LS-10 The Magic Box HOME MANAGEMENT GATEWAY OPERATION MANUAL V2.
Table of Contents INTRODUCTION 1, BASE UNIT 1.1 Display 1.2 Rear Panel 1.3 Mounting Bracket 1.4 Beeps & LED indication 1.5 Device Numbering Plan 2, System Connection 2.1 I/O Terminals 2.2 Home Automation Control Interface 2.3 RJ-45 Ethernet Interface 2.4 Power Input 2.5 Micro USB Interface 3, Working Scenario: 3.1 Works with HyperSecureLink software through USB port for local access. 3.2 Access the LS-10 by HyperSecureLink software or Mobile App. from local Intranet. 3.
INTRODUCTION Thank you for purchasing the LS-10 Web Based Home Management Gateway. By adopting modern embedded system and Cloud Server technologies, the LS-10 is designed to provide all the most advanced features to meet your home management requirements through Internet. The LS-10 not only provides you a secure life but also a convenient living environment that allows you to control as many as 15 programmable switches through a cloud server, mobile App.
1. BASE UNIT 1.1 Display The Blue LED flashes when there is data sending out from the LS-10. Three LEDs in green, yellow and red colors represent the system operation mode and alarm/ warning status as listed in the following table.
1.2 Rear Panel: Clear/Enroll Button: Clear LED Status: Press the button for about 0.2 sec. to clear the alarm and warning LED status (with a long beep). The LED status also can be cleared from HyperSecureLink command. Device Enroll: Press the button for about 3 sec. the LS-10 enters into Enroll Device State for 30 seconds. (Buzzer beeps and Green, Yellow, Red LEDs blink) Please refer to Section 4.1. 1.
1.4 Beeps & LED indication Status Beep G LED Y Remark R PWR On (OK) Beeps on operation mode B Disarm 1L B Monitor 1L B Home 2S Away 4S Clear (OK) 1L Entry Delay M-M-M--( >10sec.) S-S-S--- (< 10sec.) Exit Delay M-M-M--( >10sec.) S-S-S--- (< 10sec.) Open Detect 5sec. continuous Alarm delay M-M-M--- (30sec.
1.5 Device Numbering Plan All the sensors of LS-10 are divided into five main categories. 1, Controller /Panic Devices (C) x 32: Remote Controller, Keypad. 2, Burglary Sensors/Sirens (B) x128: Door Magnet, PIR, Glass Break Detector, Vibration Sensor, Pressure Change Detector, Wireless Siren. 3, 4, 5, Fire Sensors (F) x64: Smoke/Heat Detector, CO Detector, Gas Detector, Fire Call Point. Medical Help Transmitters (M) x32: Medical Button, Inactivity Detector.
2, System Connection Complete Connection Diagram of LS-10 System 2.1 I/O Terminals: For the settings of the I/O Terminals, please refer to Appendix A.
2.2 Home Automation Control Interface This port is for the user to interface the Home Automation Control System. (X-10 protocol in default). 2.3 RJ-45 Ethernet Interface This port connects to the user’s Ethernet Hub or Router for remote control through cloud web server, mobile App. or HyperSecureLink software. 2.4 Power Input 7V DC adaptor socket of the LS-10 Base Unit. 2.5 Micro USB Interface USB connector to PC for local control from HyperSecureLink software or external power backup.
3, Working Scenario: LS-10 can work standalone with Free HyperSecureLink software, third party’s Mobile App or connect to a cloud server to enjoy much more service from the provider. 3.1 Works with HyperSecureLink software through USB port for local access. (Only for the LS-10 with USB Data Interface option) Connecting the LS-10 with PC by USB cable for both power and data interface.
3.2 Access the LS-10 by HyperSecureLink software or Mobile App. from local Intranet. Note: LS-10 must be set as a Server. Connecting the LS-10 to a router as a server to be accessed by Mobile App. or HyperSecureLink software locally. Setting the LS-10 as a server by VCOM and web browser. Access the LS-10 by HyperSecureLink software or Mobile App. from local.
3.3 Works with HyperSecureLink software or Mobile App. from Internet. Note: LS-10 must be set as a Server, please refer to Appendix C.1. Note: 1, To be accessed from the Internet, the Router needs a fixed IP address or a domain name. A dynamic domain name can be got from www.dyndns.org, www.no-ip.com (free) or other dynamic domain name service provider, some router manufacturers provide free domain name service if you use their router such as DLINK. Please refer to the web site: http://support.dlink.
3.4 Connects to a Cloud Server to Get Full Home Management Service from the Provider. Note: LS-10 must be set as a Client, please refer to the Appendix C.2.. Cloud Server IP address and port setting. Service example from a cloud server..
3.5 Connects to a Central Monitor Station to Get Alarm Service from the Service Provider. Note: LS-10 must be set as a Client. CMS monitoring software example from a service provider.
4, Installation 4.1 Device Enroll The first step to start the operation of LS-10 is to enroll all the sensor/controller devices into the Base Unit one by one. (Please refer to the User Guide of the devices to be enrolled as well.) *Press the Clear/Enroll button for 3 seconds, the LS-10 enters into Enroll Device State for 30 seconds. (Buzzer beeps and Green, Yellow, Red LEDs blink simultaneously) * Trigger the target device to send RF signal in 30 seconds.
4.2 Placement of the Base Unit and Sensors It is important for the Base Unit to have a good reception quality for the RF signals transmitted from all the sensors and controllers. Place the Base Unit near the central of your home or business if possible. Keep the Base Unit away from large appliances and other metal objects. Locate the Base Unit near a power outlet and the router. Install all the sensors according to your site planning.
5. OPERATION MODE 5.1 AWAY Mode: When you leave your home or business, set the system into Away Mode. Away Mode Arming Sequence Disarm Exit Delay AWAY mode active → System status: ↑ (0-255 seconds) Set AWAY mode Note: When you set the LS-10 in AWAY Mode, the Base Unit clears any previous alarm and warning status on the LED and check the state of the Door Magnet sensors.
5.2 HOME Mode: In this operation mode, those burglar sensors with their Enable State – “24-Hour Zone” or “Guard in Home Mode” = Yes, will still be on alert and offer the protection you need while at home. Note: When you place the LS-10 in Home Mode, the Base Unit will check the status of the Door Magnet sensors. If any of the sensors is still open (for example, you forgot to close the back door), the Base Unit will keep a “Protection Loop Open” in the Event Log.
5.3 DISARM/ MONITOR Mode: The LS-10 will not issue any alarm for Burglar sensors, but 24-Hour sensors, Fire sensors, Panic, Medical Buttons and Environment sensors still work all the time. Enter into “DISARM” or “MONITOR” Mode from different devices or services. Monitor Mode: In this mode all the trigger signals from the Burglar Sensors (not including the sensors assigned in Group number 91-99 Partial Arm Zones) will be recorded in the Event Log as trigger signals only; no alarm will be issued.
5.5 Reaction of LS-10 to Burglar Alarm Burglar Alarm Response AWAY Mode Burglar Alarm → Entry Delay Operation Mode ↑ ↑ (0-255 seconds) Burglar sensor triggered Siren goes off, Alarm data out. Burglar alarms can only be issued when the system is in AWAY or HOME mode or with the sensors assigned as a 24-Hour Zone device, while Fire, Panic, Medical and Environment alarms can be triggered anytime, regardless of the system operation mode. The siren can be stopped by disarming the system. 5.
6. SYSTEM CHECK 6.1 Event Log: The Base Unit can store 512 event records in its memory. These events can be checked from HyperSecureLink Software or Mobile App. If user applies a Cloud Service then much deeper Event Log can be recorded. Event Log read from HyperSecureLink software Event Log read from a mobile App. Event Log read from a cloud server.
6.2 Device Status: The latest state of the sensors including, signal strength and readings can be checked by device status from the HyperSecureLink Software or Mobile App. If user applies a Cloud Service then each device can be named for easy identification and Environment readings or activities can be show in graphics. Device Status read from HyperSecureLink software Device Status read from a Mobile App.
Cloud server allows user to assign a name to each device for user to identify the sensor much easier. Device Status read from a Cloud Server. 24 Hours history of a CO2 sensor shown from a Cloud Server.
7. HOME AUTOMATION CONTROL There are 15 switches can serve as alarm indications or home appliances control purpose. These switches can be controlled by Remote Controller, Keypad locally or by HyperSecurelink software, mobile App or Cloud Server remotely. 7.1 Switch setting by HyperSecureLink software to be controlled by Remote Controller. 7.2 Directly control from HyperSecureLink software, Mobile App or cloud service.
7.3 Switch control from Keypad. (Please refer to the KP-3S User Guide for more information.) 7.4, Automatic controlled by Burglar Sensors with “Home Automation=Yes” in Disarm Mode. Ex. Below settings will turn the switch #3 on for 10 minutes when the Burglar Sensor 01-02 was triggered in Disarm Mode. (For PIR sensor, it will turn off till the “Motion Stop” signal was received as well.
7.5 Automatic control by the Special Sensors with their “High/Low” limit settings. Ex, Below settings will turn on switch #3 when reading is above “28” and turn off switch #3 when reading is below “26”. (Note: “High Limit” Control is for cooler, and “Low Limit” Control is for Heater) 7.6 Automatically switch control scheduled by HyperSecureLink software. Note: This function is not available for LS-10N. Ex: The switch #1 will turn on at 19:00 and turn off at 07:05 everyday.
8. CONTROL AND PARAMETER SETTINGS 8.1 Control *Siren Test: This test will activate the beeper, external alarm siren and send an Activate signal to the Remote Siren (if a remote siren is installed) immediately. *Device Test: Enter into Device Test Mode for 5 minutes. Any trigger signal (not including the control signal from Remote Controller) in this time will be treated as a test signal. After 5 minutes, the system will exit from this mode automatically.
8.2 Settings for Timers *Entry Delay ( for Burglar Sensor only, 0-255 seconds, default=10 sec.) This setting is the time between any burglar sensor triggers and the alarm action procedure starts. When you return home and open the door, the Base Unit will issue warning beeps (if the Delay Activation = On) to remind you that the system is still in the Arm state and you should disarm the system within this time. For the system controlled by Wireless Keypad, this timer should be set more than 20 seconds.
Disarm Exit Delay AWAY ARM effective → System status: ↑ (0-255 seconds) Set AWAY mode This Delay only works on the Controller with its Delay Activation=Yes, see below. * Beeper Action Time: 0-255 seconds (default, 60 sec.) The time of the Inner Beeper sounds when the alarm trips. *Alarm Siren Action Time: 0 second to 120 minutes (default, 60 sec.) The activation time of the external Alarm Siren sounds (on the rear panel) when the alarm trips.
*Remote Siren Time: 0 seconds to 30 minutes (default, 60 sec.) The time of the wireless Remote Siren sounds when the alarm trips. ( Remote Siren is an Option.) * Pre-warning Time: 0-30min. (default, 2 min.) The switch action time when triggered by a Pre-warning Burglar sensor. *Home Automation Time: 0-30min. (default, 10 min.) The switch action time when triggered by a Burglar Sensor in “Disarm” mode with “Home Automation=Yes”. (Please refer to 8.4 “Device Status Settings”.
8.3 Setting for Beep & Siren *Door Bell (default= ON): The Base Unit will issue a doorbell beep in Disarm Mode when receiving a triggering signal from a Burglar sensor with its “Bell in Disarm = ON”. Note: The Bell function only works for the Burglar Sensor with “Bell in Disarm = Yes”.
8.4 Device Status Settings: *Device Bypass (default= No): (For all devices) Bypass = Yes: The system will ignore the trigger signal from this sensor. *Delay Activation(default= Yes): (For Controller & Burglar sensor) Delay Activation =Yes: (Refer to Exit Delay/Entry Delay.) For the Remote Controller, the Exit Delay time will be imposed on the Away command from this controller. For the Burglar sensor, the Entry Delay time will be imposed on the Burglar alarm signal from this sensor.
*24-Hour Zone (default = NO): (For Burglar sensor) 24-Hour Zone=YES: This Burglar sensor’s trigger signal will be processed all the time regardless of the system’s operation mode, either in Arm or Disarm. 24-Hour Zone=NO: This Burglar sensor’s trigger signal will only be processed in Arm Mode. *Guard in Home Mode (PIR default=No, Door Magnet default= Yes): (For Burglar sensor) Home Mode =Yes: This Burglar sensor will trigger an alarm in Home Mode operation.
Inactivity Time (refer to Inactivity Time), the Inactivity Alarm (medical) will be issued. Note: “Inactivity” function will be disabled in “Away” mode automatically and will issue alarm if the Inactivity sensor is triggered. Inactivity=No: This is a normal Burglar Sensor. *Supervised: (Automatically set by the sensor itself, refer to Sensor Supervise Time.) Supervised=Yes: System will check the “heartbeat” signal from this sensor.
“Control High Limit” then the corresponding switches will turn on and when the reading is below the “Control Low Limit” the corresponding switches will turn off. Low Limit: For the control of heater type device, it means when the reading is below the “Control Low Limit” then the corresponding switches will turn on and when the reading is above the “Control High Limit” the corresponding switches will turn off.
8.6 Wire Sensor Input Settings Trigger Open/Close (default, Trigger=Close): Alarm will be triggered by close (grounded) or open (>3V) the sensor input contact (or voltage). Away Open/Close (default, Away=Close): (For Wire Sensor input assigned as a Controller only) System will enter Away or Disarm Mode by close (grounded) or open (>3V) the sensor input contact (or voltage). 8.7 Switch On When Triggered: Select the switches that will be activated when this sensor is triggered.
8.8 Switch Settings *Switch Type (Default X-10 type): House Code : (X-10 Type switch only, default ) This code should be the same as the House Code set on the X-10 switches, user can select from A to P. 8.9 MISC. Settings * Deny Arm If Not Ready: (default, No) If set “yes” then system will not enter into “Away” or “Home” Mode if not all the Door/window Magnet s are closed. Note: If “Away” or “Home” control is remotely issued by command from HyperSecureLink, App.
8.10 CMS Settings For the user to subscribe the CMS/Cloud services please consult with the service provider first. *CMS Account Number: The user account (8 digits Max.) number for CMS IP Alarm Report. *Server Ack. Required (default=no) If there is no acknowledgement from the CMS or Cloud server within 30 seconds after the alarm issued then the alarm report will be resent max. for 3 times. Note: Since robust TCP/IP protocol is used in alarm data transmission, the fail of transmission is almost impossible.
*Operation Scene: 8 operation scenes can be set and controlled by KP-3S Keypad Ex.: If Scene 2 is selected by KP-3S then Partial Zone 91, 92, 93 will enter into “Away Mode”.
SPECIFICATIONS Input Power: 7V DC or Micro USB input. Standby Current: About 280mA RF : (Follows local regulations, other frequencies as requested) Receiving Frequency: 915MHz (For FCC), 868MHz (For CE) Transmission Frequency: 433MHz Data Modulation: OOK (On Off Key). Power: less than 10mW. Range: about 100m to 300m or more @open field, 25℃ (Depends on sensors and Hardware version). Receiver Type: super heterodyne. RF Security Code: 16,777,216 combinations with check sum for each type of sensors.
Appendix A: I/O Terminals A.1 External Wire Sensor Input: The External Wire Sensor should have NO/NC contact and connects to Input and Ground terminals. It can be assigned as a Controller, Panic, Burglar, Fire, Medical or Tamper device. The Zone number of this input is fixed as “00-03”. Setting of Wire Sensor Type and its parameters from HyperSecureLink software. A.2 External Alarm Siren Output: The alarm siren should be connected to the Siren (+) and Siren (-) terminals, the max.
“Alarm with Siren” needs to be enabled on the wire input or sensors if the Sirens (both Wire Siren and Remote Siren) should go off when alarm triggered by this sensor after the Delay time. Enabling the Alarm Siren of the Wire Sensor Input from HyperSecureLink software. Enabling the Alarm Siren of the Wireless Sensor (01-01) from HyperSecureLink software.
Appendix B: Partial Zone Control B.1 Set Partial Zone Operation Mode: Groups 91 to 99 are nine independent protected zones and these zones can be Armed /Disarmed individually. Setting of Partial Zone Operation Mode from HyperSecureLink software The Group Numbers from “91” to “99” are partial arming zones. They can be controlled by a Remote Controller, Wireless Keypad, or through the HyperSecureLink software individually but independent of the main groups (Group Number “01”~”89”).
Appendix C: How to Configure the Internet parameters C.1, Working with HyperSecureLink Software or Mobile App. Configure the LS-10 as a server to be accessed by the HyperSecureLink Software or mobile Apps from Internet. Note: Mobile Apps are from third parties and are not free, please refer to the web sites: https://play.google.com/store/apps/details?id=com.uioo.uioomyhome https://play.google.com/store/apps/details?id=com.ts3v.ls30&hl=nl C.1.1, LS-10 sets up as a server.
C.1.2, Configure the Ethernet Router. The following example is for Fixed IP address application. But if you have no Fixed IP address then you can apply some free DDNS service from the internet. For example D-Link provides free DDNS service for their routers. http://support.dlink.com/emulators/wbr2310/tools_ddns.htm Enter the web page of your Ethernet Router and find the setting of Virtual Server.
* The VCOM software searches in the network for the LS-10 and shows the findings on the screen. * Open the Internet browser you are using and enter the IP address. admin * Enter User Name and Password. (Default User Name: admin, default Password: admin. * The setup menu of Administrator Setting will be shown on the screen and change the parameters according to your network environment.
Nickname: Name or location of the system. IP Address: As the setting of the Virtual Server in the Ethernet Router. Subnet mask: 255.255.255.0 Gateway: Please enter the gateway address of your Ethernet Router. DNS: Please get this address information from your ISP. IP Configure: To operate as a server, Static must be selected Password Setting: Enter new User Name and Password.
If the IP address has been changed then enter the new IP address and User Name/ Password to access the LS-10 setup web page again. (You can use VCOM software to locate the new IP address.) * Select TCP Mode and change the settings according to your network environment: Telnet Server/Client: Select Server. Port Number: As the setting of the Virtual Server in the Ethernet Router. Remote server IP Address: Don’t care. Client mode inactive timeout: 20 minutes (default).
* Select UART to check if the settings are the same as below. Mode: RS-232. Baudrate: 9600. Character Bits: 8. Parity Type: None Stop Bit: 1. Hardware Flow Control: None. Delimiter: No need * If any of the settings has been changed then double click the Update to update the settings. Then Click the Reset to save the settings. ● The setting is completed here and the Ethernet Adapter is at your service. About the HyperSecureLink software please refer to the HyperSecureLink user guide.
C.2, Working with a Cloud server or Central Monitoring Station (CMS). (This setting is only valid for the user who has Cloud or CMS service. User has to know the IP address and port number of the Cloud server or CMS service before setting the LS-10.) Note: For the Cloud Server or Central Monitor Station please refer to web sites: Cloud Server: www.livingpattern.co or http://www.abell-security.com Central Monitor Station: www.iklomp.com C.2.1, LS-10 sets up as a client.
C.2.2, Configure the LS-10 * RUN the VCOM program on your PC. Click the Search * The VCOM software searches in the network for the LS-10 Ethernet Adapter and shows the findings on the screen. * Open the Internet browser you are using and enter the IP address.
admin * Enter User Name and Password. (Default User Name: admin, default Password: admin. * The setup menu of Administrator Setting will be shown on the screen and change the “IP Configure” to “DHCP”. Nickname: Name or location of the system. IP Address: Don’t care Subnet mask: 255.255.255.0 Gateway: Don’t care. DNS: Don’t care. IP Configure: To operate as a client, DHCP must be selected Password Setting: Enter new User Name and Password.
* If any of the settings has been changed then double click the Update to update the settings. Then Click the Reset to save the settings. Use VCOM software to locate the new IP address and enter the LS-10 setup web page again. * Select TCP Mode and change the settings according to the information from the web server or CMS service provider. Telnet Server/Client: Select Client. Port Number: Please check with your web server or CMS service provider for this information.
* Select UART to check if the settings are the same as below. Mode: RS-232. Baudrate: 9600. Character Bits: 8. Parity Type: None Stop Bit: 1. Hardware Flow Control: None. Delimiter: No need * If any of the settings has been changed then double click the Update to update the settings. Then Click the Reset to save the settings. ● The setting is completed here and check with your web server or CMS service provider if they can receive the report from your system.
Appendix D: Switch Action Table for Burglar Sensors PW= Pre-warning, HA= Home Automation, A= Away, H=Home, D=Disarm, M=Monitor, S=Motion Stop Door Mag.
For Any Burglar Sensor Assigned as An Inactivity Monitoring Device DC=Don’t Care Inact PW HA 24H State Alarm Switch on time CID code Remark Yes DC Yes DC A Yes Alarm Burg Disable Inactivity Yes DC Yes DC D/M/H NO HA NO Trigger Medical Alarm if no action detected in the Inactivity Time Yes DC NO DC A Yes Alarm Burg Disable Inactivity Yes DC NO DC D/M/H NO NO NO Trigger Medical Alarm if no action detected in the Inactivity Time
Appendix E: Load Factory Default of Internet Adaptor If user forgot the Device ID/ Password, the LS-10 works abnormally or couldn’t be found by VCOM software then user can load the Factory Default to re-initialize the device. D.1, Disconnect the power/data cable from the LS-10 D.2, Open the cover of the LS-10. D.3, Take out the Jumper from JP3 (Remember the position of the Jumper on JP3) and put the Jumper on JP1 D.4, Apply the power to LS-10 for 3 seconds. D.5, Disconnect the power/data cable. D.
D.9, Change the IP address and the Gateway address of the PC to the same segment of the LS-10. Ex: Since the IP address of LS-10 is 192.168.2.53 then set the IP address and Default gateway to 192.168.2. xx as below. D.10, Run the VCOM again then LS-10 will be show on the “Searching” screen. D.11, Open an Internet Browser and set the LS-10 according to your network requirement. D12, Disconnect the Ethernet cable and put the cover back. D13, Connect your PC and the LS-10 to the Internet.
WARRANTY The Manufacturer warrants its products (hereinafter referred to as the Product) to be in conformance with its own plans and specifications and to be free of defects in materials and workmanship under normal use and service for a period of twelve months from the date of shipment by the Manufacturer. The Manufacturer’s obligations shall be limited within the warranty period. At its option, to repair or replace the Product or and part thereof.