5
PReasy 4116
+
-
+
-
44
43
42
41
33
32
31
+
-
12
14
13
11
10 V
1 V
+
-
10 V
1 V
24
23
22
21
4 3 2
*
Input for RTD, TC, Ohm,
potentiometer, mA and V
2-wire supply > 16 V
FM-approved for installation in Div. 2
Output for current, voltage and 2 relays
Universal AC or DC supply
Advanced features:
Programmable via detachable display front
(4501), process calibration, signal and relay
simulation, password protection, error
diagnostics and selection of help text in
several languages.
Application:
Linearised, electronic temperature
measurement with RTD or TC sensor.
Conversion of linear resistance variation to a
standard analogue current / voltage signal, i.e.
from solenoids and butterfly valves or linear
movements with attached potentiometer.
Power supply and signal isolator for 2-wire
transmitters.
Process control with 2 pairs of potential-free
relay contacts and analogue output.
Galvanic separation of analogue signals and
measurement of floating signals.
The 4116 is designed according to strict
safety requirements and is thus suitable for
application in SIL 2 installations.
Technical characteristics:
When 4116 is used in combination with
the 4501 display / programming front, all
operational parameters can be modified to
suit any application. As the 4116 is designed
with electronic hardware switches, it is not
necessary to open the module for setting of
DIP-switches.
A green / red front LED indicates normal
operation and malfunction. A yellow LED is
ON for each active output relay.
Continuous check of vital stored data for
safety reasons.
4-port 2.3 kVAC galvanic isolation.
Applications
Input signals:
Current
Potentio-
meter
Output signals:
Relays
Supply:
21.6...253 VAC
or
19.2...300 VDC
Analogue, 0/4...20 mA and voltage
Volt-
age
RTD and lin. R TC
Connection, wires
UNIVERSAL TRANSMITTER
*Order separately: CJC connector 5910.
MTS
Messtechnik
Schaffhausen GmbH
CH
-
8260 Stein am Rhein
Telefon +
4152
-
6725000
Messen Prüfen Automatisieren www.mts.ch