October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions V2 Collector and Remote Radio Models C22-2812 & M22-0110 Installation Instructions Radarfind™ Corporation 877-Radarfind (723-2734) www.radarfind.com Copyright RadarFind Corp.
Radarfind Corporation V2 Collector and Remote Radio Installation Instructions October 2008 DANGER: • Risk of electric shock. Disconnect all supplies before working on any circuit. • It is important to follow all instructions shipped with this product. Failure to follow all safety precautions and instructions may result in property damage, serious injury, or death to you or others. • Electric installation should conform to national, state, and local electrical codes.
October 2008 Caution: Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 3 If the equipment is damaged, do not attempt to install or operate it. 1. When the equipment arrives, unpack the unit(s). 2. Check for damage that may have occurred in transit. 3. If contents are damages contact the carrier immediately to file a claim stating the extent of the damage.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 4 Remote Radio wiring and Installation RadarFind Remote Radios are connected to their Collectors with standard Ethernet Cat5e cabling. The power and signaling used on the cables between the Collectors and the Remote Radios is not Ethernet, although the wiring and connector pattern is the same.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 5 Mounting Remote Radios below the ceiling grid. Mount the Remote Radio under the ceiling tile grid using the clips provided on the back of the case. Dress wire neatly, and position one antenna horizontally – facing across the hall - and the other vertically – facing down. Fig 2 – Standard mounting for Remote Radio Note: Any Remote Radio may be used at any location.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 6 Collector Installation Preparing for Collector Installation Site Selection Criteria The selection of the mounting location for the Collector and routing of wiring must be accomplished under the direction of the facilities engineer and the safety engineer responsible for the proposed building or location. The Collector installation location must be indoors and protected from all weather and water.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 7 Typical Collector Installation Each RadarFind Collector is labeled and the accompanying installation documentation designates where each specific Collector is to be placed. Note: Collectors MUST be placed in the designated locations according to the installation documentation and plugged into the correct Ethernet and Remote Radio connections.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 8 Installation Procedure Hold Collector level against wall in desired location and mark the right-most slot of all four mounting holes. Figure 6: Marking locations for Collector mounting screws Set Collector aside and insert four mounting screws into marked holes with about ¼” inch exposed. Figure 7: Collector on mounting screws after tightening.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 9 Figure 8: Remote Radio connector block. Remote Radio punch-down or termination blocks panels will be marked with the ID of each Remote Radio for the Collector. The Remote Radio ID # ends in A,B,C, or D, which corresponds with the jack ID on the Collector. Each Collector may have 2, 3, or 4 Remote Radios.
October 2008 Radarfind Corporation V2 Collector and Remote Radio Installation Instructions Page 10 Figure 9: Remote Radio jumpers marked and connected to connector block. Clearly mark and connect an Ethernet jumper from the Collector to the correct P.O.E. enabled port on the Ethernet switch. If no P.O.E. port is available an injector may be used, or an external power supply is available from RadarFind. Figure 10: Collector Ethernet jumper clearly marked at switch end. Copyright RadarFind Corp.
Radarfind Corporation V2 Collector and Remote Radio Installation Instructions October 2008 Checking the Installed Unit After installation, check the unit to ensure that it is operating properly. 1. Turn on power. 2. Verify that the LED’s on the Collector run through the power-up sequence correctly. Technical Specifications: RadarFind Collector C22-2812 Power Supply: Power: Communications: Operating: Dimensions: IEEE P802.3af PoE or 48VDC (from optional RadarFind wall adapter) 8W maximum IEEE 802.