Product data sheet
Characteristics
VW3A31207
Profibus DP communication card - 12 Mbps
Main
Product or component
type
Communication card
Range compatibility Altivar 312
Communication port
protocol
Profibus DP
Electrical connection 1 connector RJ45, Modbus
1 removable screw terminal block for inputs/outputs
Screw terminal block, Profibus DP
Transmission rate 9600 bps, 19.2, 93.75, 187.5, 500 kbps, 1.5, 3, 6 or
12 Mbps
Number of addresses 1...126
Complementary
Input/Output number AI2 and AI3: 2 analog input
LI1...LI3: 3 logic input
R2: 1 relay output
Communication service CiA 402 profile
Messaging via PKW periodic variables
Periodic variables input : 4 PKW and 2 PZD
Periodic variables output : 4 PKW and 2 PZD
Display type 1 LED
1 LED for ST (status)
Product weight 0.2 kg
Environment
RoHS EUR status Compliant
RoHS EUR conformity date 0939