Hi-MitⅡAdapter Model: HCCS-H64H2C1M EN INSTALLATION & USER MANUAL
CONTENTS Safety Precautions......................................................... 1 Product Description 2.1 Main features.................................................................... 2 2.2 Description of parts........................................................... 3 2.3 General data..................................................................... 3 Installation 3.1 Components list................................................................ 4 3.2 On-site preparations...................
1. Safety Precautions Please read this chapter thoroughly before installation. The following signal words indicate important information on safety, please observe. WARNING Hazards or unsafe practices that may result in severe injuries or damages. CAUTION Hazards or unsafe practices that may result in minor injuries or damages. WARNING CAUTION Please entrust installation to the dealer or the professionals. DO NOT install by yourself. Improper installation may lead to electric shock or a fire.
2. Product Description 2.1 Main features Hi-MitⅡadapter (hereafter referred to as adapter) should be used in conjunction with APP, with main features as below: 1) One adapter connects at most 64 indoor units, 64 outdoor units, and 64 electric meters. 2) One APP account creates at most 8 groups, and each group connects with at most 4 adapters. 3) Adapter supports both wired and wireless routers. Only one type should be selected for use.
2.2 Description of parts 1. Power status LED: red lights up when power on. POWER 2. H-NET commu. LED: yellow flashes when communicating. H-NET 3. WLAN status LED: blue lights up when connecting into network successfully. WLAN 4. System status LED: green flashes at every 1s. SYS Reset 5 Top cover (1) WiFi Reconfiguration: Insert and press the reset button for over 3s (no more than 10s). Meanwhile, the WLAN status LED flashes. The WiFi module is restored to factory settings.
3. Installation 3.1 Components list When unpacking, please check if all the following items are complete and intact. Item Adapter Installation Manual Power Adapter Accessory Pouch 1 1 1 Figure Quantity NOTE 1 The device is provided along with four AC plugs complying with British standard, European standard, American standard, Australian standard, as well as two bolts and two expansion plugs. 3.2 On-site preparations Following items should be ready before installation.
3.5 Electrical wiring 1) Remove the case: unit:mm b. take off the case in the direction of the arrow. a. remove rubber plug and screws. 2) Connect electric wires according to the diagram below. ON OFF 1 2 3 4 Address DIP switch Electric meter RS485 H-NET POWER B A 1 2 GND +12V 485 commu. cable (polarity) 1 2 1 2 1 2 Outdoor unit HCCS-H64H2C1M Internet cable H-NET commu.
4. Configuration 4.1 DIP switch setting When multiple adapters (max.3) are connected to one H-NET communication cable, DSW1 has to be set. 0xA0 0xA2 0xA1 0xA3 0xA4 0xA5 0xA7 0xA6 DSW1 ON ON OFF Note: 1 2 3 4 OFF 1 2 3 4 OFF 1 2 3 4 indicates the location of DIP switch. OFF ON ON ON ON 1 2 3 4 OFF 1 2 3 4 OFF ON ON OFF 1 2 3 4 OFF 1 2 3 4 1 2 3 4 indicates no attention needed. 4.
Declaration of Conformity EN Hereby, Hisense Hitachi declares that the radio equipment Hi-Mit II Adapter is in compliance with Directive 2014/53/EU. The full text of the EU declaration of conformity is available at the following website: http://www.hisense-vrf.com Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd. No.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Caution: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
1147090 Qingdao Hisense Hitachi Air-conditioning Systems Co., Ltd. Add: No. 218, Qianwangang Road, Economic and Technological Development Zone, Qingdao, China http://www.hisense-vrf.com E-mail: export@hisensehitachi.com The Company is committed to continuous product improvement. We reserve the right, therefore, to alter the product information at any time and without prior announcement. M00708Q Feb.