2013 January AYC-Ex5 Family AYC-T65 Convertible 2x6 Ultra-Slim Backlit PIN & Prox Reader/Controller Installation and Programming Manual Ex5 Models: AYC-E55 AYC-E65BB AYC-E65BG AYC-E65BW T65 Models: AYC-T65B AYC-T65N Ex5 T65
Copyright © 2013 by Rosslare. All rights reserved. This manual and the information contained herein are proprietary to REL, RSP Inc. and/or their related companies and/or subsidiaries’ (hereafter:”ROSSLARE”). Only ROSSLARE and its customers have the right to use the information. No part of this manual may be re-produced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of ROSSLARE.
Table of Contents Table of Contents 1. General Information ................................................... 9 1.1 Introduction ............................................................................ 9 1.2 Reader/Controller Types......................................................... 10 1.3 Box Content ......................................................................... 10 1.4 Ancillary Equipment .............................................................. 11 1.4.1 Reader .......
Table of Contents 5.3.1 Return to Factory Default Settings ................................................33 5.3.2 6. Replacing a Lost Programming Code ............................................33 Controller Functionality............................................ 34 6.1 Normal, Secure, and Master Users.......................................... 34 6.2 Modes of Operation .............................................................. 35 6.2.1 Normal Mode ........................................
Table of Contents 6.9.12 Setting the Backlight Behavior ......................................................54 6.9.13 Enrolling Primary and Secondary Codes ........................................54 6.9.14 Deleting Primary and Secondary Codes .........................................58 6.9.15 Relay Codes Assignment...............................................................60 6.9.16 Relay Code Assignment using Standard Method ..........................60 6.9.
List of Figures List of Figures Figure 1: Drilling & Mounting Template for AYC-Ex5.......................................15 Figure 2: Drilling & Mounting Template for AYC-T65 ......................................15 Figure 3: Controller Application Wiring Diagram #1 ........................................17 Figure 4: Controller Application Wiring Diagram #2 ........................................18 Figure 5: Controller Application Wiring Diagram #3 ........................................
List of Tables List of Tables Table 1: Wiring Colors .....................................................................................16 Table 2: Reader Programming Menus ..............................................................21 Table 3: Keypad Transmission Format Option Number ....................................23 Table 4: Controller Programming Menu ..........................................................40 Table 5: Quick Reference Guide for Auxiliary Mode Setting ..........................
Notice and Disclaimer Notice and Disclaimer This manual’s sole purpose is to assist installers and/or users in the safe and efficient installation and usage of the system and/or product, and/or software described herein. BEFORE ATTEMPTING TO INSTALL AND/OR USE THE SYSTEM, THE INSTALLER AND THE USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY REQUIREMENTS AND OPERATING PROCEDURES. The system must not be used for purposes other than those for which it was designed.
General Information 1. General Information 1.1 Introduction The AYC-T65 and the AYC-Ex5 family are ultra-slim, vandal-resistant, integrated convertible readers and controllers with a Piezo Mullion keypad. These units automatically determine whether to function as a reader or as a controller. If the unit is connected to a standard access control unit, then it functions as a reader.
General Information 1.2 Reader/Controller Types The different types of units described in this manual are: Type E55 has PIN only Type E65 and T65 have PIN and Proximity card Backlight Keypad Type Proximity AYC-E55 Piezoelectric AYC-E65B Piezoelectric AYC-E65BB Piezoelectric AYC-T65 Piezoelectric Upon power-on reset, the AYC-Ex5 and AYC-T65 units search for the presence of Rosslare's secure application appurtenances.
General Information 1.4 Ancillary Equipment The following equipment is required to complete your installation: 1.4.1 1.4.
Technical Specifications 2. Technical Specifications Specification AYC-E55 AYC-E65B, AYC-E65BB AYC-T65 Electrical Characteristics Power Supply Type Linear type – recommended Operating Voltage Range 5–16 VDC (when used as a controller, provided by the secure application appurtenance) Input Current Standby 15 m A@12 VDC Max Input Current 40 mA @16 VDC LED Control Input 92 mA @12 VDC 105 mA @16 VDC Dry contact N.O.
Technical Specifications Specification AYC-E55 AYC-E65B, AYC-E65BB AYC-T65 Environmental Characteristics Operating Temp. Range -22°F to 150°F (-30°C to 65°C) Operating Humidity Outdoor Usage 0 to 95% (non-condensing) Weather-resistant, meets IP-68, epoxy potted, suitable for outdoor use Physical Characteristics Size (Height x Width x Depth) Weight 155 x 44 x 6.5 mm (6.1 x 1.73 x 0.256 in.) 120 g (0.265 lb) 155 x 44 x 9 mm 121 x 70 x 8 mm (6.1 x 1.73 x (4.77 x 2.76 x 0.354 in.) 0.31 in.) 143 g (0.
Technical Specifications Comes with mounting template for easier installation Comes with an installation kit that includes a security screw and a security screw tool 2.1.1 Reader Programmable keypad transmission format Programmable card transmission formats: Clock & Data and Wiegand 26-Bit (AYC-E65B, AYC-E65BB, AYC-T65) LED control input Programmable Facility code 2.1.
Installation 3. Installation 3.1 Mounting the AYC-Ex5 and AYC-T65 Before starting, select the location to mount the AYC-Ex5 or AYCT65. This location should be at shoulder height. For wall mounting, use the included mounting template as a guide for drilling holes for mounting screws and wiring. For US Gang Box mounting, no drilling is necessary.
Wiring Instructions 4. Wiring Instructions The unit is supplied with a 60-inch (1.5 meter) pigtail, having a 6conductor cable. To connect the unit to the controller, perform the following: Prepare the unit's cable by cutting the cable jacket back 1¼ inches and strip the wire ½ inch. Prepare the controller cable by cutting the cable jacket back 1¼ inches and strip the wire ½ inch. Splice the unit’s pigtail wires to the corresponding controller wires and cover each connection.
Wiring Instructions • The individual wires from the unit are color-coded according the Wiegand standard. • When using a separate power supply for the reader, this power supply and that of the controller must have a common ground. • The reader’s cable shield wire should preferably be attached to an earth ground, or a signal ground connection at the panel, or power supply end of the cable.
Wiring Instructions Figure 4 shows the auxiliary output connection using the internal power. Figure 4: Controller Application Wiring Diagram #2 Figure 5 shows the auxiliary output connection using external power.
Wiring Instructions Figure 6 shows how to wire a reader to the access control panel.
Reader Functionality 5. Reader Functionality The AYC-Ex5 series and the AYC-T65 can function both as a reader and as a controller. If the unit is connected to standard access controller, it functions as a reader, indicated by one beep immediately after power-on reset. The following explains how the AYC-Ex5 and AYC-T65 function as a reader. 5.1 Transmit Mode When the unit is in Transmit mode, it is ready to receive data from a presented proximity card or an entered PIN code.
Reader Functionality Default factory settings are marked by a "*" sign.
Reader Functionality 2. Enter your 4-digit Programming code. If the Programming code is valid, the door LED turns green and the unit is in Programming mode. 5.2.2 Door/Program Mode/Transmit Green • The factory 4-digit Programming code is 1234. • If a Programming code is not entered within 30 seconds, the unit returns to Transmit mode. Exiting Programming Mode 1. Press # to exit the Programming mode at any time. Mode/Transmit Door/Program Red You hear a beep.
Reader Functionality The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3. Enter the appropriate option number for the keypad transmission format that you wish to select. If an incorrect option number is entered, the reader returns to Transmit mode and the keypad transmission format remains unchanged. 4. System returns to Transmit mode You hear three beeps. Mode/Transmit The Program LED turns off and the Transmit LED turns red.
Reader Functionality More information on each of the different keypad transmission formats is available below and on the following pages. 5.2.3.2 Option 1: Single Key, 6-Bit Wiegand (Rosslare Format) Each key press immediately sends 4 bits with 2 parity bits added – even parity for the first 3 bits and odd parity for the last 3 bits. 0= 1 1010 0 ="A" in Hexadecimal 1= 0 0001 0 2= 0 0010 0 3= 0 0011 1 4= 1 0100 1 5= 1 0101 0 5.2.3.
Reader Functionality 0 = 11110000 1 = 11100001 2 = 11010010 3 = 11000011 6 = 10010110 7 = 10000111 8 = 01111000 9 = 01101001 4 = 10110100 5 = 10100101 = 01011010 = "A" in Hexadecimal # = 01001011 = "B" in Hexadecimal 5.2.3.5 Option 4: 4 Keys Binary + Facility Code, Wiegand 26Bit This option buffers 4 keys and outputs keypad data with a 3-digit Facility code like a standard 26-bit card output. The Facility code is set in Programming Menu number four and can be in the range 000 to 255.
Reader Functionality 5.2.3.6 Option 5: 1 to 5 Keys + Facility Code, Wiegand 26-Bit Option 5 buffers up to 5 keys and outputs keypad data with a Facility code like a 26-Bit card output. The Facility code is set in Programming Menu number four and can be in the range 000 to 255. The factory default setting for the Facility code is 000 (see Section 5.2.6). The keypad PIN code can be one to five digits in length and can range between 1 and 65,535.
Reader Functionality 5.2.3.7 Option 6: 6 Keys BCD and Parity Bits, Wiegand 26-Bit Option 6 sends buffer of 6 keys, adds parity and sends a 26-Bit BCD message. Each key is a four bit equivalent of the decimal number. The keypad PIN code must be 6 key presses long. On the sixth key press of the 6-digit PIN code, the data is sent across the Wiegand Data lines as a BCD message.
Reader Functionality The MD-P64 interface unit outputs the data received to 7 outputs emulating a keyboard. The interface unit does not affect any data that it receives from the proximity reader whether it is Wiegand 26-Bit or Clock & Data. Key pressed = ASCII Value 0 = '0' ( 0x30 hex ) 1 = '1' ( 0x31 hex ) 2 = '2' ( 0x32 hex ) 3 = '3' ( 0x33 hex ) 4 = '4' ( 0x34 hex ) 5 = '5' ( 0x35 hex ) 5.2.3.
Reader Functionality 5.2.4 Selecting Proximity Card Transmission Format The AYC-Ex5 and AYC-T65 has three different proximity card formats to select from. To select the prox imity card reader transmission format: 1. Enter Programming mode. Door/Program Mode/Transmit Green 2. Press “2” to enter Menu 2. The Transmit LED turns red. Door/Program Mode/Transmit Red Green 3.
Reader Functionality the card buffer and the PIN code entry buffer, generates a medium length beep, and be ready to receive a new card. The keypad PIN code can be one to five digits in length in the range of 0 to 99,999. When entering a keypad PIN code, the # key must be pressed to signify the end of the PIN entry. When pressing the # key press, the data is sent by the Wiegand data lines.
Reader Functionality 5.2.5 Changing the Programming Code 1. Enter Programming mode. Door/Program Mode/Transmit Green 2. Press “3” to enter Menu 3. The Transmit LED turns red. Door/Program Mode/Transmit Red Green 3. Enter the new 4-digit code you wish to set as the Programming code. The system returns to Transmit mode. You hear three beeps. The Program LED turns off and the Transmit LED turns red. 5.2.
Reader Functionality You hear three beeps. The Program LED turns off and the Transmit LED turns red. 5.3 Door/Program Mode/Transmit Red • The Facility code can be in the range of 000 to 255. • The default Facility code is 0. Setting the Backlight 1. Enter Programming mode. Mode/Transmit Door/Program Green 2. Press “6” to enter Menu 6. The Transmit LED turns red. Mode/Transmit Red Door/Program Green 3.
Reader Functionality 5.3.1 Return to Factory Default Settings You must be very careful before using this command! This erases the entire memory and return all codes to their factory default setting. 1. Enter Programming mode. Door/Program Mode/Transmit Green 2. Press “0” to enter Menu 0. The Transmit and Program LEDs flash red. Mode/Transmit Door/Program Red Red 3. Enter your 4-digit programming code. If the Programming code is valid, all memory is erased.
Controller Functionality 6. Controller Functionality The AYC-Ex5 and AYC-T65 can function both as a reader and as a controller. If the unit is connected to Rosslare’s secure application appurtenance, it functions as a controller indicated by two beeps immediately after power-on reset. The Lock Strike and Auxiliary outputs, as well as the REX input, are not located on the AYC-Ex5 or AYC-T65 unit, eliminating the possibility of unauthorized entry to the restricted area.
Controller Functionality Secure user A Secure user must have a Primary and Secondary code programmed; the two codes must not be the same. The Secure user can gain access when the unit is in any of its three modes of operation. In Normal mode, the Secure user must use their Primary code to gain entry. In Secure mode, the Secure user must present both the Primary and Secondary codes to gain entry. Master User A Master user must have both Primary and Secondary codes programmed with the same PIN code.
Controller Functionality When the Lock Strike is programmed for Fail Safe Operation, the door is constantly unlocked. 6.2.3 Secure Mode The Mode LED is red. Door/Program Mode/Transmit Red Only Secure and Master users can access the premises during the Secured mode. A Secure user must enter their Primary and Secondary codes to gain entry. After entering their Primary code, the Door LED flashes green for 10 seconds, during which the Secondary code must be entered.
Controller Functionality 2. Press the “#” key to confirm the mode change. Mode LED turns green. 6.2.4.3 Mode/Transmit Door/Program Green Changing from Normal Mode to Bypass Mode See Section 6.9.7 to create/modify the Normal/Bypass code. 1. Enter the Normal/Secure code. Mode/Transmit The Mode LED flashes orange. Mode/Transmit Door/Program Green Door/Program Orange 2. Press the “#” key to confirm the mode change. Mode LED turns orange. 6.2.4.
Controller Functionality 6.4 Door Alarms Door alarms can be generated by connecting the Auxiliary Input to a Door Position Switch. Either Door-Forced or Door-Ajar conditions are supported, as well as, a configurable delay timer for each alarm type. Only one door alarm is enabled at any one time. Door alarms may activate auxiliary output and siren depending on the auxiliary settings. 6.
Controller Functionality passes. After this time, the door is locked even if the REX button is not released. 6.8 Fail Safe Operation – From the moment the REX button is pressed, the door is unlocked until the REX button is released, plus the Lock Strike Release Time. In this case, the Lock Strike Relay only begins its count down once the REX button is released.
Controller Functionality Table 4: Controller Programming Menu Menu Menu Description No.
Controller Functionality 6.9.2 Exiting Programming Mode 1. Press the # key twice within 2 seconds. You hear 3 beeps. The Door LED turns off and the Mode LED returns to Normal mode. Mode/Transmit Door/Program Green Wrong entries reset the controller back to Normal mode. While in Programming mode, if no key is pressed for one minute, the unit exits Programming mode and returns to Normal mode. 6.9.
Controller Functionality • Lock Strike Code 1 does not work in the Secure mode. • Wrong entries returns the controller to Normal mode. • Code 0000 erases the Lock Strike Code 1. • The factory default 4-digit Lock Strike code is 2580. 6.9.4 Changing Auxiliary Code The Auxiliary code is mainly used as a method to quickly test the Auxiliary Relay during installation. When the first user is added to the controller, the default Auxiliary code is automatically deleted.
Controller Functionality 6.9.5 Changing the Programming Code 1. Enter Programming mode. Door/Program Mode/Transmit Green 2. Press “3” to enter Menu 3. The Mode LED turns green. Door/Program Mode/Transmit Green Green 3. Enter the new code you wish to set as the Programming code. The system returns to Normal mode. You hear three beeps. • • 6.9.6 Door/Program Mode/Transmit Green Programming code cannot be erased, meaning the code 0000 is not valid and does not erase the Programming code.
Controller Functionality 6.9.7 • Code 0000 erases the Normal/Secure code. • This code is disabled if the Auxiliary Input is set to toggle between Normal and Secure access modes. • Default Normal/Secure code is 3838. Changing the Normal/Bypass Code and Door Chime Settings 48B 1. Enter Programming mode. Mode/Transmit Door/Program Green 2. Press “5” to enter Menu 5. The Mode LED flashes orange. Mode/Transmit Door/Program Orange Green 3. Enter the new code you wish to set as Normal/Secure code.
Controller Functionality The system returns to Normal mode. You hear three beeps. The Door LED turns off and the Mode LED turns green. 6.9.8 Mode/Transmit Door/Program Green Setting Fail Safe/Secure Operation, Tamper Siren and Lock Strike Release Time 1. Enter Programming mode. Mode/Transmit Door/Program Green 2. Press “6” to enter Menu 6. The Mode LED flashes green. Mode/Transmit Door/Program Green Green 3.
Controller Functionality The system returns to Normal mode. You hear three beeps. The Door LED turns off and the Mode LED turns green. Mode/Transmit Door/Program Green The default value is 0004, which corresponds to Fail Secure operation, no siren, and 4-seconds Lock Strike release time. 6.9.9 Defining the Auxiliary Input and Output 1. Enter Programming mode. Mode/Transmit Door/Program Green 2. Press “6” to enter Menu 6. The Mode LED flashes green. Mode/Transmit Door/Program Green Green 3.
Controller Functionality The system returns to Normal mode. You hear three beeps. The Door LED turns off and the Mode LED turns green.
Controller Functionality Table 5: Quick Reference Guide for Auxiliary Mode Setting Aux. Mode Aux. Input Function Aux. Output Activated by Aux. Relay Aux. Settings (in seconds) 0 AUX REX Valid code or AUX REX N.O. 01 to 99 Aux. relay release time 1 Normal/Secure switch Valid code N.O. 01 to 99 Aux. relay release time 2 Normal/Secure switch Star button () N.O. 01 to 99 Aux. relay release time 3 Normal/Secure switch Tamper event N.C. 01 to 99 Aux.
Controller Functionality 6.9.10 Detailed Reference Guide The following are brief descriptions of each auxiliary mode. To implement the features of each mode, refer to Section 6.9.9. 6.9.10.1 Auxiliary Mode 0 Auxiliary input function: Activates the auxiliary output Auxiliary output activated by: Valid user code, Auxiliary code, and Auxiliary input For example, in Auxiliary Mode 0, the controller can function as a two-door controller. The auxiliary relay is to be attached to the lock on the second door.
Controller Functionality 6.9.10.3 Auxiliary Mode 2 Auxiliary input function: Toggles Normal/Secure modes Auxiliary output activated by: Bell Button () For example, in Auxiliary Mode 2, the auxiliary relay can function as a general purpose time switch that can be activated when the Bell button () is pressed. The auxiliary setting establishes for how long the auxiliary relay is to be activated. The auxiliary input can switch the mode of operation of the controller between Normal and Secure modes.
Controller Functionality 6.9.10.6 Auxiliary Mode 5 Auxiliary input function: Door Monitor Auxiliary output activated by: Shunt (explanation below) For example, in Auxiliary Mode 5, the controller is capable of shunting an alarm system. In this mode, the auxiliary input is to be wired to the magnetic contact switch on the door. The auxiliary relay is wired to the alarm system.
Controller Functionality if the door does not close prior to the end of this period, the controller activates the auxiliary relay. The auxiliary setting defines the door-ajar time. 6.9.10.9 Auxiliary Mode 8 Auxiliary input function: Green LED control Auxiliary output activated by: Valid user code, Auxiliary code For example, in Auxiliary Mode 8, the controller can function as a two-door controller and also provide indicator functionality control.
Controller Functionality 6.9.11 Setting the Lockout Feature If the controller is presented with wrong codes several times consecutively, the unit goes into Lockout mode. When a lockout occurs, the controller keypad and reader are locked so no codes can be entered until the set lockout period expires. During Lockout, Mode LED is off, Door LED flashes red, and the controller beeps every two seconds. The default setting for the Lockout Feature is 4000 (Lockout Disabled).
Controller Functionality 6.9.12 Setting the Backlight Behavior The controller allows you to define the way the unit’s backlight works. 1. Enter Programming mode. Door/Program Mode/Transmit Green 2. Press “6” to enter Menu 6. The Mode LED flashes green. Mode/Transmit Door/Program Green Green 3. Construct a code using the following instructions: The first digit is “5” indicating the backlight and LED option. The second key can be 0-3 indicating the type of activity.
Controller Functionality Primary codes cannot be the same as any system codes, such as the Normal/Secure code or Lock Strike code. Users who hold a Primary code can gain entry only during Normal mode. 6.9.13.2 Secondary Codes Secondary codes can only be enrolled to a user slot that already has a Primary code enrolled but has no Secondary code. Secondary codes do not have to be unique, meaning multiple users can all hold the same Secondary code.
Controller Functionality 6.9.13.4 Enrolling Primary & Secondary Codes using Standard Method 1. Enter Programming mode. Door/Program Mode/Transmit Green 2. Press “7” to enter Menu 7. The Door LED turns orange. Mode/Transmit Door/Program Orange 3. Enter the 3-digit user slot number between 001and 500 that you wish to enroll a Primary or Secondary code to. For example, User Slot 003 represents User #3.
Controller Functionality 4. Enter the 4- to 8-digit PIN code that you want to assign as the Primary or Secondary code for this slot number. If the PIN that is entered is valid, the Mode LED stops flashing and then the controller is ready for you to enter the next 3-digit slot number (refer to Step 2) that you want to assign a code to. 5. Press the “#” key to move to the next slot number. If you do not wish to continue enrolling codes, press the “#” key twice and the controller returns to Normal mode. 6.9.
Controller Functionality If the Primary code entered is not valid, you hear a long beep and the unit continues to wait for a valid Primary code. 6. Enter the 4- to 8-digit code to be used as the Secondary code. If the Secondary code is valid, the controller beeps three times and returns to Normal mode. If the Secondary code is invalid, the controller sounds a long beep, and the unit continues to wait for a valid Secondary code to be entered. 6.9.
Controller Functionality 4. Enter your programming code to confirm the deletion. If the programming code is valid, three beeps are heard and the controller returns to Normal mode. If the programming code is invalid, a long beep is heard and the controller returns to Normal mode. It is recommended that a record be kept of added and deleted users so that it is easier to keep track of which user slots are empty and which user slots are not. 6.9.14.2 Deleting Primary & Secondary Codes using Search Method 1.
Controller Functionality 5. Enter your Programming code to confirm the deletion. If the Programming code is valid, you hear three beeps and the unit returns to Normal mode. If the Programming code is invalid, you hear a long beep and the unit returns to Normal mode. It is recommended that a record be kept of added and deleted users so that it is easier to keep track of which user slots are empty and which user slots are not. 6.9.
Controller Functionality 4. Enter the assignment digit for the current user slot: “1” activates the Lock Strike relay only default “2” activates the Auxiliary relay only “3” activates the Lock Strike and Auxiliary relays If the assignment code is valid, the Mode indicator stops flashing. The controller is now waiting for another slot number. 5. Press the # key to move to the next slot or enter a new slot number.
Controller Functionality 5. Enter the assignment digit for the current user slot: “1” activates the Lock Strike relay only default “2” activates the Auxiliary relay only “3” activates the Lock Strike and Auxiliary relays If the assignment digit is valid, three beeps are heard and the controller returns to Normal mode. If the assignment digit is invalid, a long beep sounds and the controller waits for another assignment digit to be entered. 6.9.
Controller Functionality If the Programming code is valid, all memory is erased. You hear three beeps and the controller returns to Normal mode. If the Programming code is invalid, you hear a long beep and the controller returns to Normal mode without erasing the memory contents. 6.9.19 Replacing a Lost Programming Code The AYC-Ex5 and AYC-T65 must be in Normal mode; otherwise, this does not work. Make sure that the Mode LED is green before proceeding. To replace a lost Programming code: 1.
Declaration of Conformity A. Declaration of Conformity This declaration applies to the AYC-T65 model only. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation.
Limited Warranty B. Limited Warranty ROSSLARE ‘S FIVE-YEAR LIMITED WARRANTY is applicable worldwide. This warranty supersedes any other warranty. ROSSLARE'S FIVE-YEAR LIMITED WARRANTY is subject to the following conditions: WARRANTY Warranty of ROSSLARE'S products extends to the original purchaser (Customer) of the ROSSLARE product and is not transferable.
Limited Warranty minimum US$ 50.00 or equivalent charge will be applied to each Product for labor required in the evaluation. ROSSLARE will repair or replace, at its discretion, any product that under normal conditions of use and service proves to be defective in material or workmanship. No charge will be applied for labor or parts with respect to defects covered by this warranty, provided that the work is done by ROSSLARE or a ROSSLARE authorized service center.
Limited Warranty LIMITED WARRANTY TERMS This warranty sets forth the full extent of ROSSLARE’S warranty. The terms of this warranty may not be varied by any person, whether or not purporting to represent or act on behalf of ROSSLARE. This limited warranty is provided in lieu of all other warranties. All other warranties expressed or implied, including without limitation, implied warranties of merchantability and fitness for a particular purpose, are specifically excluded.
AYC-Ex5 Asia Pacific, Middle East, Africa Rosslare Enterprises Ltd. Kowloon Bay, Hong Kong Tel: +852 2795-5630 Fax: +852 2795-1508 support.apac@rosslaresecurity.com United States and Canada Rosslare Security Products, Inc. Southlake, TX, USA Toll Free: +1-866-632-1101 Local: +1-817-305-0006 Fax: +1-817-305-0069 support.na@rosslaresecurity.com Latin America Rosslare Latin America Buenos Aires, Argentina support.la@rosslaresecurity.com China Rosslare Electronics (Shenzhen) Ltd.