AC-F/G4x Series Outdoor Backlit Standalone Controllers Installation and Programming Manual Models: AC-F43 AC-F44 AC-G43 AC-G44
Copyright © 2018 by Rosslare. All rights reserved. This manual and the information contained herein are proprietary to ROSSLARE ENTERPRISES LIMITED and/or its related companies and/or subsidiaries’ (hereafter: "ROSSLARE"). Only ROSSLARE and its customers have the right to use the information. No part of this manual may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of ROSSLARE.
TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION MAY RESULT IN LEGAL PROCEEDINGS.
Table of Contents Table of Contents 1. Introduction ............................................................. 11 1.1 Controller Types ......................................................................................11 1.2 Box Content ..............................................................................................12 1.3 Ancillary Equipment ...............................................................................12 2. Technical Specifications ............................
Table of Contents 4.3.4 From Bypass to Normal Mode .............................................................. 27 4.4 Auxiliary Input and Output .................................................................28 4.5 REX Function.............................................................................................28 4.6 Tamper Feature .......................................................................................29 4.7 Lockout Feature (Keypad/Card Tamper) .........................
Table of Contents 5.9.6 Auxiliary Mode 5 ......................................................................................... 47 5.9.7 Auxiliary Mode 6 ......................................................................................... 48 5.9.8 Auxiliary Mode 7 ......................................................................................... 48 5.9.9 Auxiliary Mode 8 ......................................................................................... 49 5.9.
Table of Contents 5.17 Replacing a Normal/Secure Code....................................................66 A. Declaration of Conformity......................................... 67 B. Limited Warranty ......................................................
List of Figures List of Figures Figure 1: Drilling Holes Identification ........................................................................ 17 Figure 2: Wiring Diagram for Lock Strike Relay and REX .................................. 20 Figure 3: Wiring Diagram for Auxiliary Input & Output .................................... 21 Figure 4: Wiring Diagram for the BL-D40 External Sounder ............................
List of Tables List of Tables Table 1: Wiring Color Guide .......................................................................................... 18 Table 2: Programming Menus....................................................................................... 31 Table 3: Quick Reference Guide for Auxiliary Mode Setting ...........................
Introduction Notice and Disclaimer This manual’s sole purpose is to assist installers and/or users in the safe and efficient installation and usage of the system and/or product, and/or software described herein. BEFORE ATTEMPTING TO INSTALL AND/OR USE THE SYSTEM, THE INSTALLER AND THE USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY REQUIREMENTS AND OPERATING PROCEDURES. The system must not be used for purposes other than those for which it was designed.
Introduction All data contained herein subject to change without prior notice. In no event shall manufacturer be liable for any special, direct, indirect, incidental, consequential, exemplary or punitive damages (including, without limitation, any and all damages from business interruption, loss of profits or revenue, cost of capital or loss of use of any property or capital or injury).
Introduction 1. Introduction The AC-F4x series and AC-G4x series access control units are waterproof standalone controllers. All the units are suitable for both indoor and outdoor mounting. The unit(s) accepts up to 500 users and allows entry via a personal identification number (PIN) and/or by presenting a proximity card. 1.
Introduction 1.2 Box Content Before beginning, verify that all of the following is in the box. If anything is missing please report the discrepancy to your nearest Rosslare Office. One unit Installation kit 1.
Introduction BL-D40 external sounder (optional) – provides siren, bell, and chime. Magnetic contact (optional) – installed for door monitor capabilities. Other Rosslare accessories can be found at Rosslare's website: www.rosslaresecurity.
Technical Specifications 2. Technical Specifications AC-F43 AC-F44 AC-G43 AC-G44 Input VDC 12 to 24 VDC Voltage VAC 16 to 24 VAC Maximum Input Current 125 mA 160 mA 125 mA 160 mA 75 mA 95 mA 75 mA 95 mA (12 VDC) Standby Input Current (12 VDC) Maximum Relay Current 2A REX Input Normally Open (dry contact) Aux. Input Normally Open (dry contact) Max.
Technical Specifications AC-F43 Size (H x W x D) AC-F44 120.9 x 71.1 x 29.7 AC-G43 AC-G44 135.4 x 44.2 x 28.5 mm (4.7 x 2.8 x 1.2 in.) mm (5.3 x 1.7 x 1.1 in.) Weight 244 g (8.6 oz) 178 g (6.3 oz) * Measured using a Rosslare proximity card or equivalent. Range also depends on electrical environment and proximity to metal.
Installation 3. Installation Installation of an RFID reader adjacent to metallic surfaces might alter the reader’s specifications. To diminish this interference, use a plastic spacer when mounting the reader. 3.1 Mounting Prior to starting, select the location where the controller unit is to be mounted. To install the controller: 1. Peel off the back of the self-adhesive mounting label template and place it on the required mounting location. 2. At the bottom of the unit’s case, remove the screw.
Installation Figure 1: Drilling Holes Identification 5. Drill an additional 10-mm (7/16”) hole for the cable. When installing the reader on a metallic surface, cover the inside of the hole with a grommet or electrical tape. 6. Insert the unit’s cable wire into the cable hole and wire the unit as described in Section 3.2. 7. Screw the back plate into the surface. Ensure the screws are the size specified on the installation template. The unit can also be mounted using strong epoxy glue.
Installation 3.2 Wiring The unit is supplied with a 10-conductor 100-cm (40-in.) pigtail (18-AWG cable) with exposed wires coated with solder. To wire the controller: 1. Select the appropriate connections according to Table 1. Table 1: Wiring Color Guide 2. Color Description Red V input Black Ground Green REX/BL White In / Monitor Purple Lock: Com Gray Lock: N.O. Brown Lock: N.C. Blue Aux: Com Yellow Aux: N.O. Orange Aux: N.C.
Installation 3. Splice the controller pigtail wires to the corresponding ancillary devices and insulate each connection, including unused wires.
Installation Figure 2: Wiring Diagram for Lock Strike Relay and REX 20 AC-F/G4x Series Installation and Programming Manual
Installation Figure 3: Wiring Diagram for Auxiliary Input & Output AC-F/G4x Series Installation and Programming Manual 21
Installation Figure 4: Wiring Diagram for the BL-D40 External Sounder 22 AC-F/G4x Series Installation and Programming Manual
Operation 4. Operation • In the Operation chapter, “code” refers to a PIN code or proximity card depending on the unit you have. • Memory slots can be a proximity card or PIN code depending on the unit you have. 4.1 Modes of Operation In case of power failure, once the power is restored, the controller returns to Normal mode for security reasons. There are three modes of operation. 4.1.1 Normal Mode The left LED is green. Green Normal mode is the default mode.
Operation green for 10 seconds, during which the Secondary code must be entered. A Master user only needs to present the code once to gain entry. 4.1.3 Bypass Mode The left LED is orange. Orange In Bypass mode, access to the premises is dependent on whether the controller's Lock Strike Relay is programmed for Fail Safe Operation or Fail Secure Operation. When the Lock Strike is programmed for Fail Secure Operation, the door is locked until * is pressed.
Operation A normal user only has a primary code and is granted access only when the controller is in its Normal or Bypass mode. Secure A Secure user must have a Primary and Secondary code assigned, and the two codes must not be the same. The Secure user can gain access in any mode of operation. In Normal mode, the Secure user must use the Primary code to gain entry. In Secure mode, the Secure user must first enter the Primary and then the Secondary code to gain entry.
Operation 4.3 Switching Operational Modes The three modes of operation defined above can be changed through a few steps. 4.3.1 From Normal to Secure Mode The default factory setting for the normal/secure code is 3838. To change from Normal to Secure mode: 1. Enter the 4-digit Normal/Secure code. The left LED flashes red. 2. Red Press # to confirm the mode change. The left LED stops flashing.
Operation 2. Press # to confirm the mode change. The left LED stops flashing. Green The auxiliary input of the controller can also be used to switch the mode of operation from secure to normal and vice versa, if the auxiliary input is selected it de-activates the Norma/Secure mode code (see Section 5.9). 4.3.3 From Normal to Bypass Mode By default, there is no Normal/Bypass code. The Normal/Bypass code must first be programmed to use this function (see Section 5.
Operation 2. Press # to confirm the mode change. The left LED stops flashing. 4.4 Green Auxiliary Input and Output For optimum usability in different applications, the controller’s auxiliary input and output can be configured in 10 different modes of operation (see Section 5.9). 4.5 REX Function The REX button is located within the premises and is used to open the door from the inside. It is usually located in a convenient location, such as next to the door or at a receptionist’s desk.
Operation From the moment the REX button is pressed, the door is unlocked until the REX button is released. In this case, the Lock Strike relay only begins its countdown once the REX button is released. This feature is designed to keep the door open, when used in conjunction with fire systems. 4.6 Tamper Feature If the controller is forcibly opened or the controller is removed from the wall, a tamper event is triggered. A tamper signal is sent to the BL-D40 external sounder.
Operation 4.8 BL-D40 External Sounder The BL-D40 external sounder is designed for indoor use only and installed within the secured premises. The sounder can be powered by a 12 to 24 VDC power supply or by a 16 VAC transformer. The BL-D40 is capable of emitting four different types of audible and visual alerts: bell, chime, siren and strobe light. The bell sounds when the controller’s bell button is pressed.
Programming 5. Programming • In the Programming chapter, “code” refers to a PIN code or proximity card depending on the unit you have. • When entering a PIN or presenting a proximity card is mentioned, the meaning may vary between units. Programming is done solely via the unit’s keypad driven Programming Menu System. To reach the Programming Menu System, the controller must first be placed into Programming mode (see Section 5.1).
Programming Menu Description No. Default 4 5 6 Section 4-8 Digits Digits Digits Digits code 5 Change Normal/Bypass N/A 5.7 0004 5.8 2004 5.9 code 6 Change Door Release time 6 Define auxiliary inputs/outputs 6 Set Lockout Feature 4000 5.10 6 Backlight and LED 5100 5.11 N/A 5.12 N/A 5.13 N/A 5.14 N/A 5.
Programming 5.1 Entering the Programming Mode • The controller must be in Normal mode to enter the programming mode. • The factory default 4-digit programming code is 1234. • If a Programming code is not entered within 5 seconds, the controller returns to Normal mode. To enter Programming mode: 1. Press # twice. The left LED turns off and the right LED turns red. 2. Red Enter your 4-digit Programming code. The right LED turns green. 5.
Programming You hear 3 beeps. The left LED turns green and the right LED Green turns off. Wrong entries reset the controller back to Normal mode. While in Programming mode, if no key is pressed for one minute, the unit exits Programming mode and returns to Normal mode. 5.3 Changing the Open Code The Open code is mainly used as a method to quickly test the Lock Strike relay during installation.
Programming To change the Open code: 1. Enter Programming mode. 2. Press 1 to enter Menu 1. The left LED turns red. 3. Green Red Green Enter the new 4-digit Open code. You hear three beeps. The system returns to Normal mode.
Programming 5.4 Changing the Auxiliary Code The Auxiliary code is mainly used as a method to quickly test the Auxiliary relay during installation. For security reasons, when the first user is added to the controller or the open code is changed, the default auxiliary code is automatically deleted; non-default codes are not be erased automatically. • Auxiliary code does not function in Secure mode. • Auxiliary code only works when the Auxiliary mode is 0, 1, 8 or 9.
Programming 5.5 Changing the Programming Code • The Programming code cannot be erased; the code 0000 is invalid and does not erase the Programming code. • The factory default 4-digit Programming code is 1234. To change the Programming code: 1. Enter Programming mode. 2. Press 3 to enter Menu 3. The left LED turns green. 3. Green Green Green Enter the new 4-digit Programming code. You hear three beeps. The system returns to Normal mode.
Programming 5.6 Changing the Normal/Secure Code • When the Auxiliary mode is 1, 2, 3 or 4, the auxiliary input takes priority over the Normal/Secure code. • Code 0000 erases and deactivates the Normal/Secure code. To change the Normal/Secure code: 1. Enter Programming mode. 2. Press 4 to enter Menu 4. The left LED flashes red. 3. Green Red Green Enter the new 4-digit Normal/Secure code. You hear three beeps. The system returns to Normal mode. 5.
Programming 2. Press 5 to enter Menu 5. The left LED flashes orange. 3. Orange Green There are four different ways to program the Normal/Bypass code and door chime: Disable both Bypass code and the door chime. Enter the code 0000. Disable Bypass code and enable the door chime. Enter the code 0001. Enable Bypass code and disable the door chime. Enter any code ending with 0. Enable Bypass code and enable the door chime. Enter a code not ending with 0. You hear three beeps.
Programming 5.8 Setting Fail Safe/Secure Operation In this paragraph, the failsafe/fail secure operation of the door lock and the Door Lock Strike Release time are set. Setting the sounding period for the siren feature requires a BL-D40 external sounder. To set the Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time: 1. Enter Programming mode. 2. Press 6 to enter Menu 6. The left LED flashes green. 3.
Programming For example, 0312 means a Fail Secure Operation consisting of a 3-minute siren and a 12-second Lock Strike release time. You hear three beeps. Green The system returns to Normal mode. 5.9 Setting Auxiliary Modes The default auxiliary setting is 2004. Auxiliary Relay activation is subject to the user’s Auxiliary code assignment (excluding Shunt, which is activated by all users). For more details, see Section 5.14. To set Auxiliary modes: 1. Enter Programming mode. 2.
Programming 3. Construct a code using the following instructions: Second digit (Auxiliary Mode) In addition to the Lock Strike Relay and Lock Strike REX, the unit features an Auxiliary Input. The Auxiliary mode defines the function of the Auxiliary Input. Third and fourth digits (Auxiliary Setting) Each of the Auxiliary modes has a 2-digit setting that affects how the Auxiliary mode functions (Table 3). You hear three beeps. The system returns to Normal mode.
Programming Table 3: Quick Reference Guide for Auxiliary Mode Setting Auxiliary Mode 0 Auxiliary Auxiliary Function Activated Input AUX REX Output Auxiliary Auxiliary Relay by Settings (in seconds) Valid code or N.O. 01 to 99 Aux. Relay AUX REX Release Time 00 Aux. relay toggle 1 Normal/Secure Valid code N.O. switch 01 to 99 Aux. Relay Release Time 00 Aux. relay toggle 2 Normal/Secure Star button switch N.O. (*) 01 to 99 Aux. Relay Release Time 00 Aux.
Programming 6 Door Monitor Forced door N.C. 01 to 99 Forced 7 Door Monitor Door ajar N.C. 01 to 99 Ajar delay 8 LED control – N.O. 01 to 99 Aux. Relay delay Valid code Green Release time 00 Aux. relay toggle 9 LED control – Red Valid code N.O. 01 to 99 Aux. Relay Release time 00 Aux.
Programming The following subsections describe each Auxiliary mode. 5.9.1 Auxiliary Mode 0 Auxiliary input function: Activates the auxiliary output Auxiliary output activated by: Valid user code, Auxiliary code, Auxiliary input For example, in Auxiliary Mode 0, the controller can function as a two-door controller. The auxiliary relay is to be attached to the lock on the second door. The auxiliary setting defines the Door Open time for the second door.
Programming controller can be automatically switched from Normal mode (during office hours) to Secure mode (after office hours). 5.9.3 Auxiliary Mode 2 Auxiliary input function: Toggles Normal/Secure modes Auxiliary output activated by: Star Button (*) For example, in Auxiliary Mode 2, the auxiliary relay can function as a general purpose time switch that can be activated when * is pressed. The auxiliary setting establishes for how long the auxiliary relay is to be activated.
Programming from Normal mode (during office hours) to Secure mode (after office hours). 5.9.5 Auxiliary Mode 4 Auxiliary input function: Toggles Normal/Secure modes Auxiliary output activated by: direct shunt (explanation below) For example, in Auxiliary Mode 4, the controller is capable of bypassing an alarm zone by shunting an alarm system’s door sensor. The auxiliary output is to be wired in parallel to the door sensor output.
Programming opens; if the door closes, the auxiliary relay closes. When a valid code is entered, a countdown for maximum Shunt time, as defined by the auxiliary setting, begins; if the door is not closed before the maximum Shunt time, the alarm is triggered. 5.9.7 Auxiliary Mode 6 Auxiliary input function: Door Monitor Auxiliary output activated by: Forced entry For example, in auxiliary mode 6, the controller can trigger the auxiliary relay if the door has been forced.
Programming on the door. The auxiliary relay is to be wired to the alarm system. If the door is opened, the controller waits for the Door Ajar Delay time to elapse and if the door does not close prior to the end of this period, the controller activates the auxiliary relay. The auxiliary setting defines the Door Ajar time. If the BL-D40 external sounder is connected in the system and a door-ajar event occurs, the BL-D40 chimes every few seconds for 1 minute or until the door is closed. 5.9.
Programming 5.9.10 Auxiliary Mode 9 This mode controls the door indicator (right LED). The right LED is not lit when: • A valid code is entered • While in Secure mode when waiting for Secondary code. Auxiliary input function: Red LED control Auxiliary output activated by: Valid user code, Auxiliary code For example, in Auxiliary Mode 9, the controller can function as a 2-door controller and also provide LED indicator functionality control. The auxiliary relay is connected to the lock on the second door.
Programming red, and the controller beeps every two seconds. The default setting for the Lockout Feature is 4000 (Lockout Disabled). Using the lockout feature is highly recommended, especially when selecting to use short PIN code length (4 or 5 digits). To define the Lockout feature: 1. Enter Programming mode. 2. Press 6 to enter Menu 6. The left LED flashes green. 3.
Programming 5.11 Setting the Backlight Behavior The controller allows you to define the way the unit’s backlight works. To set the backlight behavior: 1. Enter Programming mode. 2. Press 6 to enter Menu 6. The left LED flashes green. 3.
Programming 5.12 Enrolling Primary and Secondary Codes 5.12.1 Primary Codes Definition Primary codes can only be enrolled to an empty user slot, a slot with no existing Primary code in the controller’s memory. A Primary code must be unique; for instance, one user’s primary code may not be the same as that of another user. Primary codes cannot be the same as system codes, such as: the Normal/Secure code or the Open code.
Programming A Secondary code can be the same as the primary code of any user. 5.12.3 Enrolling Methods There are two methods used to enroll primary and secondary codes: the standard method and the code search method. The Standard Method is used when the user slot number, for the user you wish to program, is known. You can program both primary and secondary codes using this method. The Code Search Method is mainly used when enrolling a secondary code and the user’s slot code is unknown.
Programming For example, User Slot 003 represents User #3. If the selected slot has no Primary code, the left LED flashes green, indicating that the controller is ready to accept a Primary Gree Orange code. If the selected slot already has a Primary code but no Secondary code, the left LED flashes red, indicating that the controller is Red Orange ready to accept a Secondary code.
Programming If the PIN or user card presented is valid, the left LED stops flashing and the controller is ready for you to enter the next 3-digit slot number (refer to Step 3) for the slot to which you want to assign a code. 5. Do one of the following: Press # to move to the next available user slot number. Enter another 3-digit user slot number. If you do not wish to continue enrolling codes, press # twice and the controller returns to Normal mode. 5.12.3.
Programming The controller is now waiting for the Primary code of the user to whom you want to add a Secondary code. 4. Perform one of the following: Enter the PIN code belonging to the user for whom you wish to add a Secondary code. Present the user card belonging to the user for whom you wish to add a Secondary code. The left LED flashes red. Red Orange If the Primary code entered is not valid, you hear a long beep and the unit continues to wait for a valid Primary code. 5.
Programming 5.13 Deleting Primary and Secondary Codes There are two methods to delete Primary and Secondary codes: a standard method and a search method. When deleting a user slot, both the primary code and the secondary code are erased. It is recommended that a record be kept of added and deleted users. This makes it easier to keep track of user slots’ status (empty or not). 5.13.
Programming If the user slot is empty, you hear a long beep and the unit returns to Normal mode. 4. Enter your 4-digit Programming code to confirm the deletion. If the Programming code is valid, three beeps are heard and the controller returns to Normal mode. If the Programming code is invalid, a long beep is heard and the controller returns to Normal mode. 5.13.2 Deleting Primary and Secondary Codes using the Code Search Method To delete the Primary and Secondary codes using the Code Search Method: 5.
Programming 8. Perform one of the following: Enter the PIN code of the Primary code belonging to the user you want to delete. Present the user card of the Primary code belonging to the user you want to delete. The left LED flashes red. 9. Red Orange Enter your 4-digit Programming code to confirm the deletion. If the Programming code is valid, you hear three beeps and the unit returns to Normal mode. If the Programming code is invalid, you hear a long beep and the unit returns to Normal mode. 5.
Programming There are two methods to assign relay codes to users: a standard method and a search method. 5.14.1 Relay Code Assignment using Standard Method To assign the relay code using Standard method: 1. Enter Programming mode. 2. Press 9 to enter Menu 9. Green The left LED turns green and the right LED turns orange. 3. Green Enter the 3-digit user slot for code 9 assignment. The left LED flashes green. 4.
Programming 5. Do one of the following: Press # to move to the next available user slot number. Enter another 3-digit user slot number. If you do not wish to continue enrolling codes, press # twice and the controller returns to Normal mode. 5.14.2 Relay Code Assignment using Search Method To assign the relay code using Search method: 1. Enter Programming mode. 2. Press 9 to enter Menu 9. Green The left LED turns green and the right LED turns orange. 3. Enter 000 for user slot access.
Programming 4. Do one of the following: Enter the PIN code of the Primary code belonging to the user you want to delete. Present the user card of the Primary code belonging to the user you want to delete. The left LED flashes green. 5.
Programming 5.15 Changing PIN Code Length/Factory Default Settings You must be very careful before using this command! Changing the PIN code length also erases the entire memory contents, including all user and special codes, and returns all codes to their factory default settings. To change the PIN code length: 1. Enter Programming mode. 2.
Programming If the Programming code is invalid, you hear a long beep and the controller returns to Normal mode without erasing the memory contents. 5.16 Replacing a Programming Code The unit must be in Normal mode; otherwise, this does not work. Make sure that the left LED is green before proceeding. To replace a Programming code: 1. Remove power from the controller. 2. Press and hold the REX button. 3. Apply power to the unit with the REX button pressed. 4. Release the REX button. 5.
Programming 5.17 Replacing a Normal/Secure Code The unit must be in Secure mode; otherwise, this does not work. Make sure that the left LED is red before proceeding. To replace a Normal/Secure code: 1. Remove power from the controller. 2. Press and hold the REX button. 3. Apply power to the unit with the REX button pressed. 4. Release the REX button. You now have 15 seconds to use the Normal/Secure code to return to the Normal mode. 5.
Declaration of Conformity A. Declaration of Conformity This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
Limited Warranty B. Limited Warranty The full ROSSLARE Limited Warranty Statement is available in the Quick Links section on the ROSSLARE website at www.rosslaresecurity.com. Rosslare considers any use of this product as agreement to the Warranty Terms even if you do not review them.
AC-F/G4x Series Asia Pacific, Middle Latin America East, Africa Rosslare Latin America Rosslare Enterprises Ltd. Kowloon Bay, Hong Kong Tel: +852 2795-5630 Fax: +852 2795-1508 support.apac@rosslaresecurity.com Buenos Aires, Argentina Tel: +54-11-4001-3104 support.la@rosslaresecurity.com China Rosslare Electronics (Shenzhen) Ltd. United States and Shenzhen, China Canada Tel: +86 755 8610 6842 Fax: +86 755 8610 6101 Rosslare Security Products, Inc.
CERT ISO 9001 ISO 14001 0706-0960101+04