PowerLogic Series PD100 Partial Discharge Tag User Manual PowerLogic offers power quality, uptime and efficiency. GEX5968601-00 08/2022 www.se.
Legal Information The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners. This guide and its content are protected under applicable copyright laws and furnished for informational use only.
PD100 Partial Discharge Tag Table of Contents Safety Information ......................................................................................5 About the Book ...........................................................................................7 Safety Precautions ...................................................................................... 8 Presentation ................................................................................................ 10 PowerLogic Master Range .....
Safety Information PD100 Partial Discharge Tag Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
PD100 Partial Discharge Tag Safety Information Please Note Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
About the Book PD100 Partial Discharge Tag About the Book Document Scope The aim of this guide is to provide installers, users and maintenance technicians with the technical information and procedures to install and use the PowerLogic™ Partial Discharge Tag (PD100) and associated equipment. Validity Note This guide applies to the PowerLogic Partial Discharge Tag (PD100). The PD100 is compatible with the Schneider Electric VDIS (Voltage Detecting and Indicating System) unit.
PD100 Partial Discharge Tag Safety Precautions Safety Precautions Safety Rules DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See standards or local equivalent. • Perform work only after reading and understanding all of the instructions contained in these instructions. • Turn off all power supplying the system before working on or inside the system.
Safety Precautions PD100 Partial Discharge Tag The following schematic gives the location of the different parts of the PD100 to be processed: The following table gives the list of recommendations for the disposal of the PD100 components and materials for the items shown on the illustration.
PD100 Partial Discharge Tag Presentation Presentation PowerLogic Master Range The PD100 is part of the PowerLogic master range. PowerLogic smooths the power supply, and protects the network, the installation and the operator by improving the power factor and hence the quality of the power. It also allows for remote control of equipment and the monitoring of its performance and condition in real time.
Presentation PD100 Partial Discharge Tag PD100 Dimensions Top view 89.40 3.50 mm in. Side view R4.00 R0.16 96.00 3.78 mm in. 23.15 0.90 87.01 3.52 23.15 0.90 48 1.89 mm in. Front view 110.16 4.33 96.00 3.78 PD100 Front Face Description PD100 with cover open PD100 with cover closed D E C A B A A. System LED B. Zigbee LED C. System button D. Zigbee button E. QR code System LED The system LED indicates the system state. The following table describes the system LED behavior.
PD100 Partial Discharge Tag Presentation LED indication Description PD100 in test mode (accelerated monitoring reporting rate). 0s 1s Diagnostic connector enabled. PD100 monitoring is disabled. PD100 performing maintenance tasks like firmware update. PD100 not functional. Partial discharge monitoring and Zigbee communication disabled. PD100 in error and out of order. Zigbee LED The Zigbee LED indicates the state of the Zigbee Pro network. The following table describes the Zigbee LED behavior.
Presentation PD100 Partial Discharge Tag System Button The system button allows you to control the system state. The different modes are the following: • Test mode • Set-up mode • Diagnostic mode When you press the system button on the front panel, the PD100 enters test mode for 3 minutes. Use test mode to check PD100 commissioning. NOTE: Data is not measured in test mode. Zigbee Button The Zigbee button allows you to control the PD100 Zigbee status.
PD100 Partial Discharge Tag Presentation PD100 Mounting Clips A A A. PD100 mounting clips x 4 PD100 Serial Number A A. PD100 serial number The PD100 serial number is coded PPYYwwDllnnnn, where: 14 • PP: plant code • YY: year of manufacture • ww: week of manufacture • D: weekday of manufacture (Monday = 1) • ll: line number • nnnn: unique product number during the day.
Presentation PD100 Partial Discharge Tag Example: RN22045040123 means that product 0123 was manufactured on line number 04 at plant RN on Friday 28 January 2022. Technical Characteristics Environmental Characteristics The following table presents the environmental conditions to install the PD100.
PD100 Partial Discharge Tag Presentation Physical Characteristics Characteristics Value Reset Manual via front panel Indications LEDs Dimensions H x W x D: 48 x 96 x 110.16 mm (1.89 x 3.78 x 4.33 in) Flush-mounting cut-out (max. plate thickness: 20/10°) H x W: 45 x 93 mm (1.77 x 3.
Installation PD100 Partial Discharge Tag Installation Safety Instructions DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • The PD100 must be used only with Schneider Electric VDIS. • The PD100 must be connected on a capacitive coupling value between 15 pF and 40 pF. • The PD100 rear connectors must be inaccessible when the cubicle is energized. • The PD100 must only be installed by qualified electrical personnel.
PD100 Partial Discharge Tag Installation mm in. 25 0.98 70.4 2.77 95.4 3.75 105.3 4.14 The front cover opens downwards. Make sure that you can open the PD100 front cover and get unobstructed access to the Zigbee pairing button and the service connector. mm in. 22 0.86 Ø84 Ø3.30 1.5 0.06 Check that you can scan the QR code on the PD100 front face using a mobile phone during the assembly of the cubicle. The PD100 is compliant with DIN standard.
Installation PD100 Partial Discharge Tag 2. Insert the PD100 in the cut-out in the mounting plate by tilting the PD100 slightly. 1 2 3. Push slightly the top of the PD100, until you hear a click. 3 4. Check that the two upper mounting clips are in place and that the PD100 is fixed securely on the mounting plate. 5. Check that the gasket is in place.
PD100 Partial Discharge Tag Installation Power Supply Connection WARNING HAZARD OF PARTIAL DISCHARGE NOT BEING MONITORED • The PD100 must not be connected on a distributed power network. • No dielectric test must be done on the PD100 power supply connection. Failure to follow these instructions can result in death, serious injury, or equipment damage. NOTICE HAZARD OF IMPROPER POWER SUPPLY The PD100 must be connected onto a dedicated power supply.
Installation PD100 Partial Discharge Tag Use a type 5556 female pin. Select the exact pin depending on the wire used. Check the following requirements: • The length of the connecting lead between the PD100 and the coupling element does not exceed 3 meters. • The connecting lead does not have excess lead length. • Any excess lead is not bundled up. • The different connecting leads are designed and validated for each position of the PD100 in each cubicle type.
PD100 Partial Discharge Tag Installation Diagnostic Connection CAUTION HAZARD OF ELECTRIC SHOCK OR PRODUCT DAMAGE Do not use the front face connector dedicated to Schneider Electric tool connection for any other purposes than diagnostics tests by trained Schneider Electric personnel. Failure to follow these instructions can result in injury or equipment damage. On demand, diagnostics can be made by a Schneider Electric Field Service Representative using additional devices and sensors.
Operation PD100 Partial Discharge Tag Operation Cybersecurity Zigbee network security is managed by the trust center of the network. PD100 Zigbee communication security depends on the security level of the chosen trust center and concentrator. For a general introduction to cybersecurity threats and how to address them, see How Can I Reduce Vulnerabilty to Cyber Attacks. For more information about cybersecurity, visit the Schneider Electric Cybersecurity Support Portal.
PD100 Partial Discharge Tag Operation Result: The PD100 is in Zigbee factory reset state. Communication Lost The PD100 has lost communication with the Panel Server or gateway for more than 15 minutes when: • The operation LED is green (blinking or fixed). • The network status LED flashes red. The PD100 periodically monitors its communication state with the coordinator in accordance with product specifications.
Maintenance PD100 Partial Discharge Tag Maintenance DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH • Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel. • Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See standards or local equivalent. • Perform work only after reading and understanding all of the instructions contained in this guide.
PD100 Partial Discharge Tag Troubleshooting Troubleshooting If the system LED is red, contact your local Schneider Electric representative for assistance.
Radio Frequency Compliance PD100 Partial Discharge Tag Radio Frequency Compliance EU Declaration of Conformity Hereby, Schneider Electric Industries SAS declares that the PD100 is in compliance with the essential requirements and other relevant provisions of RED Directive 2014/53/EU. The EU BE20042401 declaration of conformity can be downloaded on www.se. com/docs. • IEEE 802.15.
PD100 Partial Discharge Tag Radio Frequency Compliance Radiation Exposure Statement: This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20 cm between the radiator & your body. Déclaration d’exposition aux radiations : Cet équipement est conforme aux limites d’exposition aux rayonnements IC établies pour un environnement non contrôlé.
Schneider Electric Green Premium™ Ecolabel PD100 Partial Discharge Tag Schneider Electric Green Premium™ Ecolabel Description Green Premium by Schneider Electric is a label that allows you to develop and promote an environmental policy while preserving your business efficiency. This ecolabel is compliant with up-to-date environmental regulations.
PD100 Partial Discharge Tag Schneider Electric Green Premium™ Ecolabel RoHs Schneider Electric products are subject to RoHS (Restriction on the use of Hazardous Substances) requirements at a worldwide level, even for the many products that are not required to comply with the terms of the regulation. Compliance certificates are available for products that fulfill the criteria of this European initiative, which aims to eliminate hazardous substances.
Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) 1 41 29 70 00 www.se.com As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication. © 2022 Schneider Electric. All rights reserved.