PRESS’O USER GUIDE
Press’o User Guide NOTICE Nke Watteco reserves the right to make changes to specifications and product descriptions or to discontinue any product or service without notice.
Press’o User Guide DOCUMENT HISTORY Date Revision Modification Description March 2016 March 2016 1.0 1.
Press’o User Guide CONTENTS 1 Introduction................................................................................................................................. 5 1.1 2 General description ............................................................................................................................................................5 Electronic ..................................................................................................................................... 6 2.
Press’o User Guide 1 INTRODUCTION This document describes the usage of the Press’o sensor. It is necessary to read the LoRaWAN Sensors Behavior on Public LoRaWAN Networks guide and the Application Layer Description guide in prerequisite for all generic information or to have more details. 1.1 G ENERAL DESCRIPTION The Press’o sensor manages two different power supplies, one is external and energizable in 9-15V the other one is internal on a disposable A 3.6V battery.
Press’o User Guide 2 ELECTRONIC To select the 4-20mA mode or the 0-10V mode, it is necessary to put the switch on the right position. 2.1 4-20 MA In the 4-20 mA mode, the V+ (power supply of the external sensor) is powered on during 120 ms at 10 V. Presso 4-20mA sensor + - 10V V+ M/Vshield [shield] V 2.2 0-10 V In the 0-10V mode, the V+ (power supply of the external sensor) is powered on during 120 ms at 14V with a max current of 50mA.
Press’o User Guide 2.3 KNOWN COMPATIBLE PRODUCT Press’o sensor is compatible with the set of product: CTE / CTU / CTW8000...CS from First Sensor.
Press’o User Guide 3 CASING Dimension: 84 * 82 * 55 mm Combustion behaviour: UL94HB All Rights Reserved – nke Watteco® Press’o Page 8 of 15 User Guide
Press’o User Guide 4 HUMAN MACHINE INTERFACE The Press’o has a buzzer that allows it to “communicate” with the end-user. The link between the sounds it makes and the sensor status can be seen in the array here below. A reed switch (or magnetic switch) is available. It is possible to use a magnet to activate it and makes specific actions on the sensor (Switch off, switch on, Re-associtation…) described in the LoRaWAN Sensors Behavior on Public LoRaWAN Networks guide.
Press’o User Guide 5 APPLICATIVE LAYER The Press’o device is a sleepy Class A device. It implements “Analog Input” clusters, associated to their Inputs.
Press’o User Guide 6 CONSUMPTION 6.1 EUROPE MODE Lifetime Simulator PHY Frame Size Tx PHY Frame Size Rx (ACK) Transmission period 75 Bytes 15 Bytes Period s Duty cycle 0.10% Battery : Theoritical capacity Actual capacity Radio Consumption: Transmission Reception 3600 mAh 3060 mAh 40 10 mA mA Measuring (Rx) Measuring Period 3600 s Measuring duration 0.12 Active measuring consumption Basic consumption (sleeping) : 50 s mA 0.
Press’o User Guide 6.2 US MODE Battery sensor: life time Estimator PHY Frame Size Tx PHY Frame Size Rx (ACK) Transmission period 75 Bytes 15 Bytes Period s Battery : Theoritical capacity Actual capacity 3600 mAh 3060 mAh Radio Consumption: Transmission Reception 40 10 mA mA Measuring (Rx) Measuring Period Measuring duration Active measuring consumption 3600 s 0.12 s 50 mA Basic consumption (sleeping) : 0.004 mA Estimated Lifetime (Years) Period(s)/SF 7 8 9 10 8 60 4.38 2.58 1.48 0.83 8.
Press’o User Guide 7 EXAMPLES In the following examples, the 6lowpan header has been removed for an easier understanding. See 6LOWPAN LAYER OVER LORAWAN™ in the LoRaWAN Sensors Behavior on Public LoRaWAN Networks guide, for more details. 7.1 C ONFIGURE A BATCH REPORT ON A NALOG INPUT, AND VOLTAGE BATTERY Specification: Timestamp and record the Voltage of a 0-10V sensor with a resolution of 0.1V, a value has to be saved at least all the 30 minutes or on a rise of 0.5V.
Press’o User Guide Result: UNCOMPRESS SERIE cnt: 5 # Counter of the batch (from 0 to 7) 263 # Timestamp in second of sending of the frame # Format of data is: TimeStamp of Measure | Label | Value 263 0 0.000000 # TimeStamp: 841 s Label 0: Analog Input Value: 0 V 263 1 3000 Label 1: Disposable Value: 3.0 V # TimeStamp: 811 s With the batch only one frame of 14 applicatives bytes is sent, instead of 2 frames representing 24 applicatives bytes.
Press’o User Guide 8 APPENDIX 8.1 PRESS’O FCC LABEL FCC ID: 2AGTV50-70-025 PRESS’O SENSOR This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference and (2) this device must accept any interference received, including interference that may cause undesired operation.