Description
The PAD100-MIM is used to monitor the status of an initiating
device(s) that contain a normally open set of dry contacts. The module
is enclosed in a plastic case to protect against inadvertent shorts and
ground faults. The case can be mounted using a single screw. The
PAD100-MIM has a status indicator LED to indicate communication
and alarm condition. In normal condition, the LED ashes when the
device is being polled by the control panel. When the input is activated,
the LED will ash at a fast rate.
Application
The micro input module (PAD100-MIM) is compatible with Potter’s
IPA and AFC/ARC series addressable re alarm control panels.
Generally the PAD100-MIM is used to monitor pull stations and
other devices where the module is installed in an electrical box or
enclosure behind the device being monitored.
Technical Specications
Operating Voltage 24.0V
Max SLC Standby
Current
200μA
Max SLC Alarm
Current
200μA
IDC Input Circuit
Wiring
Class B
Max Wiring Resistance
of IDC
100 Ω
Max Wiring
Capacitance of IDC
1μF
EOL Resistor 5.1K Ω
Operating Temperature
Range
32 to 120ºF (0 to 49ºC)
Operating Humidity
Range
0 to 93% (non-condensing)
Max no. of Module Per
Loop
127 units
Dimensions
1.75” (44.5mm)L × 1.36”
(34.5mm)W× .43” (11mm)D
Mounting Options 2-1/2” (64mm) deep single-gang box
Shipping Weight 0.3 lbs
Features
One Class B contact monitoring input
Small size allows mounting in most electrical boxes
SLC Class A, Class X & Class B
6” Pigtail wiring connections
Product includes a 5 year warranty
UUKL Listed for Smoke Control