1. Description.
The LB5/5x0,5A/2,5/AW fuse module is designed for power distribution in low-voltage systems requiring voltage of 10V÷30V
DC or 10V÷24V AC (e.g. buffer power supply, transformer etc.). It is fitted with the IN input for power supply and 5 independently
protected AUX1÷AUX5 power supply outputs. Each AUX output is equipped with short circuit protection (SCP): melting fuse F 0.5A or
PTC 0.5A polymer fuse (the possibility of using 1A fuses, not supplied) as well as with overvoltage protection - varistors. Output state is
indicated by 5 L1 ÷ L5 LEDs. Fuse failure is indicated by turning off the appropriate LED: L1 for AUX1, L2 for AUX2 etc. Additionally, in
the case of failure, the FPS output (Hi-Z state) and the L
FPS
LED are switched on. The FPS output can be used for remote control of a
module e.g. external optical indication. The module is adapted for connection of cables with a maximum cross section of 2,5mm
2
.
2. Module description.
2.1. Description of components and connectors of
the module.
Fig. 1. Electrical diagram.
Element
no. [fig. 2]
Description
[1]
L1 ÷ L5 green LEDs
[2]
F1 ÷ F5 fuses in the AUX (+)
circuits
[3]
AUX1 ÷ AUX5 independently
secured outputs,
common terminal COM (-)
[4]
FPS failure technical output
[5]
IN, COM module’s power input
[6]
Mounting panel
[7]
L
FPS
(red) LED indicating failure
[8]
Jumper for fuse - glass
fuse/PTC
3. Specifications.
Supply voltage
10V ÷ 30V DC (-2%/+2%)
10V ÷ 24V AC (-2%/+2%)
Output voltage
U
AUX
= U
IN
(equal to supply voltage)
Current consumption
6mA ÷ 41mA @ Uin=10 ÷ 30V DC
10mA ÷ 32 mA @ Uin=10 ÷ 24V AC
Number of power inputs
1 (IN terminals) max. 2,5mm
2
cable
Number of power outputs
5 (AUX terminals) max. 2,5mm
2
cable
Protections against:
- a short circuit SCP
- an overload OLP
- a surge
- 5 x F 0,5A fuse or PTC 0,5A (the
possibility of using 1A fuses, not supplied)
- varistors
LED indication
- green LED L1 ÷ L5 status of the
AUX1÷AUX5 outputs
- red LED L
FPS
indicates failure
F1 ÷ F5 fuses
F 0,5A or PTC 0,5A
Operating conditions
II environmental class, -10°C ÷ 50°C
Dimensions
L=150, W=43, H=30 (+/-2mm)
Installation
A mounting panel with an adhesive tape,
mounting screws x2 (holes 3mm)
Connectors:
- power supply input/
output, technical output
Ф0,51÷2,05 (AWG 24-12) 0,5 ÷ 2,5mm
2
Declaration, warranty
CE, 2 year from the production date
Net/gross weight
0,09kg / 0,12kg
Fig.2. The view of the module.
Pulsar
Siedlec 150, 32-744 Łapczyca, Poland
Tel. (+48) 14-610-19-40, Fax. (+48) 14-610-19-50
e-mail: biuro@pulsar.pl, sales@pulsar.pl
http:// www.pulsar.pl, www.zasilacze.pl
EN**
WEEE PARKING
According to the EU WEE Directive It is required not to dispose of electric or electronic waste as unsorted municipal waste
and to collect such WEEE separately.

Summary of content (1 pages)