Use and Care Manual

Installation Instructions for RB-700-1 Recess Box
1) Determine the installation location.
The recess box should be installed so the discharge vent maintains the minimum
allowable clearances as required by the local authority. Where no local requirement
exists, maintain the following minimum suggested clearances from building openings
as shown in Figure 1:
4’ below, 4’ horizontally from, or
1’ above any door, operable window,
or gravity air inlet into any building.
3’ above any forced air inlet within 10’.
Follow all other installation requirements
as outlined in the Installation Manual.
Note: Top, front, and side clearances noted
on the front cover of the water heater are not
applicable when installed in a recess box.
2) Construct the framing.
Prepare an opening for the recess box to
the following approximate dimensions:
40” (height) x 14-1/2” (width) x 10-1/4” (depth)
Note: The recess box is approved
for zero clearance to combustibles.
3) Prepare the recess box.
Drill 3 holes in the recess box
to accommodate the water and
gas lines. Suggestions for the
holes are shown in Figure 2.
Additional holes for running
the electrical and remote
controller wires will be
needed as well.
3'
1'
4'
4'
Figure 2: Piping options.
Warning
This recess box has been designed to be mounted in a wall cavity. Do not attempt to mount the recess box
in another configuration (i.e. outside wall, free standing, etc.). Damages resulting from an improper installation
will not be covered by the Noritz America Limited Warranty.
Figure 1: Discharge Vent Clearances.
For Model NR98OD (GQ-2857WX US)
Note: 1. Allow for drainage
from the pressure relief valve.
2. If condensing model, also allow for
drainage from condensate drain
connection.