PowerLogic HeatTag Wireless Sensor for Early Detection of Overheating Cables User Guide PowerLogic offers power quality, uptime and efficiency. DOCA0171EN-00 01/2021 www.se.
Legal Information The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners. This guide and its content are protected under applicable copyright laws and furnished for informational use only.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Table of Contents Safety Information.......................................................................................5 About the Book ............................................................................................6 Presentation.................................................................................................7 PowerLogic Master Range ..........................................................................
HeatTag Wireless Sensor for Early Detection of Overheating Cables Safety Information Safety Information Important Information Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
HeatTag Wireless Sensor for Early Detection of Overheating Cables About the Book About the Book Document Scope This document provides users with the technical information needed to operate PowerLogic™ HeatTag™ wireless sensors for early detection of overheating cables. Validity Note This document applies to HeatTag sensors with firmware version 002.002.005 or greater. Online Information The information contained in this guide is likely to be updated at any time.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation Presentation PowerLogic Master Range PowerLogic smooths the power supply, and helps to protect the network, the installation and the operator by improving the power factor and hence the quality of the power. It also allows for remote control of equipment and the monitoring of its performance and condition in real time.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation HeatTag Description Overview The HeatTag is a wireless sensor for early detection of overheating wire connections or overheating cables. The HeatTag sensor helps prevent electrical distribution switchboards from being damaged by means of analyzing gas and micro-particles in the air of the switchboard and sending alerts before any smoke or insulator browning.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation The operation LED blinks slowly orange when the HeatTag sensor triggers an alert to the panel server or gateway. NOTE: The detection and communication functions of the HeatTag sensor can be disturbed depending on its installation and use in the equipment. Temperature and Humidity The HeatTag sensor measures the ambient temperature and humidity. These values are refreshed every 60 s.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation Hardware Description Description A B C D E G F A. Operation LED B. Network status LED C. Operation button D. QR code to access device information E. DIN clip F. Air inlet G. Power supply connector For information on installation, consult the instruction sheet available on the Schneider Electric website: MFR51738. Operation LED The LED indicates the operation mode and alert status of the HeatTag sensor.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation Network Status LED The LED indicates the communication status with the panel server or gateway. LED indication Description HeatTag sensor is unpaired with factory settings. 0s Reset to factory settings in progress. 0s 8s HeatTag sensor is searching for a panel server or gateway. 0s 1s HeatTag sensor in identification mode. 0s 0s 1s HeatTag sensor is in the network.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation Technical Characteristics Electrical Characteristics Characteristics Value Conforming to standards • IEC 61010-1:2017 UL/CSA/EU CENELEC deviations • IEC 61010-2-201 • IEC/EN 61326-1 • FCC Part 15B and 15C • ETSI/EN 300328 • ETSI/EN 301489-1 • ETSI/EN 301489-17 • IEEE 802.15.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation Characteristics Value Test alert after pairing Alert requested by panel server or gateway remotely Auto-learning phase of background environment 8 hours after the first 30 minutes EU Declaration of Conformity Hereby, Schneider Electric Industries SAS declares that the HeatTag sensor is in compliance with the essential requirements and other relevant provisions of RED Directive 2014/53/EU.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation Schneider Electric Green Premium™ Ecolabel Description Green Premium by Schneider Electric is a label that allows you to develop and promote an environmental policy while preserving your business efficiency. This ecolabel is compliant with up-to-date environmental regulations.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Presentation REACh Schneider Electric applies the strict REACh regulation on its products at a worldwide level, and discloses extensive information concerning the presence of SVHC (Substances of Very High Concern) in all of these products.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Use Commissioning When commissioned, the HeatTag sensor must be paired with Schneider Electric EcoStruxure panel servers or gateways.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Acknowledging an Alert The HeatTag sensor has triggered an alert when : • The operation LED flashes orange. • The network status LED blinks green. If the HeatTag sensor triggered an alert: 1. Investigate the cause of the heating in the switchboard. 2. Acknowledge the alert by pressing the operation button for less than 2 s.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Test With the HeatTag Tester Introduction The HeatTag sensor can be tested with the HeatTag tester during commissioning, within the first 30 minutes after powering on, and whenever needed after the 8-hour environment-learning period. Only use the tester and HeatTag Tester liquid provided by Schneider Electric to test the HeatTag sensor.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Filling the Tester WARNING UNINTENDED EQUIPMENT OPERATION • To test the HeatTag sensor, fill the HeatTag tester only with the HeatTag Tester liquid provided by Schneider Electric. • Before using the HeatTag Tester liquid, check the validity date printed on the bottle. Failure to follow these instructions can result in death, serious injury, or equipment damage.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use 6. Slide the tester cap to close the tester and stop the spray. 7. Check the result of the test: If... Then... The operation LED blinks orange on the HeatTag sensor and an alert is transmitted by the HeatTag sensor to the gateway. The test is successful. The operation LED blinks orange on the HeatTag sensor but no alert is transmitted to the gateway. The HeatTag sensor has triggered an alert.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Technical Characteristics of the Tester Characteristics Value Power supply 3.7 Vdc or 5.0 Vdc with AC adapter Particle size Mass Median Aerodynamic Diameter (MMAD) <4 μm (<13.2 μft) Capacity of tank 5 ml (0.17 fl.oz.) Dimensions Ø = 27.5 mm (1.06 in), L = 134 mm (5.28 in) Weight 62 g (2.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Remote Use of Data Paired with Schneider Electric EcoStruxure panel servers or gateways, the HeatTag sensor reports: • Alerts after overheating detection (3 levels) • Air quality index • Temperature and humidity measurement • Self-diagnostics alerts The following tools are available to remotely access data of the HeatTag sensor: • EcoStruxure Facility Expert (EFE) app and software • EcoStruxure Power Monitoring Expert (PME) s
HeatTag Wireless Sensor for Early Detection of Overheating Cables Use Troubleshooting Problem description Probable cause Solutions The operation LED blinks fast red after a HeatTag selfdiagnostics. Fan clogging detected in the HeatTag sensor. Clean the fan air inlet (see detailed procedure, page 23). The operation LED turns on red after a HeatTag selfdiagnostics. HeatTag sensor inoperative. Replace the HeatTag sensor.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Appendices Appendices 24 DOCA0171EN-00
HeatTag Wireless Sensor for Early Detection of Overheating Cables Appendices HeatTag Tester Liquid - Safety Data Sheet SAFETY DATA SHEET (REGULATION (EC) n° 1907/2006 - REACH) Bio Concept - Conceptarome SOLUTION SCHNEIDER - SCHNEIDER Version 1.3 (31/08/2020) - Page 1/6 SAFETY DATA SHEET (REACH regulation (EC) n° 1907/2006 - n° 2015/830) SECTION 1 : IDENTIFICATION OF THE SUBSTANCE/MIXTURE AND OF THE COMPANY/UNDERTAKING 1.1. Product identifier Product name : SOLUTION SCHNEIDER Product code : SCHNEIDER.
HeatTag Wireless Sensor for Early Detection of Overheating Cables SAFETY DATA SHEET (REGULATION (EC) n° 1907/2006 - REACH) Bio Concept - Conceptarome SOLUTION SCHNEIDER - SCHNEIDER Appendices Version 1.3 (31/08/2020) - Page 2/6 In the event of swallowing : In the event of swallowing, if the quantity is small (no more than one mouthful), rinse the mouth with water and consult a doctor. Keep the person exposed at rest. Do not force vomiting. Seek medical attention, showing the label.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Appendices SAFETY DATA SHEET (REGULATION (EC) n° 1907/2006 - REACH) Bio Concept - Conceptarome SOLUTION SCHNEIDER - SCHNEIDER Version 1.3 (31/08/2020) - Page 3/6 Recommended equipment and procedures : For personal protection, see section 8. Observe precautions stated on label and also industrial safety regulations. Packages which have been opened must be reclosed carefully and stored in an upright position.
HeatTag Wireless Sensor for Early Detection of Overheating Cables SAFETY DATA SHEET (REGULATION (EC) n° 1907/2006 - REACH) Bio Concept - Conceptarome SOLUTION SCHNEIDER - SCHNEIDER Appendices Version 1.3 (31/08/2020) - Page 4/6 SECTION 9 : PHYSICAL AND CHEMICAL PROPERTIES 9.1. Information on basic physical and chemical properties General information : Physical state : Fluid liquid.
HeatTag Wireless Sensor for Early Detection of Overheating Cables Appendices SAFETY DATA SHEET (REGULATION (EC) n° 1907/2006 - REACH) Bio Concept - Conceptarome SOLUTION SCHNEIDER - SCHNEIDER Version 1.3 (31/08/2020) - Page 5/6 No data available. 12.5. Results of PBT and vPvB assessment No data available. 12.6. Other adverse effects No data available.
HeatTag Wireless Sensor for Early Detection of Overheating Cables SAFETY DATA SHEET (REGULATION (EC) n° 1907/2006 - REACH) Bio Concept - Conceptarome SOLUTION SCHNEIDER - SCHNEIDER Appendices Version 1.3 (31/08/2020) - Page 6/6 Abbreviations : ADR : European agreement concerning the international carriage of dangerous goods by Road. IMDG : International Maritime Dangerous Goods. IATA : International Air Transport Association.
Schneider Electric 35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) 1 41 29 70 00 www.se.com As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication. © 2021 – Schneider Electric. All rights reserved.