Installation Manual

2 OCCUPANCY TIME DELAY
The length of time an occupancy sensor will keep the lights
on and at full bright after it last detects occupancy (assuming
minimum on time has been met)
3 DIM TO OFF TIME
An extended length of time after the occupancy time delay has
expired that a sensor will rst reduce lighting to the low dimming
range setting before turning completely off
4 100 HOUR BURN-IN / AUTO SET-POINT
Test Mode
Disables Minimum On Time, sets Occupancy Time Delay to
30 sec, and shortens all photocell transition and dimming
rates. Mode will expire after 10 min or if function 4 is set back
to Normal.
100 HOUR BURN-IN
Overrides relay on and/or dimming output to full bright
(typically for lamp seasoning)
AUTO SET-POINT
Photocell calibration procedure for detecting optimum lighting
control level
5 TEN’S DIGIT OF SET-POINT
The ten’s digit of the target light level that is to be maintained by
the device (in foot-candles)
6 ONE’S DIGIT OF SET-POINT
The one’s digit of the target light level that is to be maintained by
the device (in foot-candles)
7 SUNLIGHT DISCOUNT FACTOR
Value used to improve the tracking accuracy of a photocell during
periods of high daylight. Decreasing the value will lower the
controlled level of the lights
8 INCREMENTAL SET-POINT ADJUSTMENT
Alters the target light level that is to be maintained by the device
(in foot-candles)
10 MINIMUM ON TIME
The length of time required for lamps to be on in order to prevent
all short cycling that shortens lamp life. If occupancy time delay
expires prior to minimum on time being satised, the lamps will
remain on until time has been met.
11 PHOTOCELL MODE
Indicates a photocell sensor’s method of operation. One mode
enables the sensor to turn the lights both on and off, while the
other mode can only inhibit the lights from turning on. For dimming
sensors, this mode enables disabling of on/off functionality.
12 DUAL TECHNOLOGY (MICROPHONICS
TM
)
A second method of occupancy detection that allows the sensor
to hear occupants
14 LAMP INFORMATION
LAMPMAXIMIXER+ (Enable/Disable)
Advanced operating mode where occupancy time delay
adjustments are automatically made every two weeks.
The time delay is adjusted according to an algorithm that
determines the optimum time delay in order to maximize both
lamp life and energy savings.
TOTAL SWITCHES
The current count (in 1000’s) of the number of off to on cycles
since sensor installation (or since count was manually reset)
TOTAL RUN-TIME
The current elapsed time (in 1000’s of hrs) a controlled lamp
has been on since sensor was installed (or since count was
manually reset)
RESET LAMPMAXIMIZER+
Method of clearing the sensor’s historical occupancy
information such that if a sensor is phycially moved, only new
occupancy information will inuence LampMaximizer+ results
15 DIMMING RANGE (HIGH)
The maximum output level (0-10 VDC) of a sensor with a
dimming output
16 DIMMING RANGE (LOW)
The minimum output level (0-10 VDC) of a sensor with a dimming
output