PLM Reader Model R22-1012 with P10-xx10 PlugSert option Installation Instructions RadarFind™ Corporation 877-RadarFind (723-2734) www.radarfind.
Radarfind Corporation PLM Reader Installation Instructions 12/5/2008 Page 2 of 10 DANGER: Cautions: • Risk of electric shock. Disconnect all supplies before working on any circuit. • It is important to follow all instructions shipped with this product. Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death to you or others. • Risk of malfunction. Use only copper wires of size 12AWG (or larger) suitable for 105°C (221°F).
12/5/2008 Radarfind Corporation PLM Reader Installation Instructions Page 3 of 10 General Safety Information • • • • Wear safety goggles when working under conditions that might be hazardous to your eyes. Keep tools where you and others will not fall over them. Keep the installation area clear during the installation. Do not wear loose clothing that could become caught in the equipment.
Radarfind Corporation PLM Reader Installation Instructions 12/5/2008 Page 4 of 10 Preparing for Installation Note: Read all instructions before installing or operating this equipment. Site Selection Criteria The selection of the mounting location for the reader and the method of connecting it into the existing electrical system must be accomplished under the direction of the facilities engineer and the safety engineer responsible for the proposed building or location.
Radarfind Corporation PLM Reader Installation Instructions 12/5/2008 Page 5 of 10 Installing a RadarFind Plug-in Reader Warning: ALWAYS confirm that Location ID label on top of Reader matches Location ID on map for where Reader will be installed. If it is necessary to install a Reader in any other location for any reason RadarFind must be notified immediately. Note: A RadarFind Reader can only be installed with the ground pin orientation the same as the existing receptacle.
12/5/2008 Radarfind Corporation PLM Reader Installation Instructions Page 6 of 10 Hard wiring a Reader In places where the Reader must be installed off-axis to the receptacle or over a quad box the Reader Plug-Sert must be removed and the Reader must be wired directly into the receptacle box. Removing the Plug-Sert from Reader 1. Remove Reader back plate 2. Remove Reader cover plate 3. Loosen Plug-Sert wire tap screws, from the bottom front of the Reader behind the receptacle 4.
12/5/2008 Radarfind Corporation PLM Reader Installation Instructions Page 7 of 10 Hard wired Reader Installation Procedure 1. Turn off the power to the outlet. 2. Remove the existing receptacle cover plate and mounting screw, set aside screws for use later. 3. Unscrew receptacle, save screws for later use, and pull receptacle out of box. NOTE: If Reader orientation is off axis to the existing receptacle or if the existing receptacle is an quad see Reader mounting adapter plate 80-000-1019 adapter plate.
12/5/2008 Radarfind Corporation PLM Reader Installation Instructions Page 8 of 10 8. Wire Reader into circuit with Reader leads protruding from rear of Reader. 9. Pass receptacle through reader cavity and tip Reader onto the protruding box screws (RED) by sliding slotted end of metal mounting frame onto bottom screw, tipping the Reader to left and turning clock-wise onto top screw. IMPORTANT ! Use caution to assure that no wires are caught under metal Reader frame. 10.
12/5/2008 Radarfind Corporation PLM Reader Installation Instructions Page 9 of 10 Accessories Reader mounting adapter plate – 80-000-1019 In some cases other objects near a receptacle, such as railings or cabinets, will prevent the Reader from being installed in its default position or orientation. RadarFind Readers may be hard wired at a 90 degree angle over single gang wall receptacles or in any orientation over quad receptacles with the accessory adapter plate.
12/5/2008 Radarfind Corporation PLM Reader Installation Instructions Page 10 of 10 Tamper-resistant mounting accessories RadarFind R11-1411 Readers are packaged with standard 6/32 combination head screws for the center plate retention screw and the four corner anchor screws. Tamper resistant screws and matching drivers are available as accessories.
Radarfind Corporation PLM Reader Installation Instructions 12/5/2008 Page 11 of 10 Technical Specifications: Part # - R22-1012 AC supply: Power: 108-130 VAC RMS, single phase 60HZ 1.2 VA Double Insulated Communications: RF frequency range: Transmit power: Antenna: Operating: Dimensions: FHSS FCC Subpart 15.249 and 15.247 FSK channel between 902 and 928 MHz +8dBm maximum 6 dB gain cardioid 0 to 40º C, 5% to 90% RH, non condensing 5” W x 12.3” L x 2.