Owner's Manual
PAD100-MIM
Micro Input Module
8830079 - REV D • 12/18 PAGE 1 OF 2
Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com
Description
The PAD100-MIM is used to monitor the status of an initiating
device(s) that contain a normally open set of dry contacts. The module
is enclosed in a plastic case to protect against inadvertent shorts and
ground faults. The case can be mounted using a single screw. The
PAD100-MIM has a status indicator LED to indicate communication
and alarm condition. In normal condition, the LED ashes when the
device is being polled by the control panel. When the input is activated,
the LED will ash at a fast rate.
Application
The micro input module (PAD100-MIM) is compatible with Potter’s
IPA and AFC/ARC series addressable re alarm control panels.
Generally the PAD100-MIM is used to monitor pull stations and
other devices where the module is installed in an electrical box or
enclosure behind the device being monitored.
Technical Specications
Operating Voltage 24.0V
Max SLC Standby
Current
200μA
Max SLC Alarm
Current
200μA
IDC Input Circuit
Wiring
Class B
Max Wiring Resistance
of IDC
100 Ω
Max Wiring
Capacitance of IDC
1μF
EOL Resistor 5.1K Ω
Operating Temperature
Range
32 to 120ºF (0 to 49ºC)
Operating Humidity
Range
0 to 93% (non-condensing)
Max no. of Module Per
Loop
127 units
Dimensions
1.75” (44.5mm)L × 1.36”
(34.5mm)W× .43” (11mm)D
Mounting Options 2-1/2” (64mm) deep single-gang box
Shipping Weight 0.3 lbs
Features
• One Class B contact monitoring input
• Small size allows mounting in most electrical boxes
• SLC Class A, Class X & Class B
• 6” Pigtail wiring connections
• Product includes a 5 year warranty
• UUKL Listed for Smoke Control
firealarmresources.com