Preliminary ILB BT ADIO MUX... Description The set consists of two modules that form a fixed pair as the master and slave. The Wireless-MUX module transmits 16 digital and 2 analog signals bidirectionally by means of wireless communication. It therefore replaces a 40-wire signal cable. The wireless solution has been developed specifically for use under industrial conditions. It is reliable, robust, and easy to handle.
Description .............................................................................................................................. 1 2 Table of contents ..................................................................................................................... 2 3 Ordering data .......................................................................................................................... 3 4 Technical data ...................................................................
Order No. Pcs./Pkt. Wireless-MUX set, two modules with 16 digital inputs and ILB BT ADIO MUX-OMNI outputs and 2 analog inputs and outputs (0 ... 20 mA, 0 ... 10 V) each, incl. omnidirectional antennas with 1.5 m cable 2884208 1 Wireless-MUX set, two modules with 16 digital inputs and ILB BT ADIO MUX outputs and 2 analog inputs and outputs (0 - 20 mA, 0 - 10 V) each, without antennas 2702875 1 Accessories Type Order No. Pcs./Pkt.
Pcs./Pkt. Omnidirectional antenna, 2.4 GHz, 6 dBi, linear vertical, opening angle h/v 360°/20°, N (female), IP65, salt water resistant RAD-2400-ANT-OMNI-6-0SW 2903219 1 Dual band omnidirectional antenna with protection against RAD-ISM-2459-ANT-FOODvandalism; IP68 protection; frequency band/gain: 6-0 2.4 GHz/up to 6 dBi, 5 GHz/up to 8 dBi; EN 50155; temperature range: -40°C to +80°C; N (f) connection; 1 m long adapter cable, N (m) - SMA (m) connection. 2692526 1 Panel antenna, 2.
Accessories Type Order No. Pcs./Pkt. 2701204 1 Set for mast mounting of the FL RUGGED BOX housing, incl. screw clamps for masts up to 89 mm FL RUGGED BOX POLE SET 2701205 1 Vulcanizing sealing tape for external protection of adapters, cable connections, etc. against the effects of weather, roll length: 3 m RAD-TAPE-SV-19-3 1 Control box for robust construction of wireless systems for FL RUGGED BOX industrial applications, IP66, 25 x 18 x 13 cm, polycarbonate material, gray, drilled, incl.
Power supply for module electronics Supply voltage 24 V DC Supply voltage range 19.2 V DC ... 30.5 V DC (via power connector) Current consumption 60 mA (Communications power at 24 V DC, 25 °C) Preliminary ILB BT ADIO MUX... 25 mA (Actuator supply, +load current Digital OUT (8 A)) Protective circuit Polarity protection, surge protection Connection method Inline connector Wireless interface 2.402 GHz ... 2.48 GHz (ISM bandwidth) Channel distance 2 MHz No.
Preliminary ILB BT ADIO MUX... Digital outputs Behavior with inductive overload Output can be destroyed Reverse voltage resistance to short pulses Reverse voltage proof Resistance to permanent reverse voltage ≤2A Behavior at voltage switch-off The output follows the power supply without delay Overcurrent shut-down ≥ 0.7 A Output current when switched off ≤ 10 µA (When not loaded, a voltage can be measured even at an output that is not set.
Preliminary ILB BT ADIO MUX... Certification Conformance FCC Directive, Part 15.247 ISC Directive RSS 210 EAC UL, USA/Canada UL 508 Listed Emitted interference in acc. with EN 61000-6-4 Emitted radio interference in acc.
5 Safety regulations and installation notes 5.1 Intended use 5.2 The devices are intended for application in industrial environments. • Turkey: Please note that, in combination with antennas, the maximum permissible transmission power may be exceeded. In this case, set the transmission power via the software. Install the wireless module at least 1 m away from other devices using the 2.4 GHz frequency band (e.g., WLAN, Bluetooth, microwave ovens).
FCC approval This device complies with Part 15 of the FCC rules and Industry Canada's licence-exempt RSSs. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received, including interference that may cause undesired operation. NOTE: Interference This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules.
6 Local diagnostic and status indicators 7 Connect supply, actuators, and sensors Preliminary ILB BT ADIO MUX... CAUTION: Electric shock AO2 PWR1 FS LINK AI2 QUALITY The device is only intended for operation with SELV according to IEC 60950/EN 60950/VDE 0805.
7.1 Terminal point assignment NOTE: device damage 2-7 1 1 2.1 1.1 1 2 2.1 1.1 1.2 1.3 1 1 2 2 3 3 1.2 2.2 1.3 1 1 2 2 3 3 AI2 2.3 1.4 2 AO The terminal points for GND and UL can have a total current of 8 A per terminal point. Make sure that this value is not exceeded. 2 TY LINKLI QUA 4 4 2.2 The feeding points have the same ground potential. All ground supplies on a device are electrically connected with one another. 2.3 2.
8 Preliminary ILB BT ADIO MUX... Basic circuit diagram 24 V DC UL μC 3,3 V DC 24 V DC Preliminary 15 V DC UA OUT IN Figure 4 9 OUT IN Digital Analog Basic circuit diagram Connection example The numbers above the device identify the connector slots.
Assignment of terminal points to the remote station Master Slave Slave Master Master Slave Slave 4 (IN) 1.1 2.1 1 2 2 (OUT) 1.1 2.1 1 2 Slot Terminal point LED Slot Terminal point LED 4 (IN) 1.1 2.1 1 2 2 (OUT) 1.1 2.1 1 2 Slot Terminal point Slot Terminal point Connector 7: Analog IN 1.1 2.1 1.2 2.2 Connector 6: Analog OUT 1.1 2.1 1.2 2.2 Slot Terminal point Slot Terminal point Connector 7: Analog IN 1.1 2.1 1.2 2.2 Connector 6: Analog OUT 1.1 2.1 1.2 2.2 1.2 3 2.2 4 1.3 5 2.3 6 1.4 7 2.
11.1 Antennas When installing two antennas, it is desirable to have a line of sight between them wherever possible, as any obstacles between the antennas will impair the connection. The Fresnel zone, which extends around the direct connecting line between transmitting and receiving antennas, should also be taken into account. For an optimum wireless connection, this zone must be free of obstacles.
Preliminary ILB BT ADIO MUX... RAD-ISM-2400-ANT-OMNI-2-1-RSMA omnidirectional antenna (supplied as standard) Order No. 2701362 Temperature range -20 °C ... +65 °C Degree of protection IP65 Impedance 50 Ω Gain 2 dBi Cable length 1.
Preliminary ILB BT ADIO MUX...
11.2 Range 11.3 Specifying ranges is very difficult due to the influence of various factors. Based on practical tests, it is possible to provide the following guide values. They may be significantly higher or lower depending on the actual application. Typical combinations of antennas and adapter cables Preliminary ILB BT ADIO MUX...