Manual Owners & Installation LISTINGS AND CODE APPROVALS These gas appliances have been tested in accordance with AS4553, NZS 5262 and have been certified by the Australian Gas Association for installation and operation as described in these Installation and Operating Instructions. Your unit should be serviced annually by an authorised service person.
To the New Owner: Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY. The PG121-1 / PG121LC-1 / PG121RC-1 / PG131-1 has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The model PG121-1 / PG121LC-1 / PG121RC-1 / PG131-1 has been approved by the Australian Gas Association for both safety and efficiency.
TABLE OF CONTENTS DATA BADGE Data Badge................................................................. 4 INSTALLATION Important Message ..................................................... 5 Before You Start ......................................................... 5 General Safety Information......................................... 5 Installation Checklist ................................................... 5 Specifications .............................................................
SAFETY LABEL This is a copy of the label that accompanies each PG121-1 / PG121LC-1 / PG121RC-1 / PG131-1 Zero Clearance Room Sealed Gas Fireplace. We have printed a copy of the contents here for your review. The safety label is located on the front inside base of the unit, visible when the bottom louver is open. NOTE: Regency units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.
INSTALLATION IMPORTANT: SAVE THESE INSTRUCTIONS The Regency PG121/PG121LC/PG121RC/ PG131-NG1 or PG121/PG121LC/PG121RC/ PG131-LPG1 Room Sealed Gas Fireplace must be installed in accordance AG601 and NZS 5261 and with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation.
INSTALLATION SPECIFICATIONS PG121-1 - See Thru Note: These units are non-load bearing.
INSTALLATION PG121LC-1 - Left Corner Unit Note: These units are non-load bearing.
INSTALLATION LOCATING YOUR GAS FIREPLACE 1) When selecting a location for your stove, ensure that the clearances are met as outlined in the "Clearances" section. A) PG121-1 - See Thru 2) Provide adequate clearances for servicing. 3) The appliance must be installed on a flat, solid, continuous surface (e.g. wood, metal, concrete). This may be the floor, or raised up on a platform to enhance its visual impact.
INSTALLATION CLEARANCES The clearances listed below are Minimum distances unless otherwise stated (refer to diagrams in "Locating Your Gas Fireplace" section): Clearance to Combustibles from: Back 0" (0mm) Side 0" (0mm) Floor 0" (0mm) CAUTION REQUIREMENTS: The top, back and sides of the fireplace are defined by standoffs. The metal ends of the standoffs may NOT be recessed into combustible construction. Determine the total thickness of the finished floor (eg.
INSTALLATION FRAMING AND FINISHING 1) For ease of installation, frame your fireplace after it is positioned and the flue system is installed. Remember to install the top standoffs. Use 2x4's and frame to local building codes. PG121 (See Thru) CAUTION: Verify your fireplace dimensions, framing methods and finished wall facing details before framing. Determine the total thickness of facing material - drywall plus ceramic tiles, slate, etc.
INSTALLATION FACING & FINISHING REQUIREMENTS This fireplace is supplied with a 3" metal extension trim above the fireplace. The extension trim may be replaced if the framing is faced with a noncombustible material placed flush with the front and side face of the unit and extending from the top of the unit. (ie. tile, slate, etc.) UNIT ASSEMBLY PRIOR TO INSTALLATION The 4 Top Standoffs must be correctly positioned and attached to the top before unit is slipped into position.
INSTALLATION EXTERIOR FLUE TERMINATION LOCATIONS Minimum clearances required for balanced flue terminals or the flue terminals of outdoor appliances according to AS5601-2004 (AGA gas installation code) or NZS 5261 (New Zealand) Minimum Clearance (mm) a b c d e f g h j k Below eaves, balconies or other projections: - Appliances up to 50 MJ/h input 300 - Appliances over 50 MJ/h input 500 From the ground or above a balcony 300 From a return wall or external corner 500 From a gas meter (M) 1000 From an elec
INSTALLATION FLUEING ARRANGEMENT - HORIZONTAL TERMINATIONS Regency Direct Vent System (Flex) Horizontal Terminations Only These flueing systems, in combination with the PG121-1 / PG121LC-1 / PG121RC-1 / PG131-1 Direct Vent Gas Fireplace, have been tested and listed as a direct flue heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Flue Terminal Locations diagram.
INSTALLATION SIMPSON DURA-VENT FLUEING Horizontal or Vertical Terminations The Simpson Dura-Vent Direct Vent System offers a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized finish. We recommend using the galvanized finish for installation with the PG121-1 / PG121LC-1 / PG121RC-1 / PG131-1.
INSTALLATION FLUEING ARRANGEMENTS - HORIZONTAL TERMINATIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM The diagram below shows examples of horizontal termination arrangements using one, two, or three 90o elbows (two 45o elbows equal one 90o elbow). Note: 1) A maximum of three 90o elbows are permitted. 2) Minimum distance between elbows is 1 ft. (305mm). • • • • • Simpson Dura-Vent Maintain clearances to combustibles. 4" inner diameter Horizontal flue must be supported every 3 feet.
INSTALLATION Horizontal Flueing with Two (2) 90o Elbows Option A) B) C) D) E) F) V 1' (305mm) Minimum 2' (610mm) Minimum 3' (914mm) Minimum 4' (1.22m) Minimum 5' (1.5m) Minimum 6' (1.86m) Minimum H + H1 2' (610mm) Maximum 5' (1.5m) Maximum 8' (2.4m) Maximum 11' (3.35m) Maximum 14' (4.27m) Maximum 15' (4.5m) Maximum With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 15 feet total horizontal.
INSTALLATION FLUEING ARRANGEMENTS - VERTICAL TERMINATIONS SIMPSON DURA-VENT DIRECT VENT GS SYSTEM • • • • Flue must be supported at offsets Maintain clearances to combustibles. Firestops are required at each floor level and whenever passing through a wall. Must use optional flue adapter when using Simpson Dura-Vent pipe (Part# 510-994). The PG121-1 / PG121LC-1 / PG121RC-1 / PG131-1 is approved for a maximum 35 ft. (10.
INSTALLATION Vertical Flueing with Two (2) 90o Elbows Option A) B) C) D) E) F) V 1' (305mm) Minimum 2' (610mm) Minimum 3' (914mm) Minimum 4' (1.22m) Minimum 5' (1.5m) Minimum 6' (1.86m) Minimum Vertical Flueing with Two (2) 90o Elbows Option A) B) C) D) H 4' (1.22m) Maximum 6' (1.86m) Maximum 9' (2.7m) Maximum 12' (3.6m) Maximum 15' (4.5m) Maximum 17' (5.1m) Maximum With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 17 feet total horizontal.
INSTALLATION Vertical Flueing with Three (3) 90o Elbows Option A) B) C) D) V + V1 2' (610mm) Minimum 3' (914mm) Minimum 4' (1.22m) Minimum 5' (1.5m) Minimum H + H1 3' (914mm) Maximum 6' (1.86m) Maximum 9' (2.7m) Maximum 12' (3.6m) Maximum With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal. Please note minimum 1 foot between 90o elbows is required.
INSTALLATION TERMINATION 1) Maintain the 1-1/4" clearances (air spaces) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafter, or other nearby combustible surfaces. Do not pack air spaces with insulation. Check pages 17-19 for the maximum vertical rise of the flueing system and the maximum horizontal offset limitations. Diagram 3 pipe to the flue termination, slide the Wall Thimble (Part # 942) over the flue pipe.
INSTALLATION can result from high wind conditions near big trees or adjoining roof lines, in these cases, increasing the flue height may solve the problem. 7) Ensure flue is vertical and secure the base of the flashing to the roof with roofing rails, slide storm collar over the pipe section and seal with a mastic. Note: To make the installation more aesthetically pleasing, we recommend framing out a square to mount the terminal to. 8) Install the vertical termination cap by twistlocking it.
INSTALLATION Conversion Kit# 360-968 from NG to LPG THIS CONVERSION MUST BE DONE BY A QUALIFIED GAS FITTER IF IN DOUBT DO NOT DO THIS CONVERSION !! Conversion Kit contains: Qty. 1 1 1 1 1 1 Part # 904-529 904-641 918-590 908-528 910-037 918-578 Description 5/32" Allen Key Burner Orifice #50 "Converted to LPG" label Red "LPG" label #30 ULPG Pilot Orifice Instruction Sheet 6) Remove burner orifice with a 1/2" spanner and discard. Use another spanner to hold on to the elbow behind the orifice.
INSTALLATION 16) Remove the control box cover by undoing the 3 screws. Maneuver through antenna. 21) Adjusting the Outlet Pressure All the adjustments must be carried out in the following order: 22) At the end of all setting and adjustment operations, check electrical insulation and gas leaks. Remove the modulator plastic cap (A) using needle nose pliers. 23) Re-install the glass, louvers and trims. 24) Check operation of flame control. Maximum pressure: Turn the unit ON to its highest input rating.
INSTALLATION PG121/PG121LC/PG121RC/ PG131-NG1 System Data inlet and manifold pressures should be checked using the valve pressure ports on the valve. a soap and water solution or gas leak detector. Do not use open flame for leak testing. Periodically check the pilot flames. Correct 1) Make sure the valve is in the "OFF" position. #31 Max. Input Rating Min. Input Rating 41 mj. 22 mj. Supply Pressure min. 1.
INSTALLATION LOG SET INSTALLATION Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation. 3) Place Log 326 on the front right side of the burner. Ensure that the notches on the far right side of the log fit into the grate posts. Push back side of the left end of the log up against the tab on the burner.
INSTALLATION Repeat step 4 on the opposite side of the burner. 6) Place Log 328 on the middle right side of the burner. Ensure that the log fits over the 2nd grate post from the right. 327 327 328 5) Place Log 329 on the middle left side of the burner. Rest the bottom of the Log onto the second grate post from the left. Ensure that the log fits into a pin that is on Log 326. Grate Post Repeat step 6 on the opposite side of the burner.
GLASS DOOR REMOVAL 1) Remove the 8 screws that secure the glass door. FINISHING TRIM LOUVERS & GRILLS 1) Slide the Side Finishing Trim up into the slot in the top flange of the fireplace. Push tight against the magnet at the base of the unit. 1) Attach the screws provided to the top left and right corners. NOTE: Do not tighten the screw entirely, ensure that some room is left to be able to hang the grill or louver over the screw. Slide Trim into slot.
INSTALLATION REMOTE CONTROL Use the Regency Remote Control Kit approved for this unit. Use of other systems may void your warranty. The remote control kit comes with a hand held transmitter and a wall mounting plate. 1) Choose a convenient location to mount the hand held transmitter, protection from extreme heat is very important. The remote can also be used as a wall thermostat. WIRING DIAGRAM This heater requires a 240V A.C. supply for the gas control to operate. A 240V A.C.
OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Before operating this appliance, proceed through the following check list. 1) Read and understand these Instructions before operating this appliance. 2) Check to see that all wiring is correct and enclosed to prevent possible shock. 3) Check to ensure there are no gas leaks. 4) Make sure the three pieces of door glass are properly positioned. Never operate the appliance with any of the glass removed or with the door open.
OPERATING INSTRUCTIONS FIRST FIRE DO NOT BURN THE APPLIANCE WITHOUT THE GLASS FRONT IN PLACE. The first fire in your stove is part of the paint curing process. To ensure that the paint is properly cured, it is recommended that you burn your fireplace for at least four (4) hours the first time before you use it with the fan on. When first operated, the unit will release an odour caused by the curing of the paint, the burning off of any oils remaining from manufacturing.
OPERATING INSTRUCTIONS COPY OF THE LIGHTING PLATE INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING This appliance must be installed in accordance with local codes, if any; if not, follow the current CAN1-B149/ANSI Z 223.1 (Australia: AS5601-2004, New Zealand: NZS 5261) WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
MAINTENANCE 3) Check for evidences of excessive condensation, such as water droplets forming in the inner liner, and subsequently dripping out the joints, Continuous condensation can cause corrosion of caps, pipe, and fittings. It may be caused by having excessive lateral runs, too many elbows, and exterior portions of the system being exposed to cold weather. 4) Inspect joints, to verify that no pipe sections or fittings have been disturbed, and consequently loosened.
MAINTENANCE 6) Remove the burner by removing the 4 screws. 9) Open the bottom louvre and remove the 2 screws which secure the front cover to the valve tray. 15) Remove the 16 screws that secure the valve tray. 16) Lift the entire assembly out. 7) Slide the burner assembly away from the orifice and lift out. 10) Unplug the 5 pin Molex Connector and carefully pull out the control box. 17) To replace the burner tray assmebly, reverse these instructions.
MAINTENANCE MANUAL CONTROL REPLACEMENT 7) Remove the ECS box cover by undoing the 3 screws. 1) Unplug the power source. 2) Open the bottom louver. 3) Undo the 3 screws to remove the manual control box from the louver. 8) Unplug in the CAT5 cable of the manual control box from the connector in the ECS box. 4) Remove the louver bracket from the manual control box by undoing one screw.
PARTS LIST ELECTRONIC COMPONENTS PARTS LIST Note: Depending on the model, the diagram below may not be exactly as shown - for reference purposes only.
PARTS LIST PG121-1 (SEE THRU) MAIN ASSEMBLY Part # 1) 9) 10) 11) 17) 24) 360-528/P Door Assy Front - Tempered 360-946 Door Assy Front - Ceramic (Optional) 360-046 360-047 430-001 360-086 * 32) 362-528 33) 362-528 34) 902-603 36 Description Nailing Strip - Top - Front Nailing Strip - Top - Side Standoff - Top Gasket - Relief Door Relief Door Assembly Brick Panel - Base - Front Brick Panel - Base - Side Brick Panel - Side Part # Description Part # Description 135) 360-069 Heat Shield - Side 181)
PARTS LIST PG131-1 (PIER) MAIN ASSEMBLY Part # 1) 2) Description Part # 360-528/P Door Assy Front - Tempered 360-946 Door Assy Front - Ceramic (Optional) 146) 360-035 Finishing Trim 181) * Extension Trim - Pier 149) 360-122 150) 360-123 151) 904-258 Magnet Bracket - Corner Magnet Bracket - Front Magnet 204) 360-940 206) 910-172 224) 360-942 Dec. Grill Front - Black (set) Fan Axial 240V Dec.
PARTS LIST PG121RC-1 (RIGHT CORNER) MAIN ASSEMBLY Part # 1) 2) Description 360-528/P Door Assy Front - Tempered 360-946 Door Assy Front - Ceramic (Optional) 360-529/P Door Assy Side - Tempered 360-948 Door Assy Side - Ceramic (Optional) 9) 360-046 10) 360-047 11) 430-001 780-013 17) 360-086 24) * Nailing Strip - Top - Front Nailing Strip - Top - Side Standoff - Top Standoff - Rear Gasket - Relief Door Relief Door Assembly 32) 33) 34) 35) Brick Panel - Base - Side Brick Panel - Base - Front Brick Pane
PARTS LIST PG121LC-1 (LEFT CORNER) MAIN ASSEMBLY Part # 1) 2) Description 360-528/P Door Assy Front - Tempered 360-946 Door Assy Front - Ceramic (Optional) 360-529/P Door Assy Side - Tempered 360-948 Door Assy Side - Ceramic (Optional) 9) 360-046 10) 360-047 11) 430-001 Nailing Strip - Top - Front Nailing Strip - Top - Side Standoff - Top 17) 360-086 24) * Gasket - Relief Door Relief Door Assembly 32) 33) 34) 35) Brick Panel - Base - Side Brick Panel - Base - Front Brick Panel - Side Brick Panel -
PARTS LIST BURNER ASSEMBLY & LOG SET Part # 360-930 Description 41) 42) 43) 44) Log Set Front Right Log Front Left Log Middle Left Log Middle Right Log 360-578/P 360-580/P 56) 910-080 910-081 Valve Assembly -NG Valve Assembly - LP Valve SIT - NG Valve SIT - LP 57) 360-090 58) * Gasket - Valve Tray Valve Tray 66) 910-936 910-937 Pilot Assembly - NG Pilot Assembly - LPG 67) * 68) W840470 Pilot Holder Pilot Assembly Gasket 79) 360-525 82) 360-027 904-690 936-170 Burner Assembly Grate Assembly Orif
NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ______________________________________
NOTES ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ___________________________________________________ ______________________________________
WARRANTY Regency Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our door. Regency Industries Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a Regency Product.