Specification Sheet

®
SPECIFICATIONS
ORDERING INFO
OPTIONS
LOW VOLTAGE RELAY (R)
Enables sensors to interface with other
systems (e.g., BMS, lighting panels)
Provides dry contact closure via a
SPDT, 1 Amp, 40 Volt relay
Only one relay needed per zone
Changes state when all connected
sensors register unoccupied
Relay requires sensor power to function
OCCUPANCY CONTROLLED
DIMMING (D)
Provides dimming output to control
0-10 VDC dimmable ballasts
Provides a second occupancy time-out
period that enables the lights to go to a
dim setting before turning off
Adjustable max/min dim setting
Only one sensor per zone needs to
have dimming output
PHOTOCELL (P)
Auto set-point calibration
Two selectable modes of operation
On/Off mode: Photocell has full control
during periods of occupancy
Inhibit mode: Photocell can prevent
lights from turning on if adequate
daylight is available, but cannot turn
lights off
PHOTOCELL W/ DIMMING (ADC)
Photocell within sensor maintains total
room light level by controlling levels of
0-10 VDC dimmable ballasts
Photocell also has full on/off control
during periods of occupancy
Provides a second occupancy time-out
period that enables the lights to go to a
dim setting before turning off
Note: LampMaximizer+ features not
available with ADC option
LOW TEMP/HIGH HUMIDITY (LT)
Sensor electronics are coated for
corrosion resistance
• Operates down to -4º F (-20º C)
Required for cooler/freezer applications
OVERVIEW
Classrooms are ideal applications for the
CM PDT 10 Series Extended Range 360º
occupancy sensor. When mounted at 9 ft (2.74
m), this sensor provides line of sight Passive
Infrared (PIR) detection of walking type motions
up to 28 ft (8.53 m) in all directions. Additionally,
the CM PDT 10 provides overlapping
Microphonics™ technology to detect smaller
motions and occupant movements that occur
behind obstructions. When comparing small
motion detection, the CM PDT 10 far out
performs dual technology sensors that are
specied with 2,000 ft
2
of coverage. Spaces
with low ceiling heights are also best covered
by the CM PDT 10.
SENSOR OPERATION
Sensors with Passive Dual Technology
(PDT) rst see motion using 100% digital
Passive Infrared (PIR) detection and then
engage Microphonics™ to hear sounds that
indicate continued occupancy. This patented
technology uses Automatic Gain Control
(AGC) to dynamically self adapt a sensor
to its environment by ltering out constant
background noise and registering only noises
typical of human activity. When occupancy is
detected, a DC output goes high and can drive
up to 200 mA of connected load. If needed, a 10
second grace period also allows the lights to be
voice reactivated after shutting off. The sensor
is powered with 12-24 VAC/VDC and typically
operates with a PP20 or MP20 power pack,
enabling 20 Amp circuits to be controlled.
LAMPMAXIMIZER
®
This sensor also contains patented
LampMaximizer technology that allows users
to aggressively target energy savings while
still protecting lamp life. A minimum on timer,
factory set at 15 minutes, helps preserve lamp
life by eliminating all lamp cycles shorter than
lamp manufacturers’ recommendations. A
standard occupancy time delay is also present
that ensures lights turn off (assuming minimum
on timer has elapsed) if no occupancy is
detected. This timer is factory set at 10 minutes
to promote energy savings, but is adjustable
between 30 seconds and 20 minutes. These
adjustments can be done manually, through
the unit’s push-button, or automatically every
two weeks through an advanced mode, called
LampMaximizer+, that determines the optimum
time delay in order to maximize both lamp life
and energy savings. Additionally, this sensor
maintains statistics on total lamp on time and
number of cycles.
EXTENDED RANGE 360º SENSOR
CEILING MOUNT • LOW VOLTAGE • DUAL TECHNOLOGY (PDT)
CM PDT 10
FEATURES
100% Digital PIR Detection,
Excellent RF Immunity
360º Coverage Pattern
Patented Dual Technology with
PIR / Microphonics Detection
Push-Button Programmable
Adjustable Time Delays
Convenient Test Mode
No Field Calibration or Sensitivity
Adjustments Required
100 hr Lamp Burn-in Timer
Green LED Indicator
LAMPMAXIMIZER
®
TECHNOLOGY
Protects Lamp Life while
Maximizing Energy Savings
Minimum On Timer (15 min default)
Occ. Time Delay (10 min defatult)
LampMaximizer+ Mode -
Optimizes Lamp Life & Energy
Savings (disabled by default)
Switch Counter (in 1000’s)
Total Lamp On Time (in khrs)
PHYSICAL SPECS
SIZE 4.55” Dia. (11.56 cm)
1.55” Deep (3.94 cm)
WEIGHT 6 oz
MOUNTING
Ceiling Tile Surface
3.5” Octagon Box
Single Gang Handy Box
COLOR White
ELECTRICAL SPECS
OPERATING VOLTAGE
12-24 VAC/VDC
CURRENT DRAW
Standard, 4 mA
w/ R option, 16 mA
DIMMING LOAD Sinks < 20mA;
~40 Ballasts @ .5mA each
RECOMMENDED POWER PACK
PP20
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
SILICONE FREE
ROHS COMPLIANT
RELAY
TEMP/HUMIDITY
Blank = None Blank = None Blank = Standard
R = Low Voltage Relay D = Occupancy Controlled Dimming LT = Low Temp
P = Photocell
ADC = Photocell w/ Dimming
CM PDT 10 [RELAY] [DIMMING/PHOTOCELL] [TEMP/HUMIDITY]
DIMMING / PHOTOCELL CHOOSE ONE ONLY
C US LISTED
TITLE 24
ASSEMBLED in U.S.A.
5 YEAR WARRANTY