R2 R1 Q2 Q1 F2 F1 N W V A1 A2 V AC S UF R150 SL UF 50 Hz 60 Hz R150 AVR Installation and maintenance
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR This manual concerns the alternator AVR which you have just purchased. We wish to draw your attention to the contents of this maintenance manual. SAFETY MEASURES Before using your machine for the first time, it is important to read the whole of this installation and maintenance manual. All necessary operations and interventions on this machine must be performed by a qualified technician.
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR CONTENTS 1 - GENERAL DESCRIPTION .................................................................................................4 2 - OPERATION OF THE AVR .................................................................................................4 3 - TECHNICAL SPECIFICATION ...........................................................................................5 4 - MAIN FUNCTION OF THE AVR ................
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR 1 - GENERAL DESCRIPTION The R150 automatic voltage regulator (AVR) is a compact, high-performance encapsulated unit. It incorporates the latest technology and efficient components to achieve a high degree of miniaturisation when applied to a 3-phase and 1-phase AC brushless generator, within its input and output limits. The unit offers excellent reliability.
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR 3 - TECHNICAL SPECIFICATION 1) Sensing input - Voltage: 240 VAC ± 10% for 1-phase, 380 V to 480 VAC ± 10% for 3-phase, 2-line sensing. The AVR senses the true average of the line-to-line waveform. Use the resistor (SMD) network for trouble-free sensing and control of sensed voltage/regulation.
Installation and maintenance Electric Power Generation 5384 en - 2022.02 / j R150 AVR 4 - MAIN FUNCTION OF THE AVR The AVR is powered by the line-to-neutral terminals of the AC generator with 240 VAC at 50/60 Hz. The regulated sensing voltage is based on the generator line-to-line terminals. STATOR: 6 wires (T1 to T6 identification) MAIN FIELD Varistor EXCITER Armature + Exciter field T1 U1 T2 V1 T3 W1 T4 U2 T5 V2 T6 W2 Delta configuration 8 S2 P2 TI04 7 blue 2K/2.
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR 5 - AVR SETTINGS 5.1 - V-TRIM (V) 5.3 - STAB (S) This function is provided for setting the voltage up to ± 12% of rated voltage by means of a potentiometer. Turn the potentiometer clockwise to increase the voltage and vice versa, once the rated speed has been reached. It is also possible to connect an external potentiometer. 5.
Installation and maintenance Electric Power Generation 5384 en - 2022.02 / j R150 AVR 7 - TROUBLESHOOTING CHART Symptom No voltage build-up High voltage build-up Low voltage build-up Cause Fuse blown Action Check and replace Low residual voltage across U If the generator’s residual voltage at rated speed and N terminals is less than 2.5 VAC (L-N), disconnect the AVR and connect a 24 VDC battery, keeping F1 as positive and F2 as negative.
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR 8 - MULTIMETER CHECKS Equipment: Digital multimeter. Select Diode mode on the digital multimeter. The resistance between F1 and F2 (with the multimeter jack common applied to F1 of the AVR) should be between 0.4 and 0.6 V, and vice versa (with the multimeter jack common applied to F2 of the AVR) should give INFINITY.
Installation and maintenance Electric Power Generation 5384 en - 2022.02 / j R150 AVR 9 - STATIC TEST PROCEDURE For 3-phase circuit AVR (3PH) Model: R150 F2 F1 N W V LAMP 100 W 230 V F1 R F2 Y F3 B 415 V, 3PH, 50 Hz, WITH NEUTRAL VAC 0-500 V N VARIAC 8 A, 415 V STATIC TEST CONNECTION DIAGRAM OF 3PH AVR This test should only be attempted after making sure that the AVR has passed all multimeter checks.
Electric Power Generation Installation and maintenance 5384 en - 2022.
Electric Power Generation Installation and maintenance R150 AVR 11 - SPARE PARTS 11.1 - Designation Description Type Code AVR R150 5014127 11.2 - Technical support service Our technical support service will be pleased to provide any additional information you may require. For all spare parts orders or technical support requests, send your request to service.epg@leroy-somer.com or your nearest contact, whom you will find at www.lrsm.co/support indicating the type and the code number of the AVR.
Electric Power Generation Installation and maintenance 5384 en - 2022.02 / j R150 AVR Disposal and recycling instructions We are committed limiting the environmental impact of our activity. We continuously monitor our production processes, material sourcing and products design to improve recyclability and minimise our environmental footprint. These instructions are for information purposes only. It is the user’s responsibility to comply with local legislation regarding product disposal and recycling.
Electric Power Generation Installation and maintenance R150 AVR 14 5384 en - 2022.
Service & Support Our worldwide service network of over 80 facilities is at your service. This local presence is our guarantee for fast and efficient repair, support and maintenance services. Trust your alternator maintenance and support to electric power generation experts. Our field personnel are 100% qualified and fully trained to operate in all environments and on all machine types. We have a deep understanding of alternator operation, providing the best value service to optimise your cost of ownership.
www.leroy-somer.com/epg Linkedin.com/company/leroy-somer Twitter.com/Leroy_Somer_en Facebook.com/LeroySomer.Nidec.en YouTube.com/LeroySomerOfficiel 5384 en - 2022.