Installing and Connecting the AKL08RF Zigbee Zone Wiring Centre
Use the AKL08RF zone wiring centre to simply and safely connect thermostats and corresponding thermal actuators or motorised valves. The AKL08RF connects to the wireless network through the AC10RF
coordinator or the Universal Gateway SG888ZBWH. One coordinator can support up to nine wiring centres, which means that if you buy more than one wiring centre, you will only need one of the
included coordinators. Keep the other coordinators in a safe place as spares. If you are using the Universal Gateway SG888ZBWH please remove the AC10RF coordinator from your system.
Install the AKL08RF only in dry and closed interior rooms. Relative air humidity in the room may not exceed 95%. Clean the AKL08RF only with a dry and soft cloth. Do not use solvents or aggressive cleaning agents.
If you are not using theSG888ZBWH
Gateway then plug in the AC10RF
coordinator.
LED indications
Name Colour Meaning
Power
AKL08RF is supplied with 120V power
G1
Wireless network activity on group 1 thermostats
G2
Wireless network activity on group 2 thermostats
Network Status
AKL08RF is waiting to pair
AKL08RF is connected to the wireless network
Zone 1 actuators
Demand from group 1, zone 1 thermostat: actuator open
Zone 2 actuators
Demand from group 1, zone 2 thermostat: actuator open
Zone 3 actuators
Demand from group 1, zone 3 thermostat: actuator open
Zone 4 actuators
Demand from group 1, zone 4 thermostat: actuator open
Zone 5 actuators
Demand from group 2, zone 1 thermostat: actuator open
Zone 6 actuators
Demand from group 2, zone 2 thermostat: actuator open
Zone 7 actuators
Demand from group 2, zone 3 thermostat: actuator open
Zone 8 actuators
Demand from group 2, zone 4 thermostat: actuator open
Pump
Pump on
Boiler
Boiler on
CO
Heating Mode
Cooling Mode
Set the boiler delay, wireless, and thermal
actuator jumpers.
Jumper Settings/Positions for Pump/Boiler
On/Off Delay
The pump/boiler on delay and the pump
off delay are fixed 3 minutes in the software
and at 0 in the terminal. The default setting
for the boiler off delay is also 0 minutes,
but can be changed to 15 minutes.
To do this, carefully remove the jumper and
re-insert it in the other position as shown below:
Wireless
The default setting for the wireless connection
is internal (INT). If the external antennae A8RFA
is used change this setting (EXT). Carefully
remove the jumper and re-insert it in the other
position as shown below:
Type of Actuator
The default setting for the type of actuator is
normally closed (NC). To change this setting
to normally open (NO), carefully remove the
jumper and re-insert it in the other position as
shown below. Note that the actuator setting
and thermostat setting must be the same.
Push in the Dew Point
wires in the AKL08RF
for a dry contact
humidity sensing.
Bend and place the wires into their
correct positions.
Reattach the 24V supply connection.
Bend and place the wires into the
round holes at the button of the
AKL08RF for actuators/motorised
valves. You can add up to 4 actuators
or motorised valves for each zone.
Reattach the white cover to the
wiring center and secure it with two
screws.
Make sure there is the correct
fuse (4 Amp).
Re-attach the plastic cover. Turn the
screw in the lock position. Switch on
main power supply to the unit. The red
LED comes on.
Re-attach the High voltage cover and
secure it with two screws.
Coordinator
Connecting the AKL08RF (s) to the ZigBee Wireless Network
1. On powering up the AKL08RF, all actuator LEDs light up green then go off, then the Network Status LED flashes green.
2. Press and hold the button on the coordinator for five seconds. The button flashes red to indicate the coordinator is
ready to pair. The Network Status LED on the AKL08RF goes steady green when connected.
3. Repeat the process for every AKL08RF in the system. Note that one coordinator can support up to nine AKL08RFs.
4. To identify your AKL08RF (WC) number press Pair for one second. The LED on the zone number lights green:
Zone 1 = WC -1, Zone 2 = WC-2, and so on. The Network Status LED is used to identify WC-9.
5. To pair your Salus thermostats, see your thermostat manual.
6. Press the coordinator button for five seconds until the LED flashes steady red.
Note: To restore the AKL08RF back to factory default settings at any time, using a suitable tool, press the Reset button to the left
of the pair button.
Checking the System Configuration and Communication
Press and hold the coordinator button for one second. All devices connected to the system flash. To stop checking, press and hold the coordinator
button again for one second.
Press and hold the Pair button on the WC for five seconds. All devices connected to the AKL08RF will flash. To stop checking, press and hold the Pair
button again for five seconds.
Deleting all Devices from the Wireless Network
To delete all devices connected to the network, press and hold the coordinator button for 15 seconds. The colour of the button changes from red
to amber.
To delete all devices connected to the AKL08RF, press and hold the pair button on the AKL08RF for 15 seconds. The G1 and G2 LEDs turn from flashing
red to solid red then go off.
Note: After all devices have been deleted from the wireless network, they will need to be reinstalled. Refer to the instruction manuals.
Universal Gateway
Connecting the AKL08RF (s) to the ZigBee Wireless Network
1. On powering up the AKL08RF, all actuator LEDs light up green then go off, then the Network Status LED flashes green.
2. Remove the coordinator, access the Wise.ly App and add your AKL08RF. When in Pairing Mode, the Universal Gateway will start flashing red. The Network
Status LED on the AKL08RF goes steady green when connected.
3. Repeat the process for every AKL08RF in the system. Note that one Universal Gateway can support up to 100 devices
(thermostats, ARV’s, etc.).
4. To identify your AKL08RF (WC) number press Pair for one second. The LED on the zone number lights green:
Zone 1 = WC -1, Zone 2 = WC-2, and so on. The Network Status LED is used to identify WC-9.
5. To pair your Salus thermostats, see your thermostat manual.
6. The Universal Gateway will turn solid blue automatically, once the pairing process is complete.
Note: To restore the AKL08RF back to factory default settings at any time, using a suitable tool, press the Reset button
to the left of the pair button.
Checking the System Configuration and Communication
Go to the Wise.ly App and press the Identify button. The device will start flashing. Stop the identify process by pressing
the button from the App again.
Press and hold the Pair button on the WC for five seconds. All devices connected to the AKL08RF will flash. To stop
checking, press and hold the Pair button again for five seconds.
Deleting all Devices from the Wireless Network
You can remove your devices from the Wise.ly App. Equipment, All equipment menu.
To delete all devices connected to the AKL08RF, press and hold the pair button on the AKL08RF for 15 seconds. The G1 and G2 LEDs turn from flashing
red to solid red then go off.
Note: After all devices have been deleted from the wireless network, they will need to be reinstalled. Refer to the instruction manuals.
Antenna protective cap
Connect your wiring center to
a 120VAC supply
Connect the wires to the correct terminals.
3
Warning
Use the powercord connections that are
suitable for your system.
5
7
8
9
10
11
12
13
Clip in the terminals for boiler and pump
connection. Press the terminal button,
insert the cable and release the button.
Ensure the Pump and Boiler wires are placed in
their respective grooves in the back plate.
4
i
Make sure to put the wires through
the grooves.
24
VAC
6
24
VAC
Push in the CO wires
for dry contact
heating/cooling
changeover switching.
An open switch is for
heating (red LED). A
closed switch is for
cooling (blue LED).
Heating mode
Cooling mode
A. Remove the plastic cover by turning the
screw 90 to the Unlock position.
B.
Remove the High voltage cover.
C. Detach the 24V supply connection .
D. Remove the white terminal for access to the
power cord connections.
E. Insert wires for the Power, Pump and Boiler
and fasten securely.
F. Use the proper wire connectors (purchased
separately) for a 120VAC power supply
system. After placing the wires through the
wire connectors, secure them by
tightening the screws.
A.
B.
D.
E.
C.
1
F.
2
Attach the back of the AKL08RF to the wall or
in a suitable location.
110mm/4.33in
Pump
100mm/3.93in
Actuator or Motorised valve
Power 120V
www.salusna.com Technical Helpline 1-650-360-1725
If you need to install the specified
external antenna and have set the
wireless jumpers to EXT:
a. Disconnect power.
b.
Remove the protective cap
from the antenna connection
on the bottom of the AKL08RF/
SAA6MI1.
c.
Screw the antenna into the
AKL08RF/SAA6MI1.
d.
Change the INT/EXT jumper position
to EXT position.
e.
Reconnect power. The AKL08RF
/SAA6MI1 will now use the
external antenna and not the
internal antenna.
i
The antenna (type A8RFA, gain 2.15dBi, made by
Salus ) for AKL08RF
/SAA6MI1 is sold separately.
110mm/4.33in