DC/DC 5A module of converter switching
DC/DC50HV v.1.0/I
DC/DC 5A HV Step down DC/DC converter with adjustable output voltage.
L
W
H
DESCRIPTION
5 5 HV
2 60 12 24 VADJ
The step down converter DC/DC A (DC/DC 0 ) is used for step down the input voltage from the range
between 8V÷ V DC to the voltage range of V DC at the output, adjusted with the potentiometer.
The maximum load current is Imax=5A (Pmax=60W). The module does not feature galvanic isolation between
input/output (IN-AUX) and operates on common "ground" (0V) potential (IN- and AUX- terminals are galvanically
connected = common terminal).
Pulsar
®
The module’s features:
· Step down DC/DC converter with adjustable output voltage
· Example of use: step down from 48V to 12V DC
· The input voltage range: 28÷60V DC
· The output voltage range: 12÷24V DC
· The maximum load current 5A (60W)
· The PSU technical output indicating converter failure
triggered by:
· Short-circuit of the output
· Output overload
· Protections:
· Short-circuit protection SCP
· Overload protection OLP
· High efficiency: 92%
· Optical LED indication
· Warranty – 2 years from the production date
· Mounting:
· Mounting strip with adhesive tape
· Mounting screws
Input voltage (power supply)
28V÷60V DC
The output voltage range
12V÷15V, 15V÷24V
Jumper adjustable.
Factory setting: 12V.
P module power
60W max.
Energy efficiency
85%÷ 92%
Ripple voltage
80mV p-p max.
Output current
5A max.
Current consumption by module systems
20 mA max.
Short-circuit protection SCP
electronic, automatic recovery
Overload protection OLP
110-150% of the module’s power, manual restart (the failure
requires disconnection of the DC output circuit)
Technical outputs
- PSU output indicating failure – overload or short-
circuit in the AUX output
- OC type, 50mA max. Failure status: hi-Z state (high
impedance), normal status: L level (0V)
Optical indication
- IN LED indicating DC power status
- AUX LED indicating DC supply status at the output
- PSU LED indicating failure - overload or short-
circuit in the AUX output
- red, normal status: is lit continuously
- green, normal status: is lit continuously
- red, normal status: does not lit, failure: is lit continuously
Operating conditions
II environmental class, -10°C ÷40°C, ensure air flow around
the unit for convection cooling
Dimensions
140 x 43 x 45 (L x W x H)
Net/gross weight
0,15/0,20 kg
Mounting
mounting tape or mounting screw x 2
Declarations, warranty
CE, 2 years from the production date

Summary of content (1 pages)