Instruction Manual

Table Of Contents
COPPER COMPRESSION CONNECTORS
For Technical Support: www.panduit.com/resources/install_maintain.asp
Page 1 of 4
INSTALLATION INSTRUCTIONS T-PMPI-62-PC
Panduit Corp. 2021
C
1. Use a connector marked for the wire size and wire material to be used. NEVER
use a copper connector on aluminum wire.
2. Strip wire insulation to approximate length shown on tool chart. DO NOT nick
or ring the conductor strands.
3. Clean the wire.
4. Insert stripped wire into connector until the wire stops.
5. Using installation tooling shown on other side, insert connector in die and crimp
between color bands or knurl markings. REQUIRED NUMBER OF
COMPRESSIONS SHOWN IN ( ).
6. After crimping, inspect for sharp edges, flash or burrs and remove if present.
1. Refer to Panduit catalog or www.panduit.com for heat shrink material information,
tubing size, voltage rating, and shrink temperature.
2. Cut tubing to length allowing insulation coverage as desired. Allow a minimum
of 1-1/2" inch overlap on wire insulation.
3. Shrink with a standard propane torch or heat gun. MOVING FROM CRIMPED
PORTION OF CONNECTOR TOWARD INSULATED WIRE. Adhesive flow at
ends indicate shrinkage complete.
COPPER COMPRESSION CONNECTOR INSTALLATION
HEAT SHRINK INSULATION INSTRUCTION
Rev 11