idDAS Installation and Maintenance Guide Doc. No. 00109GU Rev. 2.0 cobhamwireless.
Preface Material Copyright © 2020 Axell Wireless Limited trading as Cobham Wireless All rights reserved. No part of this document may be copied, distributed, transmitted, transcribed, stored in a retrieval system, or translated into any human or computer language without the prior written permission of Axell Wireless Limited trading as Cobham Wireless. The manufacturer has made every effort to ensure that the instructions contained in this document are adequate and free of errors and omissions.
About this Manual and for whom it is Intended This Installation Guide is intended for experienced technicians and engineers. It is assumed that the customers installing, operating, and maintaining Cobham Wireless equipment are familiar with the basic functionality of this type of equipment.
General Warnings Required Permissions and Licenses Prior to the use of this equipment, the user must ensure they have the permissions and licenses required for the intended transmissions. Safety Instructions and Warnings Throughout this manual, important safety warnings and admonishments are included to warn of possible hazards to persons or equipment. A safety warning identifies a possible hazard and then describes what may happen if the hazard is not avoided.
FCC Part 15 This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.
idRU IC Compliance WARNING! This is NOT a CONSUMER device. This device is designed for installation by an installer approved by an ISED LICENCEE. You must have an ISED LICENCE or express consent of an ISED Licensee to operate this device. ATTENTION! Ce n'est pas un appareil consommateur. Cet appareil est conçu pour être installé par un installateur agréé par un licencié ISED. Vous devez avoir une licence ISED ou le consentement exprès d’un détenteur de licence ISED pour utiliser cet appareil.
Maximum Permissible Exposure (MPE) calculation for frequency bands MPE calculation for 395MHz, 446MHz, 791MHz, 2540MHz NOTE: Limits according to FCC. The following calculations are used to estimate MPE distance for a single band and for multiple bands: Parameters for calculation: Pn = Maximum measured conducted power for each single path, 43.75 dBm = 23,714 mW G = Maximum antennas gain (w/o cable loss) = 14dBi, 11dBi, 8dBi, 5dBi Gn = Maximum antenna gain 13.617, 12.589, 6.309, 3.
Combined Bands: x x x x Each idRU supports up to four bands that are combined in one PLEXER into one antenna port. Each band can transmit up to +43.75 dBm (23.714W). All four bands can transmit four times the power, +49.75dBm (94.856W). When more than one operator operates the band, the power budget is divided between the operators automatically. For example, when two operators using same band (different frequencies), each operator has a maximum output power of +40.75dBm (+43.75dBm / 2 = +40.75dBm).
Equation for minimum distance for multiple bands: R Worst case scenario when all bands are active. ANTENNA GAIN 14dBi 11dBi 8dBi 5dBi R- MINIMUM DISTANCE 524.37 cm 371.22 cm 262.80 cm 186.
The maximum recommended power density or field strength for typical Cobham Wireless repeaters would be as follows: FM broadcast 100MHz 2W/m² VHF 150MHz 2W/m² TETRA 390MHz 2W/m² UHF 460 MHz 2.3W/m² 900 MHz 4.5 W/m² 1800 MHz 9 W/m² 2100 MHz 10 W/m² 2600 MHz 10 W/m² It should be noted that exposure to electromagnetic fields in excess of those stated above is not necessarily dangerous to the public but should such fields be present the installation should be investigated and action taken.
General Safety Warnings Concerning Use of System Throughout this manual, there are "Caution" warnings. "Caution" calls attention to a procedure or practice, which, if ignored, may result in injury or damage to the system, system component or even the user. Do not perform any procedure preceded by a "Caution" until the described conditions are fully understood and met.
x Caution: RF Exposure x x x RF radiation, arising from transmitter outputs connected to AWL’s equipment, must be considered a safety hazard. This condition might only occur in the event of cable disconnection, or because a ‘spare’ output has been left un-terminated. Either of these conditions would impair the system’s efficiency. No investigation should be carried out until all RF power sources have been removed.
Sécurité générale concernant l'utilisation du système Lables Attention! Tout au long de ce manuel , il y a des avertissements "Prudence." s "Prudence" attire l'attention sur une procédure ou pratique, qui , si elle est ignorée , peut entraîner des blessures ou des dommages au système, un composant du système ou même l'utilisateur. Ne pas effectuer toute procédure précédée d'une «Attention» jusqu'à ce que les conditions décrites sont parfaitement comprises et respectées .
x Attention: exposition à RF x x x x x x Attention: sensibles aux décharges électrostatiques Attention: laser de classe 1 Cobham Wireless x Rayonnement RF qui découle de sorties du transmetteur connecté à l'équipement de AWL, doit être considéré comme un danger pour la sécurité. Cette condition ne peut se produire en cas de déconnexion du câble, ou parce qu'une sortie 'supplémentaire' a été laissée non terminée. Chacune de ces conditions serait nuire à l'efficacité du système.
x Changement de piles et élimination x Le module A-POI Controller contient une pile bouton Renata CR1220 Pile au lithium non rechargeables. L'unité MSDH contient une pile bouton Panasonic Modèle BR1225A de la batterie au lithium non rechargeable. PRECAUTIONS ! Levage et autres recommandations sur la santé et la sécurité Blocs DC Requis Cobham Wireless x x Risque d'explosion de la batterie est remplacée par type incorrect.
Table of Contents 1 IDDAS SYSTEM DESCRIPTION .................................................................................................. 1 1.1 About the idDAS System .......................................................................................................... 1 1.2 Architecture ............................................................................................................................. 3 1.3 Elements Interfaces and Power Feed .............................................
8 ORDERING INFORMATION .................................................................................................... 143 8.1 EMEA/APAC Ordering Information ........................................................................................143 8.2 Americas Ordering Information ..............................................................................................145 8.3 Bespoke Ordering Information ...........................................................................................
1 idDAS System Description This chapter provides the following information x Introduction to the idDAS system x Features of the idDAS system x idDAS for public safety x idDAS architecture x Detailed descriptions of each element, including power consumption and interfaces 1.1 About the idDAS System Cobham Wireless idDAS provides a customizable and expandable cellular and data coverage solution for multiple operators and services over a common infrastructure.
1.1.2 idDAS for Public Safety idDAS supports families of products specifically designed for to meet rigid public safety requirements as required in various regions.
1.2 Architecture The idDAS solution consists of the following main elements – refer to Figure 1-2: x APOI — Active Point of Interface. A headend service conditioning unit that supports up to 16 BTS sectors (+30dBm max input power) via up to eight, modular plug in band specific modules. See Section 1.3.1 for A-POI interfaces. NOTE: Some Public Safety installations include POI instead of APOI equipment. x MTDI — Multi-Technology Digital Interface.
1.3 Elements Interfaces and Power Feed This section describes the interfaces and power feed of the A-POI, MTDI, MSDH, and idRU. 1.3.1 A-POI Description The A-POI (Active Point of Interface) conditions and controls the level of up to 16 low power BTS sectors via band dedicated conditioning modules. All A-POI modules and interfaces are located on the front panel. The power connections for both AC and DC models are located on the rear panel. NOTE: A-POI RF modules support a maximum power of 30dBm.
Table 1-1. APOI Modules Descriptions BTSI MODULES DESCRIPTION BTSI RF Interfaces Up to eight hot-swappable band-specific conditioning modules that provides BTS to MTDI interfaces. Each module supports two same-band channels of up to 30dBm. x BTS side – simplex and duplex connections x MTDI side – simplex only. x RF interfaces – four QMA female connectors per sector: two BTS and two MTDI.
1.3.1.2 A-POI Power Feed and Grounding This section details the APOI power feed requirements for 100-240VAC and 48V DC. For bespoke applications feed, refer to Section 1.4.1. X2 VAC, 1A Max AC Feed APOI AC Power feed 100-240V~ 50/60Hz, 1A Max Connect BOTH power connectors. Figure 1-5. APOI AC Power Feed 48V DC 48V DC, 2A Max/feed Equipment DC Power Feeding: 48V DC, 2A max Power Interface Pins (numbered from left to right): Pin 1,2 Positive (+) Pin 3,4 Negative (-) Figure 1-6.
1.3.2 MTDI Description The MTDI (Multi Technology Digital Interface) unit digitizes and filters up to 16 conditioned RF sectors from one or more A-POI shelves, or up to 8 sectors from POI interfaces. The filtered signals are combined and routed over a single CPRI link (SM or MM) towards the MSDH. Signal digitization is implemented via four, band specific dual-channel modules. The MTDI is managed via the MSDH. 1.3.2.
1.3.2.2 MTDI Power Feed The section describes the power feed options for 100-240VAC or 48V DC. For bespoke 12V DC feed, refer to Section 1.4.2). MTDI AC Feed GND lug VAC 2A max AC Power feed 100-240V~ 50/60Hz, 2A Max AC feed models support a single ground lug located on the rear panel. The Figure 1-8.
1.3.3 MSDH Description The MSDH (Multi Sector Digital Hub) serves as the idDAS central switching hub and control system. It routes digitized cellular resources received from MTDI units along with data from the Ethernet backbone to the connected idRUs. All resources are routed over CPRI connections. Note the following: x The MSDH supports 16 CPRI interfaces and 16 Ethernet backhaul ports. x Each MSDH supports connection to a single additional MSDH via one of the CPRI ports.
INTERFACE DESCRIPTION LAN port Ethernet management. Console port Serves as an additional local setup port. This is useful if the LAN port is already connected to the network. System LEDs x Power and Master – steady green x Identify and Status – off x All LEDs flash every ~12sec. x Identify function – When the Identify function is activated in the GUI, all LEDs of the relevant MSDH unit blink very quickly. 1.3.3.
1.3.3.3 MSDH Fan Module The MSDH supports a replaceable fan module that can be accessed from the rear panel. For instructions on replacing the fan module, refer to section 6.6.3. The fan module and the replacement instructions are identical for the MSDH and for the MTDI and are only described in dedicated sections for clarity. Replaceable fan module Figure 1-16. MSDH/MTDI Fan Module 1.3.3.
1.3.4 idRU Interfaces A range of idRU 30 medium power, idRU 40 high power, and PS NFPA idRU models are available. The interfaces of the models may vary according to the required connections. NOTE: idRU high power units require a fan-hood assembly for additional cooling. 1.3.4.1 idRU Enclosures Following are illustrations of the idRU enclosures. idRU Medium Power idRU High Power Public Safety idRU Figure 1-18.
1.3.4.2 idRU Front Panel Elements The interface panels of idRU models may differ according to the number of antenna ports and other criteria. Figure 1-20 provides a typical example of a medium power idRU. GND Power Additional band Cascading Service te e antenna External alarms routing CPRI from MSDH AUX2 N/A CPRI for cascading IP backhaul connection Figure 1-20.
1.3.4.3 idRU PS NFPA Front Panel Elements The interface panels of idRU Public Safety NFPA models are similar to the standard idRU interfaces described in Section 1.3.4.2 with two differences: x The red enclosure x The External Alarms of some PS NFPA models are connected via a Binder-type connector and the alarms pin-out differs from the pin-out of standard repeaters Figure 1-21 provides a typical example of a PS NFPA idRU.
1.4 Bespoke 12V DC Headend Elements This section describes the bespoke headend elements supporting an external 12V DC power source: APOI, MTDI, and MSDH. Aside from the 12V DC power source, the interfaces and operation of these elements are identical to the standard elements as described in Section 1.3. 1.4.1 12V DC APOI Power Feed 12V DC Feed Be sure the power input does not exceed 12V DC.
1.4.3 12V DC MSDH Power Feed MSDH 12V DC Feed ATTENTION! Be sure the power input does not exceed 12V DC Equipment DC Power Feeding: 12V DC, 12A max Power Interface Pins (numbered from left to right): Pin 1,2 Positive (+) Pin 3,4 Negative (-) 12V DC, 12A Max Figure 1-24.
2 Topology Examples This chapter provides examples of the following types of topologies and applications x Basic topology x Cascaded idRUs x Master Slave topologies x Redundancy driven topologies – RF source and dual-system redundancy driven topologies x Special applications such as single CPRI link, idDAS for Australia, and WCS applications. NOTE: Additional topologies are supported. Each type of topology requires the appropriate setup and configuration procedures. 2.
2.2 Cascaded idRU Topology This topology supports up 36 idRUs connected to the MSDH in cascades or ‘strings’ of up to six remotes per string. The first remote in the string is connected directly to the MSDH, and the remaining remotes in the same string are interconnected. All connections are CPRI based. This provides more coverage per fibre optic link between the MSDH at the headend and remotes. The following figure illustrates the connections for a single cascade. Figure 2-2.
2.3 Master Slave Topologies This topology provides single source management for two cascaded MSDH units. A total of 36 idRUs are supported for the installation that includes both MSDH units. In this type of installation, the two MSDH units are cascaded and each MSDH unit interfaces to dedicated idRUs or idRU cascades referred to as ‘strings’. Depending on the required capacity, the MSDH units can be fed from either a single MTDI connected to the Master MSDH, or each MSDH may be fed from a dedicated MTDI.
2.4.1 RF Source Redundancy Driven Topologies The RF source redundancy driven topology supports end-to-end cell resource redundancy for a system with up to 36 cascaded remotes, installed in strings of up to six remotes per string. Each remote in a cascade has access to two independent RF feeds that include BTS farms, MTDI, and MSDH units. Redundancy is provided per individual cell resource in each remote.
Figure 2-6. Illustration of an RF Source Redundancy Driven Topology This area is intentionally left blank… Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
2.4.2 Dual-System Redundancy The dual-system redundancy driven topology provides full, end-to-end redundancy consists of two independent systems, where only one of the systems transmits RF at any one time. By default, the user designated ‘Active’ system transmits RF, and the designated Standby system is muted. If a fault is detected, switchover occurs. Each system consists of an independent set of BTS, MTDI, MSDH, and idRU units.
The following figure illustrates a dual system redundancy installation with Master-Slave MSDH and multiple MTDIs per system. The MTDIs can be connected to the same MSDH or to dedicated MSDH units. Figure 2-8. Example of Dual-system Redundancy Topology with Master-Slave and Multiple MTDIs Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
2.5 Additional Applications This section describes special topologies for specific types of requirements. The general architecture and the system elements operate as described in section 1.2 however the connections are specific to each type of special topology.
Figure 2-10, provides a detailed block diagram of the same topology for Australia. Note the following: x The CPRI link must support the needed capacity. x The topology is implemented for the usage of three operators, where some bands are allocated to one operator, some to two operators and some to three operators. x Headend elements: x The APOI, MTDI and MSDH installations are standard as described in Chapter 3. x Two APOI and two MTDI units are required for this topology.
2.5.2 WCS Applications To implement a MIMO configuration of WCS and 700/850/1700/1800 bands, three idRUs are required: x Two quad-band idRUs supporting 700, 800, 1700 and 1800 MIMO A and MIMO B bands; x One idRU supporting two 2300 LTE TDD filters, amplifiers and antennas ; Each quad-band idRU receives its bands along with the 2300FDD band from the MSDH via a dedicated CPRI link. The filtered and amplified services from each idRU are forwarded to the idRU 2300 TDD, along with the 2300 TDD.
2.5.3 Five Band SISO Configuration The five-band SISO configuration distributes five bands (800, 900, 1800, 2100 and 2600) over a single antenna infrastructure connected to one of the repeaters (Main). All five bands are transferred over a single CPRI connection from the MSDH. The Main idRU conditions four of the bands and the Aux idRU conditions one of the bands (2100). All five bands are then distributed over the same antenna infrastructure connected to the Main idRU.
2.5.4 Multi-Operator Eight Band MIMO Configuration The eight-band MIMO configuration routes eight bands (800MIMO, 900, 1800MIMO, 2100 and 2600MIMO) over a single CPRI link, for conditioning and distribution at the remote end over two remote units with dedicated antennas. All eight bands are transferred over a single CPRI connection from the MSDH. The Main idRU conditions and distributes four of the bands; the Aux idRU conditions and distributes four other bands.
3 System Installation Requirements This chapter provides the following information x General warnings x Public safety pre-installation requirements x Location selection criteria x Optics related requirements x Grounding wire requirements x Power requirements and power cables x EMV protection x idRU service antenna requirements 3.1 General Warnings x ATTENTION! The installer is held accountable for implementing the rules required for deployment.
x 32/21 M/PG x d2 28.3, d1 22.8 x 45mm Radius (Stat.) x 9.0Kg/100m x 50m VE,PU 3.3 Headend and idRU Location Criteria This section describes the locations criteria for the headend elements and for the remote units. 3.3.
3.4 RF Cable Installation Guidelines DC Blocks Required Blocs DC Requis In some installations, under certain site conditions, it is required to add DC Blocks to the antenna cables of the remote units. For example, in installation locations with power cables that can induce currents resulting in trackside voltages or loop currents. In these types of situations, DC Blocks are required to protect the idDAS remotes from damage.
3.5 Optics Related Requirements This section provides the following information: x Optic fiber cable requirements x Examples of supported CPRI transport cables x Information on required SFPs for the MSDH and for remotes 3.5.1 Optic Fibre Cable Requirements and Warnings CAUTION! Un-terminated optical receptacles may emit laser radiation. Do not stare into beam or view with optical instruments. PRUDENCE! Récipients optiques qui ne sont pas terminées peuvent émettre un rayonnement laser.
3.6 Grounding Wire Requirements x Where relevant, ground the units with their grounding bolts. x Protective grounding conductor - should be aluminum with cross-section 10AWG. x Lug of the protective grounding conductor - should be aluminum x Washers and screw - should be high Cr stainless steel, or 12% Cr stainless steel, or Cr on, Ni on steel, tin on steel 3.7 Power Requirements and Power Cables 3.7.
3.7.2.2 Cellular idRU Power Specifications IDRU 30 POWER FEED AMP / FEED POWER CONSUMPTION Quad-Band idRU 30 100-240V~ 50/60Hz 48V DC 3A Max 3A Max (per feed) 210W Max IDRU 40 POWER FEED AMP / FEED POWER CONSUMPTION Quad-band idRU 40 100-240V~ 50/60Hz 12A Max 690W to 820W 3.7.2.3 Public Safety idRU Power Specifications IDRU 40 POWER FEED AMP / FEED POWER CONSUMPTION Single-band Tetra idRU 40 48V DC 5A Max 193W 3.7.2.
Below is an example of a circuit breaker plan for a DC powered idDAS headend elements rack. Figure 3-1. Example of Circuit Breaker Plan for DC Powered Headend Elements 3.7.4 AC Power Cables This section describes the headend and remote end AC power cables. 3.7.4.1 Headend Elements - AC Power Cables AC Power Cables are provided only for AC powered units, where the supplied power cord meets the requirements of your geographical location.
For AC powered idRUs installed outdoors x x Add external to the unit, a surge suppressor rated min. 2500V: x For Europe – the surge arrestor should be installed according to local installation code and comply with IEC 61643-series. x For USA and Canada - the surge arrestor should be installed according to CEC Section 280 and NEC 26-500 to 26-512 and ANSI/NFPA70 and comply with UL 1449 standard.
3.8 EMV Protection CAUTION! Protect all coaxial cables and power cables from the transients caused by lightning. If insufficient Electromagnetic Protection is provided, or if EMV measures are not taken, warranties issued by Cobham Wireless are not valid. PRUDENCE! Protégez tous les câbles coaxiaux et les câbles d'alimentation des transitoires causés par la foudre.
3.9 idRU Service Antenna Requirements This section describes the requirements for installing the service antennas. idRU Compliance to FCC and IC WARNING! x x Direct connection of antenna to the SERV/MOB port is not permitted.
3.9.2 Indoor Installations Service Antenna Requirements Determine the antenna installation configuration, according to the transmission requirements and the installation site conditions. Installation requirements: x An indoor antenna should be installed at a convenient location. It should be free of metallic obstruction. x Install the Service Antenna at the designated height and tune it roughly toward the Service coverage area. 3.9.
4 Headend Elements Installation This chapter describes the installation of the following idDAS elements: APOI, MTDI and MSDH. This chapter provides the following information x Overview of the headend elements installation x Unpacking and accessories provided with each type of element x Rack mounting of headend elements x MSDH connections including MSDH to MTDI connections x For installations with APOI – APOI to MTDI x RF source connections to idDAS APOI or MTDI according to the installation 4.
4.2 Unpacking the Headend Units 4.2.1 General Instructions Upon receiving each element/ unit, do the following: x Examine the shipping container for damage before unpacking the unit. x Perform a visual inspection to reveal any physical damage to the equipment. x Verify that all of the elements listed in the shipping list are included. x If any of the above conditions are not met, contact Cobham Wireless service representative. 4.2.
4.2.4 MSDH AC/48V DC Packing List ITEM X1 Flash Drive with documentation and driver for USB cable A to B (cable is not supplied) X1 Cable RJ45 LSZH 1GBit CAT6 3m 180 DEG For 48V DC powered models: X1 Power cable DC distribution unit MSDH 2.5M X1 Connector female 3.81mm 4-Pin, 8A X1 Green/yellow earth CBL LSZH 300mm M4 Ring T. For AC powered models, one or more of the following cables according to your region: X1 Power cable SAA/3-H05VVF3G1,00-C13/2.5M X1 UK AC power cable TO C13 2.
4.3 Mounting in Rack, Ground and Power Connections This section provides instructions for mounting, powering and grounding individually supplied elements. NOTE: For headend units that are pre-installed in a cabinet, follow the instructions provided with our cabinet for grounding and power connections to the cabinet. 4.3.1 Mounting Elements in the Rack 4.3.1.1 Headend Elements - Physical Specifications Note the following: x The operating temperature of all elements is -5 to +50°C.
4.3.1.2 Rack Mounting Considerations General Rack-mounting Criteria x Verify the rack location meets criteria described in section 3.3.1. x Referring to the element dimensions described in 4.3.1.1 and to Figure 4-1, plan the location of each element in the rack: x x (Where relevant), DC power supply strip and power distribution unit should be located at the bottom of the rack.
4.3.2 Grounding APOI, MTDI and MSDH ATTENTION! x Refer to section 3.6 - Grounding Wire Requirements. x Ground the unit according to the grounding standards required in your region. x Make sure the grounding product used is suitable for the kind and size of cable being used. x Connect the ground bolt to the same ground. x Be sure the ground is connected before powering the equipment. ATTENTION! x Se reporter à la section 3.6 - Grounding Wire Requirements.
4.3.3 Powering A-POI, MTDI and MSDH This section describes the power connections for AC and for DC powered headend elements. 4.3.3.1 AC Powering Headend Elements CAUTIONS! x x AC powered APOI, MTDI and MSDH may be supplied with one or more AC power cords: EU, United Kingdom, Americas and Australia. Use only the supplied power cord and use the power-cord relevant to your geographical location. Be sure the equipment ground is connected before powering on the equipment.
4.3.3.2 48 V DC Powered Headend Elements CAUTIONS! x Be sure a CIRCUIT BREAKER meeting the instructions given in section 3.7.3 is connected near the shelf at an easily reachable and accessible location from the units. x The units are powered ON and powered OFF via the circuit breaker. PRUDENCE! x Assurez-vous d'un DISJONCTEUR prévu selon les instructions données dans la section 3.7.3, est x relié à proximité du châssis, dans un endroit qui est facilement accessible et accessible à partir des unités.
CONNECTOR PINOUT Equipment DC Power Feeding: 48V DC APOI: 2A max per feed; MTDI/MSDH: 3A per feed Power Interface Pins (numbered from left to right): Pin 1,2 Positive (+) Pin 3,4 Negative (-) For -48V DC Feeding: x Connect Pin 1,2 to RTN (0V) x Connect Pin 3,4 to -48V DC Terminal Connector specification: Nominal current: 8A, Rated voltage 160 V Connect the 48V DC power source to each element feed x Refer to the power specifications in section 3.7.2.1.
4.3.4.2 Powering Bespoke Headend Elements The powering procedure described in this section is relevant for bespoke 12V DC powered elements. x CAUTIONS! Be sure a CIRCUIT BREAKER meeting the instructions given in section 3.7.3 is connected near the shelf at an easily reachable and accessible location from the units. x The units are powered ON and powered OFF via the circuit breaker. x Assurez-vous d'un DISJONCTEUR prévu selon les instructions données dans la section 3.7.
To connect DC power for each elements x Refer to the power specifications in section 3.7.2. x Use wires meeting specifications described in section 3.7.4.1: x Connect the wires to the provided connector. x Refer to the above DC connector pinout. 4.
To install the SFP+ module in the MSDH NOTE: The SFP modules are installed in opposing directions in the MSDH CPRI slots top row and in the bottom row. Cobham Wireless SFP+ in MSDH TOP CPRI row (Label facing UP) 1. To insert the SFP+ modules in the MSDH CPRI top row: x Align the SFP+ module with the MSDH slot opening – SFP+ label facing UP. x Gently insert the SFP+ until it clicks into place. 2.
4.4.3 MSDH to idRU and IP Backhaul Connections This section details the basic connections between the MSDH and hosted idRUs. For more information on connecting the idRUs according to a specific topology such as Master Slave, or RF Source Redundancy, refer to Section 5.6.3. The MSDH CPRI ports provide the interface and route the RF resources towards the connected idRU. This may be a single idRU, or the first idRU in the cascade or ‘string’.
4.4.4 MSDH PS NFPA Output Alarm idDAS PS MSDH supports one General alarm relay that is triggered if any of the MSDH alarms are activated. The alarm status is reflected by the General indicator in the Master MSDH window – see Figure 4-11. The user may choose to disengage specific alarms from the relay as described in Section 4.4.4.2. NOTE: For the part numbers of the relevant MSDH units, refer to Section 8.1.2.2. 4.4.4.
4.4.4.2 MSDH General Alarm Filtering To filter out MSDH alarms affecting the relay 1. Select the MSDH Alarms Configuration hover-menu option. 2. Click the Advanced button. 3. Under Dry Contact, uncheck the required alarms to disengage them from the relay. 4. Click Apply. Filtering Relayed Alarms Figure 4-10. Filtering Alarms Associated with the Relay 4.4.4.3 MSDH General Alarm Monitoring As illustrated in Figure 4-9, the MSDH General alarm can be connected as Normally Open or Normally Closed.
4.4.5 MSDH Topologies Connections This section summarizes the MSDH connections required for the following topologies: x Master Slave x RF source redundancy 4.4.5.1 Master Slave MSDH Topology Connections In a Master Slave configuration, two MSDH units are interconnected via any of the CPRI ports. The topology is illustrated in Figure 4-12.
4.4.5.2 RF Source Redundancy Driven Topologies MSDH Connections This section describes the MSDH connections for an RF source redundancy driven topology. In this type of topology, each string of idRUs is connected to two RF supply chains – one at each end of the cascade. The MSDH units in each RF supply chain can located at a distance of up to 40 km from each other, and are interconnected via an Ethernet connection. For an overview and detailed description of the topology, refer to Section 2.4.1.
4.4.5.3 Dual-System Redundancy Driven Topologies MSDH Connections This section describes the MSDH connections for a dual-system redundancy driven topology. In this type of topology, two complete and independent systems are installed and powered-up, but only one system will be transmitting RF at any one time. For more information on the dual-system redundancy topology, refer to Section 2.4.2.
4.5 RF Source to idDAS Connections This section details the RF source to APOI and to MTDI connections. Depending on the size of your system and your familiarity with the idDAS elements, you may either directly perform the connections according to your plan or open an Admin level session to the MSDH and use the BTS Port Wizard tool. The tool is briefly described in Section 4.5.3 and detailed in the idDAS Web Management Guide. 4.5.
4.5.1.2 BTS to APOI Simplex Connections Referring to your installation plan for the connections: 1. Connect the BTS simplex connections: x BTS UL to Band Module UL x BTS DL to Band Module UL/DL 2. For BTS DL > 30dBm, use a Low PIM attenuator. Note the following: x For Simplex connections requiring attenuation, only the DL signal is attenuated to the duplex port. x Verify that the UL BTS interface signal strength corresponds in gain value to the DL BTS interface gain value.
The two A-POI channels on each APOI Band Module are combined; as such, the frequencies must be of different ranges within the band. As illustrated in Figure 4-18, the two combined APOI bands are physically routed towards as single MTDI channel. This enables each MTDI module to support up to four APOI channels. 2X CHANNELS UL1 DL1 A-POI BTSI A COMBINED MTDI RF MODULE UL2 DL2 A-POI BTSI B COMBINED 2X CHANNELS Figure 4-18.
4.5.3 Wizard Guided RF Connections The BTS Port Wizard is a tool provided by the idDAS Web Management. It can be used to facilitate the installation procedure by guiding you through the connections between the RF source and the APOI and MTDI. This ensures that the registered BTS Ports correspond to the physical connections. The BTS Port Wizard is accessed by opening an MSDH session. The tool is detailed in the idDAS Web Management Guide. Click physically connected ports Figure 4-20.
4.5.4 MSDH to idRU Connections NOTE: In order to interconnect MSDH and idRUs, matching SFPs must be installed in elements on either side of the link. To connect idRUs to the MSDH Recommendation for connections x For more orderly connections and intuitive identification, it is recommended to connect idRU CPRI cables to the higher numbered CPRI ports in the MSDH – i.e. Ports 16 and down to the available ports.
5 idRU Installation This chapter includes the following information: x idRU safety guidelines x Unpacking and package contents x idRU 40 fan hood assembly x Rack-mount procedure x Wall-mount procedure x Basic connections x Connections of cascaded idRUs and various topologies x Dry-contact alarms connections 5.
ATTENTION! x It is required to open the idRU only if the installation requires connecting External Alarms* or it is necessary to access the management GUI to diagnose problems; all other interfaces external. x The repeaters are secured with two hex screws (M8) and can also be locked with a key. x The two screws must be fully tightened. Failure to do so may affect the IP66 compliancy and therefore any warranty.
5.2 PS NFPA idRUs Installation Instructions For Public Safety NFPAs NEMA 4 ready idRUs: x Use tubing meeting the specifications detailed in Section 3.2.1, for all connected CPRI and ETH idRU connections. Unused Ethernet and CPRI ports are plugged as described in Section 5.6.5. x idDAS public repeaters support a Binder-type external alarms connecter and additional alarms as described in Section 5.7.2. 5.
5.3.3 Accessories for idRUs with Fan Hood ITEM X1 Flash Drive with documentation and driver for USB cable A to B (cable is not supplied) x2 RJ45 LSZH cable, CAT6,1 Gbit, 3 m, 180 degrees x1 Drill Template — used for marking wall mount drilling holes x4 3/8” Jumbo Anchor Bolts, zinc plated — used for wallmount installations x2 Plugs and O-rings — for plugging up to two unused Ethernet and AUX fibre ports: x Plug — threaded blanking plug, M32x1.
5.4 Brackets and Fan-Hood Assembly Depending on the model and the cooling requirements, repeaters are either provided with standard brackets, or with a fan-hood and the relevant accessories and brackets designed for the fan-hood. This section provides the following information: x Standard bracket assembly for rack and wall mount installations x Fan-hood assembly – for repeaters that include fan-hood.
5.4.2 idRU Fan Hood Assembly For repeaters that include a fan-hood (usually these are idRU-40 repeaters), it is required to assemble the fan hood onto the repeater before the repeater is mounted. x WARNINGS! This installation requires two people. x Assemble the fan hood ONLY on the repeaters with which it is supplied and designated. 5.4.2.1 Assembly Overview and Dimensions The fully assembled system is displayed in Figure 5-6, for reference. The dimensions are displayed in Figure 5-7.
The dimensions of the assembled repeater with the fan hoods are given below. Figure 5-7. idRU with Fan Hood Assembly Dimensions Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
5.4.2.2 idRU-40 Fan Hood Assembly This section describes how to assembly the fan hood onto idRU-40 repeaters. 1. Place the repeater on a flat surface with the repeater door panel facing down and the interfaces towards you. WARNING! Be sure to start with this phase – otherwise, the assembly may be damaged. 2.
3. Assemble the rear fan hood: x Position the rear fan hood under the (inserted) bolts and washers. x Tighten the four bolts. Rear fan hood panel Position under bolts and tighten bolts Figure 5-9. Assembling Rear Fan Hood Panel Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
Figure 5-10 illustrates the assembled brackets and rear fan-hood panel. Figure 5-10. Assembled Rear Fan Hood and Mounting Brackets 4. Mount the repeater according to relevant section: Rack mount – Section 5.5; Wall mount – Section 5.5.2; 5. Assemble front fan-hood panel: x Referring to Figure 5-11, loosely insert the four M8x16 bolts and washers. x Hang the front fan hood on the repeater and tighten the bolts. Loosely insert bolts and washers Figure 5-11.
6. Connect the fan hood power connections — connect the front fan hood and the rear fan hood power connectors to the repeater power connectors. Connect power of rear and front fan hood assemblies Figure 5-12. Fan Hood Power Connections Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
5.5 Mounting the Repeaters This section describes how to mount the repeaters in a rack and on a wall. x IMPORTANT! The weight of the unit requires that two people mount the unit onto the rack. x The repeaters must always be installed vertically with the connectors on the underside for protection. Horizontal installation on a bench for long time may cause damage to the signal booster due to overheating. 5.5.
5.5.2 Wall Mount Procedure x WARNINGS! The repeater mounting procedure is for concrete or brick walls only. x The weight of the unit requires that two people mount the unit on the wall. x Due to the weight of the Repeater, it is NOT recommended to fix to a hollow wall. x Always check that there are no pipes or cables hidden in the wall beneath the area to be drilled. Various pipe and cable detectors are available for this type of inspection.
To mark and drill the wall 1. Plan the location on the wall of the repeaters and any other required equipment (such as the 7-band filer/plexer for Australia if installed on the wall). 2. Using the provided template in the kit, mark out the fixing centers of the repeater and other equipment on the chosen wall. Figure 5-16. Template Example 3. Mark and drill the wall with the correct size masonry bit as specified by the fixing manufacturer.
6. Gently tighten the bolt by hand so that the anchor section of the fixing expands and grips the inside of the hole. Figure 5-17: Inserting Fixing and Tightening. 7. As the bolt pulls its way in, the sides of the anchor section are forced outwards, gripping the surrounding surface. Figure 5-18: Anchor Sides Pushed Outwards. 8. Once all four fixings are in place, carefully withdraw the four bolts. Figure 5-19: Withdraw Bolts Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
5.5.2.2 Mount the Repeater CAUTION! It is recommended that two people lift the repeater since (depending upon the configuration) the idRU weighs between 20 and 38 kg (44 and 84 lb). PRUDENCE! Il est recommandé que le répéteur est soulevé par deux personnes depuis (en fonction de la configuration), le idRU pèse entre 20 et 38 kg (44 et 84 lb). To mount the repeater x Align repeater with the four fixings. Great care should be exercised here as the repeater is very heavy.
The following figures provide EXAMPLES of additional fixings. In the examples, support is provided in the form of a CABLE HARNESS LOOP that is looped around the repeater handle and secured to the wall or part of the building support structure. NOTE: The wallmount procedure illustrated below is relevant for all idRU-40 and idRU-30 models. Figure 5-21: Example 1 – Additional Fixing to Wall Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
Another example is of a repeater installed on a stadium gantry. Again, the support can be in the form of a cable harness loop, using the handle of the repeater and part of the gantry structure. ATTENTION! Any other secure method can be used. ATTENTION! Toute autre méthode sécurisée peut être utilisé. NOTE: The illustration shows an idRU-40. The procedure is identical for the idRU-30.
5.6 idRU Connections This section describes the following connections to single repeaters: GND, CPRI, External Alarms, Antenna and Power. NOTE: The idRU model used for reference provides a general indication for all other connections. CAUTION! If insufficient Electromagnetic Protection is provided, or if EMV measures are not taken, warranties issued by Cobham Wireless are not valid. Refer to section 3.8 for EMV Protection instructions.
To ground the repeater M6 Ground stud Connect the grounding cable and lug to the ground M6 stud on the repeater front panel. Minimum recommended conductive area for a grounding cable: 16mm2 Figure 5-23. Grounding the idRU 5.6.2 SFP Installation and CPRI Connections Follow this basic connection procedure for all topologies. Refer to Section 5.6.3, for connections of specific topologies such as cascaded ‘string’ installations, Master Slave, Redundancy, etc.
To connect the CPRI cable from to the repeater CPRI port 1. Unscrew the protective cylinder on the CPRI port(s) and set the cylinder and the accompanying sponge aside. 2. If not inserted, insert the SFP module in the CPRI port. Figure 5-24. Remove Cylinder 3. Route the optic fibre through the cylinder and press into the rubber seal. Figure 5-25. Press Fiber in Rubber Seal 4. Connect the CPRI connector to the repeater MAIN or AUX1 CPRI port according to your topology. Cylinder 5.
5.6.3 Topology Specific CPRI Connections This section describes how to connect the CPRI cables for the following topologies: x A string of cascaded idRUs x Master Slave topology x RF source redundant topologies 5.6.3.1 Cascaded idRU Connections The cascaded idRU connections are relevant to all topologies that include ‘strings’ of idRUs. To cascade idRUs 1. Connect an optic fibre cable between the AUX1 port of the FIRST repeater to the MAIN port of the next repeater. 2.
5.6.3.2 Master Slave Topology idRU Connections Refer to Section 2.3 for a general description of the Master Slave topology, and to Section 4.4.5.1 for detailed information on the Master Slave element connections and illustrations. For a Master Slave installation connect the idRUs as follows 1. Referring to the site plan, connect the MAIN CPRI port of each first idRU in the string or single idRU to a CPRI port on either the Master or the Slave MSDH 2.
5.6.3.3 Dual RF Source Redundancy idRU Connections Refer to Section 2.4.1 for a general description of the Master Slave topology, and to Section 4.4.5.2 for detailed information on the Master Slave element connections and illustrations. For a dual RF source redundancy connect as follows 1. Connect the MAIN CPRI port of the FIRST idRU to the Primary MSDH. 2. Cascade each of the remaining idRUs — interconnect AUX1 CPRI to MAIN CPRI of next idRU. 3.
5.6.4 Antenna Connections DC Blocks Required Blocs DC Requis In some installations, under certain site conditions, it is required to add DC Blocks to the antenna cables of the remote units. For example, in installation locations with power cables that can induce currents resulting in trackside voltages or loop currents. In these types of situations, DC Blocks are required to protect the idDAS remotes from damage.
5.6.6 Power Connection NOTE: Refer to Section 3.7 for a full description of power requirements. x CAUTIONS! Use only the power cables (AC or DC) and any other relevant accessories provided with the unit to connect power to the idRU. x Be sure to disconnect all power sources before servicing. x Be sure the equipment is grounded before powering it on. x Make sure the antenna cables or 50 ohm terminations are connected to the repeater’s antenna connectors before the repeater is turned on.
5.7 External Alarms and Relay Connections This section describes two types of dry-contact connections: x Standard idRUs x idRU PS NFPA model 5.7.1 Standard idRUs External Alarm and Relay Connections The standard idDAS repeaters support up to four active high or active low external alarms and one relay. The external alarms can be used to monitor third party equipment such as air-conditioners or power supplies that are located in the communication room.
5.7.1.2 Connecting Alarms To connect the dry-contact alarms 1. Open the repeater door using the provided key – Figure 5-2 and Figure 5-3. 2. Route your alarms cable (not provided) to the inside of the repeater, via the Ext Alarms aperture located on the front panel – Figure 5-32. 3. Inside the repeater, route the cable and wiring towards the alarms connector – Figure 5-33. Open the repeater door Aperture for routing External Alarms wires Figure 5-32.
x Pin-9 and Pin-10 can be respectively used as an internal 15 Vdc power source and as a chassis ground source. x Each connected alarm must be configured via the idDAS web management according to its trigger: Active High or Active Low (Section 5.7.1.3). This step is also described as part of the commissioning procedures in the idDAS Commissioning Guide. x It takes about 10 sec to activate an alarm.
5.7.1.3 Configuring idRU External Alarms It is required to configure any external alarms connected to the idRU according to the trigger (high or low) and it is recommended to assign the alarms recognizable names (such as High Temperature, etc.). This is done via the web management GUI. The procedure is described in the idDAS Commissioning Guide as part of the setup, and provided in this section for your convenience.
5.7.2 idRU Public Safety External Alarms and Relay Connections The dry-contacts alarms pin-out and interface have been modified for idRU public safety repeater models for NFPA compliance. The public safety compliant idRUs support the following dry-contact alarms: x Two external alarms – Ext Alarm 1 and Ext Alarm 2. These are configured via the External Alarms hovermenu option. x Antenna Disconnect alarm – provides indication of the antenna connection status. This alarm does not required configuration.
5.7.2.2 Configuring the idRU External Alarms 1,2 The idRU PS NFPA External Alarms 1/2 are configured via the web management application. This is done as part of the commissioning procedure detailed in the idDAS Web Management Guide or at any other time. For convenience and quick reference, a brief description is provided below. To configure the idRU External Alarm 1 and External alarm 2 1. Log into the relevant idRU and click the External Alarms hover-menu option. 2.
5.7.2.3 idRU General Alarm Filtering The relayed alarm for a specific idRU can be filtered via the idRU Alarms Configuration hover-menu of that idRU. User selected alarms can be disabled for routing globally for all idRUs via the MSDH Alarm Configuration hover-menu or for a specific idRU via the idRU’s Alarm Configuration hover-menu (Section 4.4.4.2). To filter out idRU alarms affecting the relay 1. Log into the relevant idRU and select the Alarms Configuration hover-menu option. 2.
6 Verification And Maintenance This chapter provides the following information x Installation verification x Required Tools x Maintenance schedule x Routine inspections of the system x Periodical administrative and monitoring procedures x Replacement procedures x F/O Cleaning Procedure 6.
PROCEDURE VERIFY THE FOLLOWING: Installation status x Verify all fibre links end-to-end are installed and connected. x Verify the DAS is installed and connected to each idRU antenna port as per design. x Verify that all equipment, including racks and idRUs, are installed and powered. x Verify that all BTS systems are installed and activated. x Verify that all DAS between the BTS and top of the Rack installed and connected. x Verify there are no active alarms on the MSDH.
RF TEST EQUIPMENT AND KIT COMMENTS Spectrum Analyzer Capabilities: reads LTE control channel, channel power Signal Generator Up to 3Ghz @ 0dBm Multimeter RF components: x RF cable N-type Male to N-type Male, 1.5meters Cables x 4.
Terminology COLUMN DEFINITION LRU/SRU LRU – Line Replaceable Unit; SRU – Shop Replaceable Unit Maintenance Category IS (Inspection) CL (Cleaning) FC (Function Check) RP (Replacement) VC (Visual Check) 6.4 idDAS System Routine Inspections For optimum performance of the idDAS system, perform the following inspections on every site visit, at least once a year or more often as required by site conditions.
6.5 Periodical Procedures As part of the routine maintenance of the idDAS system, the administrator should perform the following operations: x With every configuration change, the current configuration should be backed up. x The optic level signal of the system connections should be verified. 6.5.1 Configuration Backup The administrator can back up the current configuration onto the MSDH Master or to another location. If needed, this backup file can then be used to restore the configuration.
6.5.2 Verifying MSDH Optical Levels Periodically, every six months, it is recommended to verify the optical levels of the system. For reference of the desired optical levels, it is recommended to save or record the initial optical levels (after commissioning) for reference. Every six months, the values should be compared to verify there is no deterioration of the optical levels. To verify the optical levels 1.
6.6 MSDH and MTDI Element Replacement Procedures This section describes how to replace the following elements: x MTDI RF module and MTDI chassis replacement x MSDH replacement x MTDI and MSDH fan module replacement 6.6.1 MTDI Elements Replacement NOTE: Only the MTDI RF modules can be replaced. Any other fault such as a control module or a power supply error, or would require replacing the chassis.
6.6.1.2 MTDI Unit Replacement This section provides basic information on replacing the MTDI unit. If the new unit is of exactly the same model and configuration as the previous unit, the Clone option can be used to transfer the configuration from the suspect unit to the new unit after the physical installation. (The Clone option will be referred to in the instructions). ATTENTION! Before reconnecting CPRI cables, be sure to clean the CPRI cable and SFP interfaces using standard fibre cleaning procedures.
9. In the web GUI: x If the MTDI is replaced by a unit of the same model, this is automatically identified by the system and the configuration of the replaced unit can be transferred to the new equipment using the Clone option. Section 6.9.2. x Click on the Inventory hover-menu option and verify the unit four-digit ID is displayed. Section 6.9.3. x Click the Routing Profiles hover-menu option and re-enable the relevant routing profile. Section 6.9.1. 6.6.
x Open a first time web session to the MSDH – MSDH factory set IP Address is 192.168.1.253. x From the Ethernet hover-menu screen, set the MSDH network parameters (Static IP address or DHCP). 10. Restore the previously backed up configuration according to Section 6.9.4. 6.6.3 MTDI/MSDH Fan Module Replacement The same fan module and the same procedure are used for replacing the MSDH and the MTDI fan modules. CAUTION! Be sure to disconnect power before disassembling the Fan Module.
To replace the idRU fan-hood modules 1. Note the four-digit number on the label at the side of the suspect repeater. This information will be needed when verifying connection to the repeater after completing the replacement procedure. Four-digit Unit Identification displayed in the web management application Figure 6-5. idRU Identification Label 2. Remove the following connections: x Disconnect power to the unit and disconnect the power connector.
5. Remove the FRONT fan-hood module. 6. If external alarms are connected, referring to Section 5.7.1, disconnect the external alarms as follows: x If the external alarms are connected to an external power source, disconnect the power. x Unlock and open the repeater door. x Label all externally connected wires connected to the alarms block. (These are pairs of wires routed via the External Alarms aperture on the repeater.) x Loosen the relevant screws on the alarms block and remove the wires.
9. Loosen the 4x screws securing the rear fan-hood and brackets to the repeater. Figure 6-8. Removing Rear Fan-hood and Mounting Brackets 10. Remove the rear fan-hood and brackets. 11. Clean the repeater fins using the standard telecom equipment cleaning procedure used at your installation site. 12. Referring to Section 5.4.2, assemble the NEW fan-hoods and brackets by reversing the steps: x Assemble the rear fan-hood and the brackets using the 4x supplied bolts and washers.
17. Verify the LINK-MAIN LED is green – this is the LED to the right of the MAIN CPRI interface (it may be mislabeled on some units). LINK-MAIN LED = green Figure 6-9. LINK-MAIN LED 18. In the web GUI – Click on the Inventory hover-menu option and verify the repeater four-digit ID is displayed (Section 6.9.3). 6.7.
2. Unpack the replacement idRU and set it aside on a flat clean surface. Be sure to save the packaging for transporting the suspect idRU. 3. Referring to Section 6.7.1 Step-3 to Step-10, uninstall the suspect idRU as follows: x Disconnect power. x Disconnect the antenna cable. x Label and disconnect the CPRI cables. x Remove the front fan-hood and set it aside – save bolts and washers for reuse. x Remove the Ground connector.
x If the idRU is replaced by a unit of the same model, this is automatically identified by the system and the configuration of the replaced unit can be transferred to the new equipment using the Clone option. Section 6.9.2. x Click on the Inventory hover-menu option and verify the repeater four-digit ID is displayed. Section 6.9.3. 6.7.2.2 idRU-30 Replacement This section provides basic information on the replacement procedure. For detailed information, refer to Chapter 5.
x If relevant, connect the External Alarms by opening the repeater door, routing the External Alarms cable internally and connecting the wires according to the labels. Close and secure the repeater door. x Connect power. 7. Verify the LINK-MAIN LED is green – this is the LED to the right of the MAIN CPRI interface (it may be mislabeled on some units). LINK-MAIN LED = green Figure 6-12. LINK-MAIN LED 8.
6.8.2 APOI RF Module (BTSC) Replacement To replace an APOI RF module 1. Remove the suspect RF module as follows: x Label the RF connections for that module to facilitate reconnection. x Disconnect the RF connections to the suspect module. x Using the T8 screw driver, loosen the 4x captive screws, and gently and evenly pull the suspect module out by its tab (located above the bottom screws). x Place the suspect module in the packaging of the new module.
To replace an APOI Control module 1. The ID of the suspect Control module will be required for the replacement procedure. Note the ID provided by the suspect APOI Control module by doing the following: x Open a session to the idDAS web management application. x Access the Inventory screen and note the ID of the APOI hosting the suspect Control module. Refer to Section 6.9.3 for details. 2.
x Analyzing the currently allocated internal IP Addresses, choose a NEW IP address (not currently listed) that is within the range of the MSDH IP Address. This address will be assigned to the NEW Control card. For example: If MSDH 10.0.0.1 assigned 10.0.2.1 to 10.0.0.8, then 10.0.2.9 would be available to assign to the APOI Control module. Currently allocated IP Addresses Figure 6-15. Determining an Available IP Address MSDH IP Address 6. Referring to Section 6.9.5.
6.8.4 APOI Chassis Replacement This section provides basic information on replacing the APOI chassis. Note the following: x An APOI chassis with one power supply can be transparently replaced by APOI chassis with two power supplies and vice versa. x Be sure to note the slot numbers in which all the modules are located and reinsert them in the new chassis in exactly the same order. To replace an APOI chassis 1. Unpack the replacement APOI enclosure and set it aside on a flat clean surface. 2.
6.9 Web GUI Operations The following web GUI operations may be required for some of the maintenance and replacement procedures as indicated in the procedure steps. x Disabling the routing profile x Viewing the Inventory screen x Cloning equipment x APOI configuration procedures required for maintenance 6.9.1 Disabling the Routing Profile Some of the maintenance procedures on MTDI and idRU elements require disabling the currently active routing profile.
6.9.2 Cloning Equipment If an APOI, idRU or MTDI unit is replaced by a unit of the same model and physical configuration, the configuration of the replaced unit can be transferred to the new equipment using the Clone option. After the equipment is replaced and running, the system identifies that the previous equipment has been replaced with equipment of the same model; the Cloning option then becomes available in the idDAS management application, equipment specific Information pane.
6.9.3 Inventory Screen During the replacement procedures, the Inventory screen can be used to verify that the unit has initiated properly and is identified by the system according to its four-digit unique ID. To access the Inventory screen Click the hover-menu Inventory option. The list of idDAS elements appears. Each element is displayed along with identifying information, including its unique 4-digit, or 5-digit ID. The filter options can be used to limit the display to specific elements.
2. To restore a configuration file: x If the file is not uploaded in the MSDH (i.e. listed under the relevant window area - System Backup Files and/or System Configuration files, click Upload File, browse and upload the relevant file. x In the relevant window area, select the file and click Load. This may take about 30 sec during which time a blank screen will be displayed 6.9.
x Configure the parameters in the order given in the following steps (the channel is activated last – after all parameters have been set). A-POI Config tab Click A-POI item Activate Channel (LAST operation) Port mode: Combine Gain Mode: SALC Figure 6-23. A-POI Configuration of Band Modules 4. Select the Port Mode for that conditioning module: x Combine – (recommended) both services are routed via the top simplex RF connections to the MTDI.
6.9.5.2 APOI IP Address Configuration 1. Verify your computer’s IP Address is in the same subnet as the A-POI IP Address. Default A-POI shelf IP Address = 192.168.1.253. 2. Connect the (supplied) Ethernet cable between the computer and the A-POI Control module CCD port. Ethernet Figure 6-24. Local Setup Connection 3. Open a standard browser and enter the default (provided) IP address of the A-POI: 192.168.1.253 Figure 6-25. Default IP Address 4.
5. In the Main window, Topology Tree, click A-POI and select the Communication Configuration tab (see Figure 6-27). Topology Tree Click Send Communication Configuration tab Click A-POI IP Address Configuration Figure 6-27, IP Address Configuration 6. Configure the shelf IP Address as follows: x Define the Local IP Address, Local Netmask and Local Gateway for this A-POI shelf. x Click Send. 6.9.5.
2. At the top of the screen, click on the Add APOI button. The following dialog appears. Figure 6-29. APOI IP Dialog Box 3. Enter the IP of the APOI you wish to integrate into the system and then click on Retrieve Data. The following dialog appears. The dialog provides identification information on the APOI, including the list of installed band modules according to their slots. A-POI identification and version A-POI Band Modules Figure 6-30. APOI Band Modules Details 4. Click Add-APOI.
6.9.6 APOI Configuration Backup/Restore The APOI supports backup and restore at a Cluster level, and per RF module where specific parameters are backup up at each level. To implement this functionality, a dedicated Backup and Restore tab is available at the Cluster level and for each RF module. The dialogs and available options are identical at both levels. The corresponding options are backed up to a *.CSV file. By default, the backup file is named according to the current date and time.
x SNMP related parameters configured in the Communication Configuration dialog. Figure 6-35. SNMP Related Parameters To access the cluster level backup and restore The cluster level pane is accessed by clicking the APOI Cluster item in the navigation tree and then selecting the Backup/Restore tab. Currently saved files (click link to Save As) Backup and restore options Figure 6-36.
6.9.6.2 RF Module Level Backup and Restore The RF module Backup and Restore option is used for backing up the user configurable values per channel: Channel Activation (mute), Operator Name, External Combiner, etc — it does not include, the read values. Figure 6-37. Backed Up Module Parameters To access the RF module level Backup and Restore tab The RF module Backup and Restore pane is accessed by clicking the relevant RF module in the navigation pane and then selecting the Backup/Restore tab.
The file management buttons provide the following options: ITEM DESCRIPTION Backup Click to save the currently running configuration file to the Master APOI control card. The file will be added to the list. A user defined file name can be assigned using the Remark option; otherwise, the file will be named according to the current date and time. Remark Enables assigning a user defined name to the file before it is backed up. The file name cannot be changed once it is created.
6.9.6.4 Restoring a Configuration Any configuration file listed in the Backup and Restore tab can be restored to the APOI. In order to restore a configuration file that was saved to a different location on your computer or the network, it must first be uploaded to the APOI and displayed in the list. To restore previous configuration 1. In the left pane, click the Cluster item and then click the Backup/Restore tab. 2. Verify the desired configuration file is displayed in the list.
6.10 F/O Cleaning Procedure 6.10.1 Tools TOOL DESCRIPTION ILLUSTRATION Fibrescope connected to a PC running the appropriate viewing software. It is highly recommended that some form of Fibre viewing equipment such as a Fibrescope is used to ensure that all Fibre connections are clean before termination; failure to do may downgrade system performance Lint-free swabs (box), P/N 99-000127 Lint-free wipes (pack) P/N 99-000125 Fujikura “One Click” cleaner P/N 98-900004.
6.10.2 Dry F/O Cleaning Procedure CAUTION! Invisible laser radiation might be emitted from disconnected Fibres or connectors. Do not stare into beams or view directly with optical instruments. PRUDENCE! rayonnement laser invisible peut être émis à partir de fibres ou les connecteurs débranchés. Ne pas regarder en faisceaux ou voir directement avec des instruments optiques. 1. Before cleaning the SFP connectors it is advisable to clean the connector of the mating cable being attached to the optical port.
7. Inspect the Fibre connector using a Fibrescope. On the PC monitor, verify that there is no contamination present on the connector end-face. 8. If the connector is dirty, clean it with a wet cleaning technique followed immediately by dry cleaning. This is to remove any remaining residue from the wet clean (the following steps demonstrate a wet cleaning technique). 6.10.3 Wet F/O Cleaning Procedure ATTENTION! Invisible laser radiation might be emitted from disconnected fibres or connectors.
7 Specifications The chapter provides the following information: x Supported Cellular and Public Safety frequencies x Headend units specifications x Cellular idRUs specifications x Public Safety idRUs specifications 7.1 Supported Frequencies 7.1.1 EMEA/APAC Frequencies EMEA/APAC APOI, MTDI, idRU (Cellular) Bands The frequencies listed below are supported by APOI, MTDI, and idRU1.
7.1.
7.1.3 Additional Supported Frequencies 7.1.3.1 Brazil Frequencies BRAZIL FREQUENCIES 850 MHz UPLINK 824-849 MHz DOWNLINK 869-894 MHz 1800 MHz 1710-1785 MHz 1805-1880 MHz 2100 MHz 1920-1980 MHz 2110-2170 MHz 2600 MHz 2500-2570 MHz 2620-2690 MHz UPLINK 703-748MHz DOWNLINK 758-803MHz 850MHz (*) 825-844.7 MHz 870-889.7 MHz 900 (*) 891.7- 915 MHz 936.7 - 960 MHz 1800MHz 1710 - 1785 MHz 1805 - 1880 MHz 2100MHz 1920 - 1980 MHz 2110 - 2170 MHz 7.1.3.
7.2 Headend Units Specifications 7.2.1 APOI Specifications RF PARAMETERS Frequencies See System Frequencies Gain flatness 3 dB (p-p) RF input power range +20 to +30dBm composite power per band GENERAL BTSI cards Up to 8 Sectors per BTSI card Up to 2 BTS side RF interfaces 4 QMA Connector Female (2 per sector) Simplex / Duplex connections per sector.
7.2.2 MTDI Specifications RF PARAMETERS Frequencies See System Frequencies Gain flatness 3 dB (p-p) RF input power range From APOI 0dBm composite power per band GENERAL Number of Digitization Modules 4 band-specific modules Max number of sectors per Digitization Module 4 sectors per module (via 2* A-POI band module in combined mode) RF Ports per module 4 QMA Connector Female Two simplex Tx/Rx connections.
7.2.
7.3 idRU EMEA/APAC Specifications This information below includes both cellular and public safety specification for the EMEA/APAC idDAS system.
idRU EMEA/APAC Specifications – cont… CPRI INTERFACE MEDIA TYPES Single mode fibre Multi mode fibre DISTANCE SUPPORTED BANDWIDTH 1310,1550 nm Up to 80 km Up to 220 MHz 850 nm Up to 300 m Up to 220 MHz MODULATION ACCURACY AT NOMINAL OUTPUT POWER WCDMA/EVM Typ. 3.5% RMS (composite according to ETSI TS 25.
7.4 idRU Americas Specifications This information below includes both cellular and public safety specification for the Americas idDAS system. IDRUS AMERICAS CELLULAR RF SPECIFICATIONS UPLINK (UL) DOWNLINK (DL) OPER.
MODULATION ACCURACY AT NOMINAL OUTPUT POWER WCDMA/EVM LTE/EVM PkCDE POWER CONSUMPTION Quad band MECHANICAL Dimensions Weight Enclosure ENVIRONMENTAL EMC Typ. 3.5% RMS (composite according to ETSI TS 25.106 with TM1/64 DPCH Typ. 3.5% RMS (composite according to 3GPP TS 136 106) <-33dB (ETSI TS 25.106 with TM 1/64 DPCH and spreading factor 256) MEDIUM POWER MODELS HIGH POWER MODELS max 210W 690-820W max MEDIUM POWER MODELS HIGH POWER MODELS 21.3” x 15” x 12.3” 540 x 382 x 313 mm (without fanhood) 21.
8 Ordering Information This chapter provides ordering information for the following elements x EMEA Cellular and Public Safety elements x Americas Cellular and Public Safety x Bespoke public safety solutions x SFPs and Jumpers 8.1 EMEA/APAC Ordering Information 8.1.1 EMEA/APAC Cellular 8.1.1.1 EMEA/APAC Cellular APOI P/N APOI MARKETING P/N DESCRIPTION ENG.
8.1.1.3 EMEA/APAC Cellular MSDH P/N MSDH MARKETING P/N DESCRIPTION ENG. NUMBER id-DAS-MSDH-48V DC id-DAS MSDH 48V DC feeding MSDH005 id-DAS-MSDH-AC id-DAS MSDH AC feeding MSDH006 8.1.1.4 EMEA/APAC Cellular idRUs P/Ns EMEA/ IDRU MARKETING P/N DESCRIPTION ENG.
8.2 Americas Ordering Information 8.2.1 Americas Cellular 8.2.1.1 Americas Cellular APOI P/N APOI CHASSIS AND ELEMENTS DESCRIPTION ENG.
8.2.1.4 Americas Cellular idRU P/N AMERICAS IDRUS MARKETING P/NS DESCRIPTION ENG. NO. id-DAS-idRU-M-3007-3008-3017-3019AC ID-DAS idRU Master 7/8/17/19 30dBm AC RRU0003 id-DAS-idRU-M-3007-3008-3017-3019DC ID-DAS idRU Master 7/8/17/19 30dBm DC RRU0008 id-DAS-idRU-M-4307-4308-4317-4319AC-F ID-DAS idRU Master 7/8/17/19 43dBm AC with fan hood RRU0019 8.2.2 Americas Public Safety Ordering Information 8.2.2.1 Americas PS MSDH P/N MSDH MARKETING P/NS DESCRIPTION ENG. NO.
8.3 Bespoke Ordering Information APOI CUSTOMIZED PS DESCRIPTION ENG. NUMBER APOI-CH-12V DC-CN APOI chassis 12V DC feed, including CCD POI0017 MTDI CUSTOMIZED PS DESCRIPTION ENG. NO. id-DAS-MTDI-4-CH-SM-MM-12V DC id-DAS MTDI 4 CH SM & MM SFP 12V DC MTDI070 id-DAS-RFB-380-450 id-DAS RF board for 380-450MHz RA00374 id-DAS-RFB-450-P25 id-DAS RF board for UHF 450MHz P25 RA00453 MSDH CUSTOMIZED PS DESCRIPTION ENG.
Appendix A – EU Declaration of Conformity This section provides the EU Declaration of Conformity for idRU, MSDH, and MTDI. Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.
Cobham Wireless idDAS Installation and Maintenance Guide 00109GU Rev. 2.