Use and Care Manual

Environmental Products
QUIET-ONE
Models:
I
NSTALLATION
O
PERATING
M
AINTENANCE
2000
Kickspace Heater
Series
KS2004, KS2006
KS2008, KS2010
Please read these instructions thoroughly before beginning your
installation!
Smith’s Quiet-One 2000 Series kickspace heaters are designed for installation in a forced hot water ( hydronic) heating system. They may
also be used with conventional gas, oil, electric, or solar powered water heaters.
IMPORTANT: BEFORE INSTALLING ANY HEATING TERMINAL UNIT TO A DOMESTIC
WATER
HEATER, CONSULT THE LOCAL PLUMBING
CODES.
When installing a kickspace heater, an accurate heat loss calculation of the space is required. Match unit selection with BTUH output at
system water temperature and flow rate. See the capacity chart below for output at various water temperatures and flow rates.

Flow
Rate
Pressure Entering Water Temperature (in degrees F) - BTU/hrs.
Unit GPM Drop (ft) 130 140 150 160 170 180 190 200 210
KS2004
1 0.06 2095 2410 2700 3000 3350 3650 3860 4000 4105
3 0.422 2240 2650 3000 3350 3765 4350 4350 4530 4635
5 1.026 2350 2755 3140 3530 3940 4590 4590 4810 4935
KS2006
1 0.12 3410 4050 4655 5265 5860 6700 6700 7110 7270
3 1.19 3735 4395 5060 5735 6330 7120 7120 7530 7790
5 2.6 3860 4540 5225 5910 6560 7415 7415 7800 8010
KS2008
1 0.12 4300 5000 5765 6500 7370 8400 8400 8735 8920
3 1.19 4580 5380 6195 7050 7930 9010 9010 9445 9740
5 2.6 4760 5625 6450 7290 8200 9360 9360 9785 10020
KS2010
1 0.41 5530 6350 7150 7975 8780 9975 9975 10330 10520
3 2.78 5880 6710 7740 8710 9625 11060 11060 11530 11740
5 3.92 6070 7030 8000 9030 10025 11525 11525 11995 12180
All capacities are rated by RTS with the kickspace installed und er a cabinet and all capacities include the heat effect factor.
For low speed ratings use: .85 for the KS2004, .75 for the KS2006, .70 for the KS2008 and .65 for the KS2010.
Heat throw: KS2004 = 10 @ 50 CFM; KS2006 = 10@ 75 CFM; KS2008 = 10’ at 90 CFM; KS2010 = 10’ @ 125 CFM.
NOTE: All kickspace heaters include a low limit aquastat which shuts off power to the fan when water temperature falls to 90
o
F. Power
is restored when water temperature rises to 110
o
F.
UNIT INSPECTION
Before starting the installation, carefully remove the kickspace heater from its box. Inspect for any damage caused in handling. The box
should include:
(1) Kickspace unit
(2) Molded grille endcaps (KS2004 only)
(2) Mounting screws
(2) Screw covers
LOCATING THE KICKSPACE HEATER
Quiet-One 2000 Series kickspace units are designed for installation under kitchen cabinets, bathroom vanities, built - in shelves or benches,
and stairways. An available recessed wall mounting kit enables vertical installation with a flush mounted grille. Consideration should be
given in regards to perishable goods stored in the cabinet above the unit.

Summary of content (5 pages)