Regency Bellavista™ B41XT Gas Fireplace Owners & Installation Manual MODELS: B41XT-NG1 B41XT-LP1 www.regency-fire.com WARNING: FOR YOUR SAFETY If the information in these instructions are not followed exactly, What to do if you smell gas: Do not try to light any appliance a fire or explosion may result causing property damage, Do not touch any electrical switch: personal injury or loss of life. do not use any phone in your FOR YOUR SAFETY building.
To the New Owner: Congratulations! You are the owner of a state-of-the-art Gas Fireplace by REGENCY®. The Bellavista™ B41XT has been designed to provide you with all the warmth and charm of a wood fireplace at the flick of a switch. The Bellavista™ B41XT has been approved by Warnock Hersey/ Intertek for both safety and efficiency. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow.
MANUFACTURED MOBILE HOME REQUIREMENTS INFORMATION FOR MOBILE/MANUFACTURED HOMES AFTER FIRST SALE This Regency® product has been tested and listed by Warnock Hersey as a Direct Vent Wall Furnace to the following standards: VENTED GAS FIREPLACE HEATERS ANSI Z21.88-2009 / CSA 2.33-2009 and GAS-FIRED APPLIANCES FOR USE AT HIGH ALTITUDES CAN / CGA 2.17-M91.
TABLE OF CONTENTS SAFETY LABEL Copy of Safety Decal .....................................................5 REQUIREMENTS MA Code - CO Detector.................................................6 DIMENSIONS (Unit Dimensions ...........................................................7 INSTALLATION Important Message ......................................................8 Before You Start ............................................................8 General Safety Information....................................
SAFETY LABEL This is a copy of the label that accompanies each Bellavista™ B41XT Direct Vent Gas Fireplace. We have printed a copy of the contents here for your review. NOTE: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one. Duplicate S/N Listed: VENTED GAS FIREPLACE HEATER Certified for/Certifiée pour: CANADA and U.S.A. Tested to: CAN/CGA-2.17-M91, ANSI Z21.88-2009/CSA 2.
REQUIREMENTS MA Code - CO Detector (for the State of Massachusetts only) 5.08: Modifications to NFPA-54, Chapter 10 (2) Revise 10.8.
DIMENSIONS UNIT DIMENSIONS 23-1/4” (591mm) 13-3/16” (335mm) 36-3/8” (924mm) 28-1/2” (724mm) 22-5/16” (567mm) 19-7/16” (494mm) 38-3/16” (970mm) 38-1/2” (978mm) 46-11/16” (1186mm) 41-11/16” (1059mm) 41-5/8” (1057mm) 38-7/8” (987mm) 49-3/16” (1249mm) 24” (610mm) 35” (889mm) 36-11/16” (932mm) 43” (1092mm) 1” (25mm) Regency Bellavista™ B41XT Gas Fireplace 7
INSTALLATION IMPORTANT MESSAGE SAVE THESE INSTRUCTIONS The B41XT Gas Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with manufacturers instructions and all applicable codes.
INSTALLATION INSTALLATION CHECKLIST 1) Locate appliance a) Room location (Refer to "Locating Your Gas fireplace" section) b) Clearances to Combustibles (Refer to "Clearances" section) c) Mantle Clearances (Refer to "Combustible Mantel Clearances" section) d) Framing & Finishing Requirements (Refer to "Framing & Finishing" section) e) Venting Requirements (Refer to "Venting" section) This includes: 1) Clocking the appliance to ensure the correct firing rate (rate noted on label), after burning appliance for
INSTALLATION CLEARANCES The clearances listed below are Minimum distances unless otherwise stated: A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions. WARNING Fire hazard is an extreme risk if these clearances (air space) to combustible materials are not adhered to.
INSTALLATION MANTEL CLEARANCES Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the diagram on the right. Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible board. Note: Ensure the paint that is used on the mantel and the facing is "heat resistant" or the paint may discolour.
INSTALLATION MANTEL LEG CLEARANCES 3" Mantel leg 1-1/2" Mantel leg 9” Side Wall (Measured from side of Fireplace Opening) 4” 7” Allowable mantel leg projection. NON-COMBUSTIBLE REQUIREMENTS Min. 13-1/2" (343mm) 48-3/4" (1238mm) Non-combustible Non-combustible Header (steel stud) on edge 41-3/4" (1060mm) Non-combustible 36-3/4" (933mm) Non-combustible 50-1/4" Non-combustible (1276mm) Non-combustible Material 47-1/4" (1200mm) Framing Min. 3-1/2” (89mm) 12 Min.
INSTALLATION FRAMING Framing Dimensions Description B41XT M Framing Width 47-1/4"(1200mm) N Framing Height 49-1/2" (1257mm) O (Rear Vent) Framing Depth - Rear Vent 23-1/4" (591mm) O (Top Vent) Framing Depth - Top Vent 22-5/8" (575mm) P Corner Facing Wall Width 60-1/4" (1530mm) Q Corner Facing Wall Width 85-3/16" (2163mm) R (Rear Vent) Framed Chase Ceiling - Rear 49-1/2" (1257mm) R (Top Vent) Framed Chase Ceiling - Top 54-1/2" (1384mm) S (Rear Vent) Vent Centerline Height - Rear
INSTALLATION FINISHING IMPORTANT FINISHING DETAIL NOTE: Important: Before placing unit into final position - it is important to know the total thickness / height of finished hearth (tile, carpet, etc.) The base of the fireplace should be level or higher than the finished hearth height. Finishing materials such as tile, river rock, etc, must not protrude beyond the front facing flanges the sides and top of the firebox opening.
INSTALLATION UNIT ASSEMBLY PRIOR TO INSTALLATION BEFORE YOU START The Top Facing Support, the Side Nailing Strips, the 2 Top Standoffs and the Flue Collar must be correctly positioned and attached before the fireplace is moved into position. TOP STANDOFF ASSEMBLY The top standoffs are shipped in a flat position and must be folded into shape and attached. 1) Remove the standoffs from the fireplace top. 2) Take each standoff and bend into the correct shape.
INSTALLATION CONVERSION TO TOP VENT Note: This conversion must be done prior to the unit being placed in position. The unit comes equipped as a rear vent unit. These instructions are to be used, only if the unit is going to be top vented.
INSTALLATION 7) From the outside top of the firebox - remove the intake cover plate by removing the 4 - 1/4" x 1/2 " screws. 10) From the inside of the firebox, place the exhaust assembly into position as shown in Diagram 1 and secure with 10 - 1/4" x 1/2" screws (Diagram 2). Ensure all screws are tight, but do not over tighten. All 10 screws must be used. Diagram 1 Before proceeding to Step 8, inspect condition of all gaskets. DO NOT install parts with damaged gaskets.
INSTALLATION VENTING INTRODUCTION The B41XT uses the "balanced flue" technology Co-Axial system. The inner liner vents products of combustion to the outside while the outer liner draws outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney. Note: These flue pipes must not be connected to any other appliance.
INSTALLATION EXTERIOR VENT TERMINATION REQUIREMENTS Minimum Clearance Requirements Canada1 USA2 A Clearance above grade, veranda, porch, deck, or balcony 12"(30cm) 12"(30cm) B Clearance to window or door that may be opened 12"(30cm) 9" (23cm) C Clearance to permanently closed window * * D Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61cm) from the center line of the terminal (check with the local code) 24"(60cm) 24"(60cm) E C
INSTALLATION 5" X 8" RIGID PIPE CROSS REFERENCE CHART ONLY Components from different Manufacturers may not be mixed. Not all Rigid Pipe components are available directly from FPI.
INSTALLATION Description Attic Insulation Shield 12” Simpson Selkirk Metal-Fab™ ICC Excel Direct Vent Pro® Direct Temp™ Sure Seal Direct 58DVA-IS N/A from FPI N/A N/A N/A Basic Horizontal Termination Kit (A) N/A 5DT-HKA N/A N/A Horizontal Termination Kit (B) 58DVA-KHA 5DT-HKB N/A N/A Vertical Termination Kit 58DVA-VHA 5DT-VKC N/A N/A High Wind Vertical Cap 58DVA-VCH N/A N/A TM-5VT High Wind Horizontal Cap N/A N/A N/A TM-5DHT Horizontal Square Termination Cap N/A 5DT-
INSTALLATION VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS FLEX VENT OR RIGID PIPE 5" X 8" The diagrams show all allowable combinations of vent runs with 5" x 8" venting using the Regency direct vent system or rigid vent system. A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes. For horizontal terminations the Regency Direct Vent Flex System may be used for installations upto a maximum continuous vent length of 10ft (3.0m).
INSTALLATION HORIZONTAL TERMINATIONS FLEX VENT 5" X 8" These venting systems, in combination with the B41XT Direct Vent Gas Fireplace, has been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram in "Exterior Vent Termination Locations" section.
INSTALLATION HORIZONTAL TERMINATIONS RIGID PIPE 5" X 8" Horizontal Termination A Top Vent - No Vertical Rise • When venting with a 90° elbow directly off the unit Flex vent or approved Rigid Vent System • Max. 3 ft. horizontal run B Rear Vent w/ Horizontal Termination • Max. 3ft.
INSTALLATION HORIZONTAL TERMINATIONS ASTROCAP XL & RIGID REAR VENT KIT FOR CORNER INSTALLATIONS RIGID PIPE 5" X 8" Designed for a minimum vent configuration when using a rear vent application with a horizontal termination in a corner installation.
INSTALLATION VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 90o (two 45o elbows equal one 90o elbow). • • • • Maintain clearances to combustibles as listed in "Clearances" section Horizontal vent must be supported every 3 feet. Firestops are required at each floor level and whenever passing through a wall. A wall thimble is mandatory for all horizontal terminations due to high temperatures.
INSTALLATION RIGID PIPE VENTING SYSTEMS BASIC HORIZONTAL & VERTICAL TERMINATIONS Rigid Pipe Vent Systems offer a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized finish.
INSTALLATION HORIZONTAL TERMINATIONS TWO (2) 90O ELBOWS (RIGID PIPE 5" X 8") H1 V H One 90o elbow = Two 45o elbows. Option V H + H1 A) 0' Min. 2' Max. B) 1' Min. 3' Max. C) 2' Min. 4' Max. D) 3' Min. 5' Max. E) 4' Min. 6' Max. F) 5' Min. 7' Max. 8' Max. G) 6' Min. 77777M No Vent Restrictor Installed With these options, maximum total pipe length is 30 feet with minimum of 6 feet total vertical and maximum 8 feet total horizontal. Please note minimum 1 foot between 90o elbows is required.
INSTALLATION VENTING ARRANGEMENTS FOR VERTICAL TERMINATIONS The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90o elbows, with Rigid Pipe Venting Systems for Propane and Natural Gas. Two 45o elbows equal to one 90o elbow. Maximum of four 45o elbows allowed. Horizontal (Feet) 0 2 4 6 8 10 12 40 38 36 Maximum: 35.5 ft. (10.
INSTALLATION VERTICAL TERMINATIONS THREE (3) 90O ELBOWS (RIGID PIPE 5" X 8") One 90o elbow = Two 45o elbows. Option A) B) C) D) E) F) G) H) V 0' Min. 1' Min. 2' Min. 3' Min. 4' Min. 5' Min. 6' Min. 7' Min. H + H1 2' Max. 2' Max. 3' Max. 4' Max. 5' Max. 6' Max. 7' Max. 8' Max. V + V1 2' Min. 3' Min. 4' Min. 6' Min. 7' Min. 8' Min. 9' Min. 10' Min. With these options, max. total pipe length is 30 feet with min. of 10 feet total vertical and max. 8 feet total horizontal. Please note min.
INSTALLATION 5" X 8" VENTING (Rigid Vent Systems) Minimum Vent Clearances to Combustibles * Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2" (38mm).
INSTALLATION Minimum Vent Clearances to Combustibles * Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2" (38mm). Horizontal Top 3" (76mm) Horizontal Side 2 " (51mm) Horizontal Bottom 2" (51mm) Vertical Vent 2" (51mm) Below are the recommended framing dimensions (inside measurements) for the 5" x 8" rigid vent terminations - for use with a firestop or wall thimble.
INSTALLATION UNIT INSTALLATION WITH VERTICAL TERMINATION 4) Assemble the desired lengths of pipe and elbows. Ensure that all pipes and elbow connections are in the fully twist-locked position and sealed. 5" X 8" VENTING (Rigid Vent Systems) Diagram 4 MUST USE RIGID PIPE ADAPTOR #770-994 * Clearances noted below must be maintained; except when passing through a wall, ceiling or at the termination where the use of a firestop or wall thimble reduces clearance to 1-1/2" (38mm).
INSTALLATION PILOT ADJUSTMENT Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner). Note: If you have an incorrect flame pattern, contact your FPI dealer for further instructions. B41XT -NG System Data Conversion Kit # For 0 to 4500 feet altitude Burner Inlet Orifice Sizes: #30 Max. Input Rating Min.
INSTALLATION BRICK PANEL INSTALLATION Must install one of the following: Brick Panels, Stainless Steel or Black Enamel Panels. Dangerous operating conditions may occur if the panels are not installed or if installed with broken panels. Handle with care. DO NOT FORCE INTO POSITION. 1) Unwrap the Brick Panels from the protective wrapping.
INSTALLATION OPTIONAL STAINLESS STEEL / BLACK ENAMEL PANEL INSTALLATION Before installation, panels must be handled and cleaned as per instructions noted below: Stainless Steel Panels Black Enamel Panels • Stainless panels must be inspected for scratches and dimples prior to installation. All claims to be recorded at this time. Claims for damage after installation will not receive consideration. • Black Enamel panels must be inspected for scratches and dimples prior to installation.
INSTALLATION 4) Remove 1 screw (see inset A), position right side panel in firebox position panel clip in place and secure with 1 screw (see inset B). Tighten the screw. 7) Carefully position and fit the top bracket in place by ensuring the tabs of the bracket fit into the baffle openings as shown below. Push downwards to secure the bracket to the top panel.
INSTALLATION LOG SET INSTALLATION Installation of Brick or Stainless Steel / Black Enamel Panels must be completed before installing the log set. Read the instructions below carefully and refer to the images. If the logs are broken do not use the unit until they are replaced. Broken logs can interfere with pilot operation. Improper positioning of the logs may create carbon build-up and can alter the unit's performance which is not covered under warranty.
INSTALLATION 5) Place Log I on the left side of the burner, directly in front of Log A. Position Log I so it fits into the pin on the burner as shown below. 8) Slide the left side of Log G back until it touches the tab on the burner shown below. Tab on Burner Back of Log G I 9) Place Log H on the right front side of the burner in front of log F. Position Log G so it fits into the pin on the burner as shown below.
INSTALLATION 11) Position Log E on top of Log G - fit Log E into the pin on Log G as shown below. B E E G 14) Position Log C on top of Log H. Log C fits into the pin in Log H. as shown below. 12) With Log E in position on Log G - ensure that Log E touches the back corner of Log A as shown below. C A E 15) With Log C in position on Log H - assure that Log C contacts the back corner of Log A as shown below. 13) Position Log B on top of Log A. Log B fits into the pin in Log A.
INSTALLATION 16) Place the lava rocks on the burner in front of the logs as shown below. Be careful not to overlap the lava rock and ensure the burner ports are left exposed in front of Logs E and H as shown below. 17) Separate platinum embers and place on the front burner on and around the lava rocks. Avoid stacking platinum embers. Platinum embers may be placed over burner ports. Platinum Embers IMPORTANT: Do not cover burner ports with lava rocks as this will change the flame pattern.
INSTALLATION Optional WALL THERMOSTAT A wall thermostat may be installed if desired, connect the wires as per the wiring diagram. Use table below to determine the maximum wire length. Note: Preferable if the thermostat is installed on an interior wall. Regency ® offers an optional programmable thermostat but any 250-750 millivolt rated nonanticipator type thermostat that is CSA, ULC or UL approved may be used. Recommended Maximum Lead Length (Two-Wire) When Using Wall Thermostat (CP-2 System) Max.
INSTALLATION OPTIONAL FAN INSTALLATION Important: 120 Volt AC power is needed for the fan switch and blower. The receptacle box will be installed on the left hand side of the unit and must be wired by a qualified electrician prior to fan assembly being installed. The neutral(wider) slot of the polarized receptacle should be at the top. 6) Position the fan base with the motor end towards the rear of the firebox and then slide the fan in towards the rear of the unit.
INSTALLATION 9) Slide the thermodisc/cover assembly onto the bracket clip on the left underside of the firebox. Ensure that no wires will touch hot surfaces. 10) Slide the the Fan control box under the clip on the floor of the firebox. Slightly open clip with flat head screw driver if necessary. Caution: If clip is opened too wide it will not hold the Fanspeed Control Box.
INSTALLATION AERATION ADJUSTMENT The burner aeration is factory set but may need adjusting due to either the local gas supply or altitude. Open the air shutter for a blue flame or close for a more yellow flame. Minimum Air Shutter Opening: NG 1/4" LP 1/2" CAUTION: Carbon will be produced if air shutter is tightly closed. Note: Any damage due to carboning resulting from improperly setting the aeration controls is NOT covered under warranty. Air shutter rod: located to the left of the valve assembly.
INSTALLATION #8 Ground Lug (for mobile home) Electrode Thermocouple Star washer Thermopile Nut Gas Pilot WIRING DIAGRAM FOR NG AND LP UNITS Optional Fan Fan Ground Neutral 120V AC 60 Hz Live Ground ON Green OFF Black Pilot Assembly Lockwasher Ground (To THTP) DC Spark Box L Brown White O OFF I ON To Thermocouple IN PILO T (To TH) H White Black Red Minimum Convection Air Temp. Switch Rotary Speed Control Fan ground wire Burner ON OFF Red Gas In "S.I.
INSTALLATION 584 Proflame GT Series Feature Sheet 1 1 1 (X) Indicates Included Feature Note 1 ~ Proflame Flame Modulator for GTM & GTMF Remote Controls are sold seperately. Choice of NG or LP flame modulator (to match unit fuel type). See Regency Retail Price pages for complete details Note: Regency Proflame systems include a white and black wall cover & switch.
INSTALLATION OPTIONAL ACCENT LIGHT INSTALLATION B41XT Accent Light Assembly Kit 1 910-814 Plug wiring + gasket 2 910-997 Halogen Bulb 2 940-363 Amber Glass 1 Light Assembly Includes gaskets (x 2) 1 918-864 Instruction Sheet Important: 120 Volt AC power is required for the optional light. The receptacle box will be installed on the lower left corner of the unit and will need to be wired by a qualified electrician prior to the optional light installation.
INSTALLATION 13) Install each light assembly from the underside of the floor of the firebox. Secure with 2 screws as shown below. 15) Install two light diffusers on to the base tray. 16) Secure diffusers onto base tray from the backside of the tray with 2 screws. 17) Reinstall base tray with light diffusers - use caution when installing do not damage the bulb. NOTE: The ground wire will need to be pulled back out of the protective casing to be able to reach the ground lug.
INSTALLATION FLUSH GLASS DOOR INSTALLATION The standard flush door comes with a black frame. To install the frame, simply hook the top door flange onto the top of the unit and swing the door towards the unit, see Diagram 1. Be careful that the glass gasket does not roll up; there must be a gap between the gasket and the door lip to ensure that the door sits securely on the unit, see Diagram 2.
INSTALLATION LOUVERS / FLUSH PANEL INSTALLATION 1. To install the lower louver or flush panel - line up the 2 hinges with the brackets in the unit as shown below. 4. Fasten the hinges to the louver / flush panel with 3 screws each as shown below. 5. Flip up the louver / flush panel to close. 2. Attach the each hinge to the corresponding bracket with 2 screws as shown below. 6.
INSTALLATION FULL SCREEN ARCH DOOR AND FRAME INSTALLATION 1) Remove glass door (refer to glass door removal in the manual). 2) Install 4 Phillips screws (supplied with packaging) to the inside walls of the unit (see Diagram 1 for locations). 4) Slide bracket into slot on the back of the full screen door frame. See diagram 3. 5) Lift screen doors off of door frame to reduce the weight during installation. Do not tighten the screws - leave them loose for the next step.
INSTALLATION 7) Secure the bracket installed in Step 4 - to the inside of the firebox in the same location and with the same screws from Step 3 . 8) Reinstall the glass door. 11) Flip the hinges down to 90° - line up the lower mesh screen door as shown below. 12) Fasten the hinges to the lower screen mesh panel with 3 screws each as shown below. 9) To install the lower screen mesh panel - line up the 2 hinges with the brackets in the unit as shown below.
INSTALLATION 14) To install the top panel - line up the 2 tabs on the panel with the corresponding bracket clip on the inside top of the unit and slide into place (see below). 16) Re-hang the screen doors. Location of bracket clips in unit. 15) The full screen doors are stabilized by 2 magnets which are attached to a bracket. Install the bracket to the flange at the base of the unit using 2 screws. There are 2 hole locations on the bracket to accommodate flush wall & thicker finishing materials.
OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS 1) Read and understand these instructions before operating this appliance. 2) Check to see that all wiring is correct and enclosed to prevent possible shock. 3) Check to ensure there are no gas leaks. 4) Make sure the glass in the glass door frame is properly positioned. Never operate the appliance with the glass removed. 5) Verify that the venting and cap are unobstructed.
OPERATING INSTRUCTIONS COPY OF LIGHTING PLATE INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTING This appliance must be installed in accordance with local codes, if any; if none, follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or Natural Gas and Propane Installation Codes, CSA B149.1. (Australia: AS5601-2004, New Zealand: NZS 5261) WARNING: If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
MAINTENANCE MAINTENANCE INSTRUCTIONS 1) Always turn off the gas valve before cleaning. For relighting, refer to lighting instructions. Keep the burner and control compartment clean by brushing and vacuuming at least once a year. When cleaning the logs, use a soft clean paint brush as the logs are fragile and easily damaged. 2) Clean appliance and door with a damp cloth (never when unit is hot). Never use an abrasive cleaner. The glass should be cleaned with a gas fireplace glass cleaner.
MAINTENANCE ACCENT LIGHT BULB REPLACEMENT 1) Shut off electrical supply. 2) Remove Full Screen Door and bottom Louver if installed. 9) Remove the 2 screws securing the base tray - lift base tray up and out. Diagram 4a and 4b. 3) Remove the glass door - see instructions in manual. 4) Remove the logs, lava rock and vermiculite if installed. 5) Remove the brick or inner panels if installed - see instructions in manual. Diagram 4a 6) Remove the burner and rear log tray - see below.
MAINTENANCE VALVE REPLACEMENT 8) Remove the 2 screws securing the burner tray - lift base tray up and out. Diagram 4a and 4b. 1) Shut off the gas and electrical supply. 2) Remove the louvers 3) Open the flush door and remove the door. 4) Remove the logs. Diagram 4a 5) Remove the burner/grate assembly by removing the 2 screws. Diagram 8 Diagram 4b INSTALLING VALVE 9) Disconnect the inlet gas line. See Diagram 5. 1) Place new valve tray and gasket into position. 2) Reinstall the 14 hold down screws.
PARTS LIST PARTS LIST MAIN ASSEMBLY Part # 1) 506-086 2) 506-074 3) 506-513 4) 506-000 5) 556-095 6) * 7) 596-042F 8) 476-023 Top Insulation Plate Top Insulation Flue Collar Outer Assembly Exhaust Gasket Flue Collar Gasket Flue Collar Inner Assembly Top Relief Plate Relief Gasket - Door Top 10) 820-389 11) 910-073 Thermodisc Bracket Spark Generator Battery Holder 12) 948-259 13) 948-025 Spring Handle Lever Spring Door Extension 14) 940-362/P 15) 506-083 Ceramic Glass Door Frame 16) 17) Outerbox A
ST PARTS LIST BURNER ASSEMBLY Part # Description 1) 506-070 Rear Log Tray 4) 506-525 506-531 B41XT Burner Assembly NG B41XT Grate Assembly 6) 910-568 Valve NG/LP SIT High/Low 820 7) 8) 9) 10) 506-072 506-071 506-055 506-075 Valve Shield Valve Mounting Valve Tray Plate Air Deflector 11) 380-013 12) 910-038 910-039 910-386 910-341 Part # Description 904-660 904-431 Orifice #30 NG Orifice #49 LP 506-574/P 506-576/P Valve Assembly - NG Valve Assembly - LP 506-003 Valve Assembly Gasket 15
PARTS LIST ACCESSORIES Part # Description 1) 506-946 3-Sided Finishing Trim 2) 507-920 507-924 507-926 Louvers Set - Black Louvers Set - Gold / Black Louvers Set - Steel / Black 3) 506-916 Black Flush Panels - Set 4) 506-901 506-902 506-905 Brick Panels - Standard Brown Brick Panels - Standard Red Brick Panels - Standard Cinder Gray 5) 506-907 506-908 Inner Panels - Brushed Stainless Steel Inner Panels - Black Enamel 6) 507-940 507-942 507-944 Full Screen Doors - Black Full Screen Doors -
WARRANTY Regency® Fireplace Products are designed with reliability and simplicity in mind. In addition, our internal Quality Assurance Team carefully inspects each unit thoroughly before it leaves our facility. FPI Fireplace Products International Ltd. is pleased to extend this limited lifetime warranty to the original purchaser of a Regency® Product. This warranty is not transferable.
Register your Regency® warranty online www.regency-fire.com Reasons to register your product online today! • View and modify a list of all your registered products. • Request automatic email notification of new product updates. • Stay informed about the current promotions, events, and special offers on related products.