Heating Panels The QuietWarmth System is available in three standard widths, and two standard voltages. The following table shows the maximum number of single panels that a thermostat can control for each width and voltage.
Additional Components NAME PART # DESCRIPTION Thermostat/Control --- UL Listed thermostat or other appropriate control rated for at least 25% greater capacity than the installed heating load. Thermostat w/Floor Sensor is recommended. Thermal Insulation --- The insulation must be of the non-flammable type specified during calculations done per Part 1. See for details. Dielectric Tape --- UL listed and/or CSA certified “electrical” tape rated for at least 90°C / 194°F.
Hole drilled for Temp Sensor Floor Subfloor Temp Sensor Insulation (min. 3/4") Floor Subfloor Temp Sensor Insulation (min.
section 4. Inspection/Testing/Completion Visual Inspection When visually checking the panels, look for any signs of damage, wear or scratching that might have occurred during installation. If any portions of a panel set appear damaged, replace the entire panel set. Electrical Test A resistance check across the supply leads using an accurate ohm meter must be made to detect defects to the system — record the resistance readings.
16” On Center Width 240V No of Panel(s) Wattage Current (Amp) High Resistance Limit (ohms) Low Resistance Limit (ohms) 1 10 0.042 6336.00 5472.00 2 20 0.083 3168.00 2736.00 3 30 0.125 2112.00 1824.00 4 40 0.167 1584.00 1368.00 5 50 0.208 1267.20 1094.40 6 60 0.250 1056.00 912.00 7 70 0.292 905.14 781.71 8 80 0.333 792.00 684.00 9 90 0.375 704.00 608.00 10 100 0.417 633.60 547.20 11 110 0.458 575.99 497.45 12 120 0.500 528 456 13 130 0.
SKETCH GRID