend using Auto False Echo Suppression to prevent false echo detection.
Commissioning 6.1 Operating via the handheld programmer 6.1.3.3 Requesting an Echo Profile • In PROGRAM mode, navigate to: Level Meter > Diagnostics (3.) > Echo Profile (3.1.) • Press RIGHT arrow ① ② ③ ④ ⑤ ⑥ to request a profile.
Commissioning 6.1 Operating via the handheld programmer 6.1.3.4 Device Address Note The address can only be changed from a remote master such as NI-FBUS Configurator or DeltaV. See Addressing in manual Foundation Fieldbus for Level Instruments (7ML19985MP01) for further details. Read only. The unique address of the device on the network. Values Temporary range during initial commissioning: 248 - 251.
Commissioning 6.2 Application examples 6.2 Application examples Note In the applications illustrated below, values are for example purposes only. You can use these examples as setup references. Enter the values in the parameter tables to select the corresponding functions. Configure the basic settings using the Quick Start wizard parameters. (These parameters are inter-related, and changes take effect only after you select FINISH in final step: Wizard Complete.
Commissioning 6.2 Application examples 6.2.1 Liquid resin in storage vessel, level measurement Note Minimum distance from flange face to target is limited by Near Range (2.5.1.). To obtain level measurement/4 to 20 mA output proportional to resin levels: ● Low Calibration Pt. = 5 m (16.5 ft) from sensor reference point ● High Calibration Pt.= 0.5 m (1.64 ft) from sensor reference point ● Max.fill/empty rate = 0.2 m/min (0.
Commissioning 6.2 Application examples Parameter type Independent parameters Parameter No. /Name Options/ Values Function Response Rate MED Medium =1 m/minute Units M meters Low Calibration Point 5 5 m (16.4 ft) High Calibration Point 0.5 0.5 m (1.64 ft) Wizard Complete FINISH Transfers Quick Start settings to device. Loss of Echo (LOE) Timer (2.3.6.) 120 120 seconds Return to Measurement: press Mode to start normal operation.
Commissioning 6.2 Application examples 6.2.2 Horizontal vessel with volume measurement Note The minimum distance from the flange face to the target is limited by Near Range (2.5.1.). To obtain level measurement proportional to vessel volume in a chemical vessel: ● Low Calibration Point = 3.5 m (11.48 ft) from sensor reference point ● High Calibration Point = 0.5 m (1.64 ft) from sensor reference point ● Max. fill/empty rate = 0.2 m/min (0.
Commissioning 6.2 Application examples Parameter type Parameter Name Options/ Values Function Independent parameters Vessel Shape (2.4.1.1.) PARABOLIC ENDS Defines vessel shape. PV (volume/level) Units (2.3.3.) L liters Level Unit (2.3.2.) M meters Maximum Volume (2.4.1.2.) 8000 8000 liters Dimension A (2.4.1.3.) 0.8 0.8 m (2.62 ft) Dimension L (2.4.1.4.) 6 6 m (19.68 ft) Loss of Echo (LOE) Timer (2.3.6.
Commissioning 6.2 Application examples 6.2.3 Application with stillpipe A stillpipe is recommended for products with a dK of less than 3, or if extremely turbulent or vortex conditions exist. This mounting arrangement can also be used to provide optimum signal conditions on foaming materials. A stillpipe is recommended for products with a dK of less than 3, or if extremely turbulent or vortex conditions exist.
Commissioning 6.2 Application examples Parameter type Parameter No./Name Options/Values Function Quick Start Wizard parameters Introduction NEXT Continue with Wizard. Language NEXT Continue with current language. Material LIQUID LOW DK Response Rate MED Medium =1 m/minute Units M meters Operating mode LEVEL Level is reported as Volume when a vessel shape is selected. Low Calibration Point 5 5 m (16.4 ft) High Calibration Point 0.5 0.5 m (1.
Commissioning 6.2 Application examples Propagation Factor/Stillpipe Diameter Values Range 0.3 to 1.0 depending on pipe size Default 1.0000 40 mm (1.5") 50 mm (2") 80 mm (3") 100 mm (4") Propagation Factor 0.9844 0.988 0.9935 0.9965 CLEF Range (2.5.7.4.) settings Low calibration point - 700 mm (2.29 ft)b) Low calibration point - 700 mm (2.29 ft)b) Low calibration point - 1000 mm (3.28 ft)b) Low calibration point - 1000 mm (3.
Remote operation 7.1 7 Operating via AMS Device Manager AMS Device Manager is a software package that monitors the process values, alarms and status signals of the device. Please consult the operating instructions or online help for details on using AMS Device Manager. You can find more information at: Emerson (http://www.emersonprocess.com/AMS/) 7.1.1 Functions in AMS Device Manager Note Do not use the handheld programmer at the same time as AMS Device Manager, or erratic operation may result.
Remote operation 7.1 Operating via AMS Device Manager Each function group is further divided into four blocks: ● Level Transducer Block (LTB) ● Liquid Crystal Display Block (LCD) ● Diagnostic Block (DIAG) ● Resource Block (RESOURCE) ① ② ③ Active function group Blocks within each function group Functions groups available In general, process parameters are accessed through the Level Transducer Block, and device parameters are accessed through the Resource Block.
Remote operation 7.1 Operating via AMS Device Manager 7.1.2 Key features of AMS Device Manager Rev. 9.0 The graphic interface in the radar device makes monitoring and adjustments easy.
Remote operation 7.1 Operating via AMS Device Manager 7.1.2.1 Pull-down menu access ① Action menu items A pull-down menu under Actions gives alternative access to several features.
Remote operation 7.1 Operating via AMS Device Manager 7.1.3 Adding a new device 7.1.3.1 Electronic Device Description (EDD) Note SITRANS LR250 requires the EDD for AMS Device Manager version 9.0. Check the product page of our website at: www.siemens.com/LR250 (http://www.siemens.com/LR250), under Downloads, for the latest version of EDD: SITRANS LR250 FF - Foundation Fieldbus - AMS V9.0. 1.
Remote operation 7.1 Operating via AMS Device Manager Startup 1. Launch AMS Device Manager – AMS Device Manager. (If AMS already running, go to step 4. 2. From the Device Connection View, right click on the FF Network icon and select Rebuild Hierarchy. 3. Double-click the device icon to open the startup screen. The startup screen shows device identification details, and a navigation window on the left-hand side of the screen. (The Block Status will show Out of Service at initial startup.) 4.
Remote operation 7.1 Operating via AMS Device Manager 7.1.4 Master Reset A master reset is recommended before first configuring a new device. (Block Status must be Out of Service to perform a Master Reset.) 1. Navigate to Configure/Setup > Resource > Operation > Methods and click to open the dialog window. 2. In the General field, click on Master Reset and click Next to perform reset to factory defaults. Click Next to accept default reset to Factory Defaults. ① Master Reset 3.
Remote operation 7.1 Operating via AMS Device Manager 7.1.6 Sensor calibration The LR250 FF does not need to be calibrated, only configured using the Quick Start Wizard below. 7.1.7 Configuring a new device Configure a new device using the Quick Start Wizard, found in the Resource Block of the function group Configure/Setup. 7.1.7.1 Quick Start Wizard via AMS Device Manager The Quick Start Wizard groups together all the settings you need to configure a device for most applications.
Remote operation 7.1 Operating via AMS Device Manager Quick Start Wizard steps Note • Complete the steps in order. Click on Apply after revising parameters in each step, or CANCEL to exit step without saving changes. (Note: Apply will write changes to the device. OK will write changes to the device and exit to the Device Connection View. CANCEL will exit to the Device Connection View without applying changes.
Remote operation 7.1 Operating via AMS Device Manager Step 1 - Identification You can accept the default values without modification. (Descriptor, Message, and Installation Date fields can be left blank.) If desired, make changes then click on Apply. (The Apply button is activated when a parameter is modified.) Go to Step 2.
Remote operation 7.1 Operating via AMS Device Manager Step 2 - Application Type Click on Step 2 - Application Type in the navigation window. Select the Application Type (level or volume), Propagation Factor (if using a stillpipe application), and the Material. For a Low Dielectric Liquid application in a stilling well, see example Application with Stillpipe (Page 60). Click on Apply to save settings then go to Step 3.
Remote operation 7.1 Operating via AMS Device Manager Step 3 - Vessel Shape Click on Step 3 - Vessel Shape in the navigation window. Select the vessel shape. To describe a more complex shape, select Linearization Table in the Vessel Shape field and see Linearization (LTB) (Page 82) for more details. Click on Apply to save settings then go to Step 4.
Remote operation 7.1 Operating via AMS Device Manager Step 4 - Ranges Click on Step 4 - Ranges in the navigation window. On the tab Step 4 of 5 Ranges: set the parameters, and click on Apply to save settings. If necessary, click on the Breakpoints tab, set the parameters, and click on Apply to save settings. Go to Step 5.
Remote operation 7.1 Operating via AMS Device Manager Step 5 - Summary Click on Step 5 - Summary in the navigation window. Check parameter settings. Return to individual steps if further changes are necessary. The Quick Start Wizard is now complete. 7.1.8 Changing parameter settings using AMS Device Manager Note • For a complete list of parameters, see Parameter Reference (Page 129). • For more detailed explanations of the parameters listed below see the pages referenced. 1.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9 Configure/Setup (Level Transducer Block-LTB) 7.1.9.1 Identification (LTB) Navigate to Configure/Setup > LTB > Identification. Identification: ● TAG: Read only. Description for the associated block: device tag prefixed by block type. ● Descriptor [see Descriptor (2.1.2.)] ● Transducer Block Type: Read only. Identifies the type of transducer block. ● Strategy: Used to identify grouping of blocks.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9.2 Operation (LTB) Navigate to Configure/Setup > LTB > Operation. Click on Block Modes to open the dialog window for access to: Block Modes: ● Actual Mode: This is the current mode of the block, which may differ from the target based on operating conditions. Its value is calculated as part of the block execution. ● Target Mode [see Mode (2.6.2.)] ● Permitted Mode: Defines the modes that are allowed for an instance of the block.
Remote operation 7.1 Operating via AMS Device Manager ● Simulation ● Simulation Value ● RAMP start ● RAMP end ● RAMP No of steps ● RAMP steplength 1. To enable simulation select Fixed value or Ramp in the Simulation field. 2. If you select Fixed value, enter a Simulation Value. 3. If you select Ramp, enter the ramp start, end, number of steps, and steplength. 4. Click Apply. 5. After simulation is complete, set Simulation to OFF and click Apply.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9.3 Setup (LTB) Sensor (LTB) Navigate to Configure/Setup > LTB > Setup and click on Sensor for access to: General [see Sensor (2.3.) for details] ● Unit [see Unit (2.3.1.)] ● Level Unit [see Level Unit (2.3.2.)] ● Temperature Unit [see Temperature Units (2.3.4.)] ● PV (Volume/Level) Unit [see PV (volume/level) Units (2.3.3.)] ● Application Type (available only via AMS Device Manager) Defines the application type.
Remote operation 7.1 Operating via AMS Device Manager ● Material [see Material (2.3.5.)] ● Loss of Echo Timer (see Loss of Echo (LOE) Timer (2.3.6.)] Calibration [see Calibration (2.3.7.) for details] ● Low Calibration Point [see Low Calibration Point (2.3.7.1.)] ● High Calibration Point [see High Calibration Point 2.3.7.2.)] ● Sensor Offset [see Sensor Offset (2.3.7.3.)] ● Low Level Point [see Low Level Point (2.3.7.4.)] ● High Level Point [see High Level Point (2.3.7.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9.4 Linearization (LTB) You can use the linearization feature to define a more complex vessel shape and enter up to 32 level breakpoints where the corresponding volume is known. See Linearization (2.4.). Navigate to Configure/Setup > LTB > Setup > Linearization and click on Linearization. Click on the Vessel Shape tab to access the parameters listed: Vessel Shape ● Vessel Shape [see Vessel Shape (2.4.1.1.
Remote operation 7.1 Operating via AMS Device Manager Level and Volume Breakpoints [see XY Index (2.4.1.5.)] ● Level 1 .... Level 32 ● Volume 1 ... Volume 32 ● Vessel Shape 1. The default for level values is percent: if you want to select units instead, go to Configure/Setup > LTB > Setup > Sensor > Level Unit, and select the desired unit. 2. Go to Configure/Setup > LTB > Setup > Sensor > PV (Volume/Level) Unit, and select the desired volume units. 3.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9.5 Signal processing Signal Processing (LTB) Note For more detailed explanations of the parameters listed below see the pages referenced. General Navigate to Configure/Setup > LTB > Setup > Signal Processing and click on General for access to: Range [see Signal Processing (2.5.)] ● Near Range [see Near Range (2.5.1.)] ● Far Range [see Far Range (2.5.2.)] ● Propogation Factor [see Propogation Factor (2.5.3.
Remote operation 7.1 Operating via AMS Device Manager Echo Select [see Echo Select (2.5.7.)] ● Algorithm [see Algorithm (2.5.7.1.)] ● Position Detect [see Position Detect (2.5.7.2.)] ● Echo Threshold [see Echo Threshold (2.5.7.3.)] ● CLEF Range [see CLEF (Contrained Leading Edge Fit) Range (2.5.7.4.)] Sampling [see Sampling (2.5.8.)] ● Echo Lock [see Echo Lock (2.5.8.1.)] ● Sampling Up [see Up Sampling (2.5.8.2.)] ● Sampling Down [see Down Sampling (2.5.8.3.)] Echo Quality [see Echo Quality (2.5.9.
Remote operation 7.1 Operating via AMS Device Manager Auto False Echo Suppression 1. Determine Auto False Echo Suppression Range. Measure the actual distance from the sensor reference point to the material surface using a rope or tape measure. 2. Subtract 0.5 m (20") from this distance, and use the resulting value. 3. Open the menu Configure/Setup > LTB > Setup > Signal Processing > TVT and set Auto False Echo Suppression Range. 4. From the same menu, set Auto False Echo Suppression to learn.
Remote operation 7.1 Operating via AMS Device Manager Manual TVT curve Displays the effects of the TVT shaper modifications. Navigate to Configure/Setup > LTB > Setup > Signal Processing and click on Manual TVT Curve.
Remote operation 7.1 Operating via AMS Device Manager Echo Profile Displays the current echo profile. Navigate to Configure/Setup > LTB > Setup > Signal Processing and click on Echo Profile to view the current echo profile and to access: Echo Profile Parameters [see Echo Profile (3.1.)] ● Level Measurement [see Measured Values (2.8)] ● Distance Measurement [see Measured Values (2.8.)] ● Confidence [see Confidence (2.5.9.1.)] ● Near Range (see (Near Range 2.5.1.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9.6 Maintenance & Diagnostics (LTB) Note For more detailed explanations of the parameters listed below see the pages referenced. Navigate to Configure/Setup > LTB > Maintenance and Diagnostics for access to: Remaining Sensor Lifetime [see Remaining Sensor LIfetime (4.3.)] ● Lifetime (expected) [see Lifetime (expected) (4.3.1.)] ● Time in Operation [see Time in Operation (4.3.2.)] ● Remaining Lifetime [see Remaining Lifetime (4.3.3.
Remote operation 7.1 Operating via AMS Device Manager Service Schedule [see Service Schedule (4.4.)] ● Service Interval [see Service Interval (4.4.1.)] ● Time Since Last Service [see Time Since Last Service (4.4.2.)] ● Time Until Next Service [see Time Until Next Service (4.4.3.)] ● Activation of Reminders [see Activation of Reminders (4.4.4.)] ● Reminder 1 before Lifetime (Required) [see Reminder 1 before Service (Required) (4.4.5.
Remote operation 7.1 Operating via AMS Device Manager Electronics Temperature [see Electronics Temperature (3.3.)] ● Electronics Temperature: Displays the current internal temperature of the device ● Minimum Value [see Minimum Value (3.3.1.)] ● Maximum Value [see Maximum Value (3.3.2.
Remote operation 7.1 Operating via AMS Device Manager 7.1.9.7 Communication (LTB) Navigate to Configure/Setup > LTB > Communication for access to: Communication: ● Static Revision No. [see Static Revision Number (2.6.1.
Remote operation 7.1 Operating via AMS Device Manager 7.1.10 Configure/Setup (Liquid Crystal Display Block-LCD) 7.1.10.1 Identification (LCD) Navigate to Configure/Setup > LCD > Identification. Identification: ● TAG ● Descriptor ● Transducer Block Type ● Strategy ● Plant Unit Note For descriptions of Identification parameters see Identification (LTB) (Page 77).
Remote operation 7.1 Operating via AMS Device Manager 7.1.10.2 Operation (LCD) Note For more detailed explanations of the parameters listed below see the pages referenced. Navigate to Configure/Setup > LCD > Operation. Click on Block Modes to open the dialog window for access to: Block Modes: ● Actual Mode ● Target Mode ● Permitted Mode ● Normal Mode Note For descriptions of Block Modes see Operation (LTB) (Page 78).
Remote operation 7.1 Operating via AMS Device Manager 7.1.10.3 Setup (LCD) Navigate to Configure/Setup > LCD > Setup > Local display for access to: Local Display Language [see Language (7.)] LCD Fast Mode [see LCD Fast Mode (4.9.)] LCD Contrast [see LCD Contrast (4.10.)] Local Operation [see Local Operation (6.2.3.)] If local operation is disabled remotely and no communication activity exists for 30 seconds, the parameter is made visible again locally. 7.1.10.
Remote operation 7.1 Operating via AMS Device Manager 7.1.11 Configure/Setup (Diagnostic Transducer Block-DIAG) Note Parameters in the Diagnostic Transducer Block used solely by factory personnel. 7.1.11.1 Identification (DIAG) Navigate to Configure/Setup > DIAG > Identification. Identification: ● TAG ● Descriptor ● Transducer Block Type ● Strategy ● Plant Unit Note For descriptions of Identification parameters see Identification (LTB) (Page 77). 7.1.11.
Remote operation 7.1 Operating via AMS Device Manager 7.1.11.3 Communication (DIAG) Navigate to Configure/Setup > DIAG > Communication. Communication: ● Static Revision No. [see Static Revision Number (2.6.1.)] 7.1.12 Configure/Setup (Resource Block - RESOURCE) Note For more detailed explanations of the parameters listed below see the pages referenced. 7.1.12.1 Identification (RESOURCE) Navigate to Configure/Setup > RESOURCE > Identification for access to: Identification ● TAG: Read only.
Remote operation 7.1 Operating via AMS Device Manager Device (read only) ● Manufacturer (see Manufacturer (5.3.)] ● Product Name: The manufacturer’s product name for this device. ● Order Number: The manufacturer’s order number (MLFB) for this device. ● Serial Number: The manufacturer’s unique serial number for this device. ● Hardware Revision [see Hardware Revision (2.2.1.)] ● Firmware Revision [see Firmware Revision (2.2.2.)] ● Loader Revision [see Loader Revision (2.2.3.
Remote operation 7.1 Operating via AMS Device Manager 7.1.12.3 Operation (RESOURCE) Navigate to Configure/Setup > RESOURCE > Operation. Click on Block Modes to open the dialog window for access to: Block Modes: ● Actual Mode ● Target Mode ● Permitted Mode ● Normal Mode Note • For descriptions of Block Modes see Operations (LTB) (Page 78).
Remote operation 7.1 Operating via AMS Device Manager General: ● Master Reset: see Master Reset (4.1.) 1. Ensure the Block Status is Out of Service. 2. Click the Master Reset button, then click Next to perform a reset. 3. Select the Reset Type Note The following parameters are not reset by any reset type: Write Protection, PIN to Unlock, Auto False Echo Suppression Range, Learned TVT.
Remote operation 7.1 Operating via AMS Device Manager Reset Type Result Factory Defaults a) Default. Resets all user parameters to the manufacturer’s default settings. Following this type of reset, complete reprogramming is required. Standard Defaults Resets all parameters to standard default settings. Informational Resets parameters such as Block Descriptor, Strategy, Device Install Date, Device Message.
Remote operation 7.1 Operating via AMS Device Manager 7.1.12.4 Maintenance & Diagnostics (RESOURCE) Navigate to Configure/Setup > RESOURCE > Maintenance & Diagnostics for access to: Remaining Device Lifetime [see Remaining Device Lifetime (4.2.)] ● Lifetime (expected) [see Lifetime (expected (4.2.1.)] ● Remaining Lifetime (read only) [see Remaining Lifetime (4.2.3.)] ● Time in Operation (read only) [see Time in Operation (4.2.2.)] ● Activation of Reminders [see Activation of Reminders (4.2.4.
Remote operation 7.1 Operating via AMS Device Manager Calibration Schedule [see Calibration Schedule (4.5)] ● Calibration Interval [see Calibration Interval (4.5.1.)] ● Time Since Last Calibration [see Time Since Last Calibration (4.5.2.)] ● Time Until Next Calibration (read only) [see Time Until Next Calibration (4.5.3.)] ● Activation of Reminders [see Activation of Reminders (4.5.4.)] ● Reminder 1 before Calibration (Required) [see Reminder 1 before Calibration (Required) (4.5.5.
Remote operation 7.1 Operating via AMS Device Manager Wear ● Powered Days (read only) [see Powered Hours (4.7.)] ● Poweron Resets (read only) [see Power-on Resets (4.8.)] 7.1.12.5 Communication (RESOURCE) ● Navigate to Configure/Setup > RESOURCE > Communication to read the following: ● Manufacturer [see Manufacturer (5.3.)] ● Product Name: the manufacturer’s product name for this device. ● Device Revision [see Device Revision (5.5.
Remote operation 7.1 Operating via AMS Device Manager 7.1.12.6 Security (RESOURCE) Navigate to Configure/Setup > RESOURCE > Security to access: Local Access ● Local Write Protected [see Write Protection (6.2.1.)] ● PIN to Unlock [see PIN to Unlock (6.2.2.)] See also Password Protection (Page 115).
Remote operation 7.1 Operating via AMS Device Manager 7.1.13 Device Diagnostics (Level Transducer Block - LTB) Note For explanations of the alarms and errors listed below, see Parameter Description charts for the respective block in manual Foundation Fieldbus for Level Instruments (7ML19985MP01). 7.1.13.1 Alarms & Errors (LTB) Navigate to Device Diagnostics > LTB > Alarms & Errors.
Remote operation 7.1 Operating via AMS Device Manager Click on Block Alarm to open the dialog window to read the following: Unacknowledged ● Unacknowledged Alarm State ● Alarm State Time Stamp ● Time Stamp Subcode ● Subcode Value ● Value 1. From the Block Error tab, check the Maintenance window to display the level of maintenance alarm that is active. 2. From the Block Alarm tab, check the Alarm State window to display the level of maintenance alarm that has been acknowledged. 3.
Remote operation 7.1 Operating via AMS Device Manager Note Acknowledging a maintenance reminder from the device (see Acknowledge (4.2.9.), (4.3.9.), (4.4.9.), (4.5.9.) will not set the Block Alarm to Acknowledged in AMS. The maintenance alarm will cause an FF block alert, and the block alert can only be acknowledged via a remote host such as NI-FBUS Configurator or AMS Device Manager (as in step 3 above).
Remote operation 7.1 Operating via AMS Device Manager 7.1.13.
Remote operation 7.1 Operating via AMS Device Manager 7.1.14 Device Diagnostics (Liquid Crystal Display Block - LCD) 7.1.14.1 Alarms & Errors (LCD) Navigate to Device Diagnostics > LCD > Alarms & Errors to read Block and Alarm errors. [Errors displayed are the same for each block (LTB, LCD, DIAG, RESOURCE). See Alarms & Errors (LTB) (Page 106) for full listing.] 7.1.15 Device Diagnostics (Diagnostic Transducer Block - DIAG) 7.1.15.
Remote operation 7.
Remote operation 7.
Remote operation 7.1 Operating via AMS Device Manager 7.1.16.2 Extended Diagnostics (RESOURCE) Navigate to Device Diagnostics > RESOURCE > Extended Diagnostics to read the following: Detailed Error Info ● Device Lifetime Limit1 ● Device Lifetime Limit2 ● Calibration Schedule Limit1 ● Calibration Schedule Limit2 ● Memory RAM ● Memory EEPROM ● Memory EEPROM Flags ● Memory Flash ● Corrupt Stack ● High Stack ● Data Safe Read ● Data Safe Write ● Board Voltage ● ADC Failed ● Seq. Corrupt ● Seq. CP ● Seq.
Remote operation 7.1 Operating via AMS Device Manager 7.1.17 Process Variables (Level Transducer Block - LTB) To compare outputs in real time navigate to Process Variables > LTB. Click on Process Variables then the Values tab to read the following: Primary Variable [see Main Output (PV - Primary Value) (2.8.1.)] ● Level/Volume (PV) The primary variable and the channel 1 output from the transducer block.
Remote operation 7.1 Operating via AMS Device Manager Echo Profile • Level Measurement [see Measured Values (2.8.)] • Distance Measurement [see Measured Values (2.8.)] • Confidence [see Confidence (2.5.9.1.)] • Near Range [see Near Range (2.5.1.)] 7.1.
Remote operation 7.1 Operating via AMS Device Manager 7.1.18.1 User Manager utility Usernames, passwords, and permissions, are assigned to users by an AMS Device Manager administrator, using the User Manager utility on the Server Plus Station. Only a user with AMS Device Manager System Administration rights can log in to User Manager. To configure a new user/edit existing user: 1. From the Windows taskbar select: Start > AMS Device Manager > User Manager. 2. In the User Manager window click on Add User.
Remote operation 7.1 Operating via AMS Device Manager 7.1.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.
Remote operation 7.