PREVENTIVE MAINTENANCE ROI-S05751 Chart 4-2 (Cont’d) Step 9 Procedure Click on “RMON(Line)(7days/day)” sub-menu button in “PMON (History)”, ---RMON(Line)(1day)--- Maintenance Mode: on Port1 Date Time Status 1 2 3 4 5 6 1: 2: 3: 4: 5: 6: 7: 8: 9: 10: 11: 12: 13: 14: 15: 16: 17: 18: 19: 20: 21: 22: RX UNICAST RX BROADCAST RX MULTICAST RX PAUSE RX CEC ERR RX ALIGNMENT ERR RX SYMBOL ERR RX UNDERSIZE RX FRAGMENTS RX 64 RX 65-127 RX 128-255 RX 256-511 RX 512-1023 RX 1024-1536 RX 1537-MAX RX JABBE
ROI-S05751 CORRECTIVE MAINTENANCE 5. CORRECTIVE MAINTENANCE Corrective maintenance done in the field is described in this chapter. Corrective maintenance in the field covers fault isolation, module/unit replacement and alignment. The fault location procedures describes how to isolate module-level/unit-level faults. Faults can be classified into those that cause deterioration of the transmission quality and those that interrupt the traffic due to a malfunction of the equipment.
CORRECTIVE MAINTENANCE ROI-S05751 5.1.1 Alarm and Status The alarm and status of each module and ODU are displayed. Each items is explained below. ODU TX Power: Indicates the status of the transmitter in the ODU. When the transmission level is decreased 3 dB or more from preset ATPC minimum level, “Alarm” is issued. TX Input: Indicates the status of the ODU input signal from IDU. When the input signal from the IDU is lost, “Alarm” is issued.
CORRECTIVE MAINTENANCE ROI-S05751 MODEM Unequipped: Module: Indicates the status of the MODEM existence. When the MODEM is loose contact or it is not mounted according to the “Equipment Setup”, “Alarm” is issued. Indicates the status of the modulator-demodulator. When a failure occurred in the modulatordemodulator and as a result of a LSI failure, “Alarm” is issued. LOF: Indicates the frame synchronization status.
CORRECTIVE MAINTENANCE ROI-S05751 Input Voltage: Indicates the power supply input voltage status. When power supply is exceeding the limited, “Alarm” is issued. Power Supply: Indicates the operating status of the power supply. When power supply is abnormal, “Alarm” is issued. IF Cable Short: Indicates the status of IF cable between IDU and ODU. When a short circuit is caused between ODU and the IDU, “Alarm” is issued. Cable EQL: Indicates the status of IF cable equalizer.
CORRECTIVE MAINTENANCE ROI-S05751 ATPC Power Mode: Indicates the status of ATPC operation mode. When the ATPC function is improper, stop the control and maintain the TX output level at HOLD/MAX/MIN selectable. INTFC (Main/Sub) INTFC(1/2) Module: Indicates the operating status of the ( ) INTFC. When any failure occurs in the INTFC(1/2) Module, “Alarm” is issued. INTFC(1) Unequipped: Indicates the existence status of the ( ) INTFC. When the ( ) INTFC(1) is not equipped, “Alarm” is issued.
CORRECTIVE MAINTENANCE ROI-S05751 Indicates the input signal status of the OC-3 from MUX. When the signal deteriorates below the preset threshold level, “Alarm” is issued. The settable threshold values are 1E-6, 1E-7, 1E-8 and 1E-9. OC-3(1) LOS (DMR) (for SONET): Indicates the signal status of the OC-3 from DMR. When the input is disconnected, “Alarm” is issued.
CORRECTIVE MAINTENANCE ROI-S05751 OC-3(1) LOF (DMR) (for SONET): Indicates the status of the input OC-3 signal from DMR. When the input signal is out of synchronization, “Alarm” is issued. OC-3(1) E-BER (DMR) (for SONET): Indicates Excessive-BER of the input OC-3 signal at the Radio side. When the signal deteriorates below the preset threshold level, “Alarm” is issued. The setable threshold values are 1E-3, 1E4 and 1E-5. OC-3(1) SD (DMR) (for SONET): Indicates the input signal status of the OC-3 from DMR.
CORRECTIVE MAINTENANCE ROI-S05751 is issued. MMC: Indicates the MMC status. When the mounted MMC is detected, “On” is displayed. APS SW Fail (for APS in SONET): Indicates the APS status of the APS system. When the APS switchover failure occurs, “Alarm” is issued. APS Online Status (for APS in SONET): Indicates online channel on the APS system. XCTRL (for XPIC in SONET): Indicates the status of control signal between Main Master IDU and Sub Master IDU.
CORRECTIVE MAINTENANCE ROI-S05751 5.1.2 Control Item Control items can be selected only under maintenance mode. As this “Control” is likely to cause disconnection of signal, take care during operation. Details of “Control” item is described as follows: TXSW manual control: Controls manual switchover of the TX SW at the transmitting side in the Hot standby (HS) configuration. RXSW manual control: Controls manual switchover of the RX SW in the 1+1 configuration.
CORRECTIVE MAINTENANCE ROI-S05751 Since the control is not interlocked with the RX SW, the RX SW control is needed to select CH which it is IF looped back in 1+1 configuration. Main Loopback (NEAR END) (for SONET)/ Main Loopback (NEAR END) INTFC (1) or (2) (for SONET APS)/: Used for distinguish equipment failure to MUX equipment or radio equipment. The input signal from MUX is looped back to the MUX.
CORRECTIVE MAINTENANCE ROI-S05751 2. The DADE adjustment is needed in initial lineup or when the IF CABLE is replaced. It is not needed readjustment when the INTFC status is indicated Inphase. LAN Device Reset (for LAN transmission only): Used for reset control to LAN interface Port 1 or Port 2. Linearizer Control: Sets Auto/Forced Reset of linearizer function. Forced Reset: When the linearizer function is not used. Auto: When the linearizer function is used.
CORRECTIVE MAINTENANCE ROI-S05751 5.1.3 Loopback When loopback condition is necessary, set the system to loopback condition. (see Chart 5-1) When there is an interruption of signals, use the STM/SONET/PDH analyzers and isolate the faulty section by checking the traffic signal by loopback. Setup the test equipment according to the following diagrams for PDH or SONET configuration.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-1 Loopback Control Step Procedure For the LCT operation, refer to Chapter 6 of LCT Operation in Appendix of this Section IV. This chart contains: A. Preparation B. IF Loopback Control C. Main Loopback (Near End) Control (SONET) D. Main Loopback (Far End) Control (SONET) If loopback operation is performed, timing loop may occur (timing loop is described in ITU-T Recommendation G.781).
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-1 (Cont’d) Step 4 Procedure Click on the “Maintenance” button in “LCT MENU”, LCT MENU Alarm/Status Equipment Setup Inventory AUX I/O Maintenance Provisioning Metering PMON(History) Maintenance1 Maintenance2 5 Click on the “Maintenance1” menu, 6 Click on the control button “On” and click “Set” button, to set to Maintenance On mode, 7 For 1+1 configuration, switchover the TX SW and RX SW for the channel is to be set loopback, (Refer to Chart 2.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-1 (Cont’d) Step Procedure For OC-3 (E) 13 Click on the setting button “On” and click on the “Set” button, ---Maintenance1--Item Maintenance Value On Main Loopback (Near End) Main Loopback (Far End) On Off Setting Off Off Off On On On Set Set Set 5-15
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-1 (Cont’d) Step Procedure For OC-3 (O) (APS) 14 Click on the “Main Loopback (Near End)” button in “Maintenance1” menu, click on the setting button “INTFC ( )” and click on the “Set” button, ---Maintenance1--Item Maintenance Value On Main Loopback (Near End) INTFC (1) Main Loopback (Near End) INTFC (2) Main Loopback (Far End) On Off Off 5-16 Setting Off Off Off Off On On On On Set Set Set Set 15 Click on the Alarm/Status on LCT MENU to check the status
CORRECTIVE MAINTENANCE ROI-S05751 5.1.4 BER Measurement Chart 5-2 BER Measurement Apparatus: Digital Multimeter with test leads Screwdriver SONET/SONET Analyzer (for SONET) Optical Variable Attenuator (for OC-3 Optical Interface only) Headset Step Procedure A. 4P LAN INTERFACE Note: The BER measurement can not be performed for the channel which is set to Not Used or the channels shared with LAN.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-2 (Cont’d) Step 1 Procedure At both transmitting and receiving ends, set the BER test set as follows: Note: Operation of the TX SW and RX SW are not required in 1+0 system for the following. 2 In HS system, set the TX SW to No.1 or No.2 to “On” condition at transmitting end (refer to Chart 2-3), 3 At receiving end, set the RX SW to either No.1 or No.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-2 (Cont’d) Step Procedure B. OPTICAL INTERFACE Caution: To avoid damage to your eyes, do not stare into laser beam or view directly with optical instruments. (Class 1 Laser Product). 1 At the transmitting end, disconnect OPT cable from the STM1 IN connector on the OC-3 INTFC (see Fig.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-2 (Cont’d) Step Procedure OC-3 INTFC(OPTICAL) • Bit rate • Code format • Level IN OUT : 155.52 Mbps : OC-3, NRZ S-1.1 : −8 to −28 dBm/ L-1.1 −10 to −34 dBm : −8 to −15 dBm/ 0 to −8 dBm • Wave length IN : 1310 nm OUT : 1310 nm Note: Operation of the TX SW and RX SW are not required in 1+0 system. 4 In HS system, set the TX SW to No.1 or No.2 to On condition at transmitting end, (refer to Chart 2-3) 5 At receiving end, set the RX SW to either No.1 or No.
CORRECTIVE MAINTENANCE ROI-S05751 5.1.5 Trouble Shooting Flow When alarm condition occurs, red alarm LEDs on the IDU are lit except when there is a power supply failure. Faults can be distinguished using the LED indicators on the front panel of the IDU. Connect the LCT to the equipment and check the equipment conditions in according with the flow chart are shown in Fig. 5-3 to Fig. 5-5.
CORRECTIVE MAINTENANCE ROI-S05751 Is ODU ALM indicator (red) on the IDU lighted? YES Is IDU ALM indicator (red) lighted? NO Connect the LCT to the IDU and check ALARM STATUS menu. Check every items whether indicated status is Alarm or Normal. YES Are both IDU and ODU ALM indicators (red) flashing? NO Is RX Level indicated Normal? YES Check the IF cable connection and connectors whether the cable is open or short circuit. YES Check the ODU TX section.
CORRECTIVE MAINTENANCE ROI-S05751 Is IDU ALM indicator (red) on the IDU lighted? YES Is ODU ALM indicator (red) on the IDU lighted? Connect the LCT to the IDU and check ALARM STATUS menu. Check every items whether indicated status is Alarm or Normal. NO YES Is PWR LED on the MODEM lit? YES NO Replace Fuse in the MODEM.
CORRECTIVE MAINTENANCE ROI-S05751 5.2 Replacement The replacement procedures of the IDU and ODU is described below. 5.2.1 ODU Replacement The procedures for replacing the ODU with a spare are given in the Chart 5-3. The label attached to the side of ODU indicates the ODU type (see Fig 5-6). To replace the ODU, prepare another ODU of the same type as indicated on the label of the failed one. Check the name plate of the spare ODU. When the indicated items are coincided, the ODU can be replaced.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-3 ODU Replacement Apparatus: T type hexagonal driver Step Procedure REMOVING 1 For 1+1 configuration, switchover the TX SW and RX SW for the standby channel is to be replaced, 2 Turn off the power switch on the MODEM which is connected to the ODU is to be replaced, 3 Remove the self-bonding tape from the IF IN/OUT connector, 4 Disconnect the IF cable from the IF IN/OUT connector on the ODU, 5 Disconnect ground cable from the FG terminal on the ODU, 6
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-3 (Cont’d) Step Procedure MOUNTING 8 When the ODU is used for vertical polarization, rotate the ODU so that the plate marked V is on top, Note: Remove the protection metallic plate covering the waveguide hole on ODU.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-3 (Cont’d) Step 12 Procedure Fit the spare ODU onto the bracket, Note: Be careful not to damage the flange and O-ring. 13 Mount the spare ODU onto the bracket and tighten the four screws on the ODU, 14 Reconnect the IF cable to the IF IN/OUT connector on the ODU, 15 Wrap twice the IF IN/OUT connector with self-bonding tape for waterproofing. (see Fig.
CORRECTIVE MAINTENANCE ROI-S05751 ANT POLE (*) ANT POLE HYB ODU ODU (*) 6-8 GHz BAND ODU Wrap twice the IF IN/OUT connector with self-bonding tape for waterproofing. 6-8 GHz BAND self-bonding tape stretch Note: * These parts should be wrapped by self-bonding tape for waterproof. ODU twice Fig.
CORRECTIVE MAINTENANCE ROI-S05751 Wrap twice the IF IN/OUT connector with self-bonding tape for waterproofing. self-bonding tape stretch ODU a half of tape width twice CONNECTOR This part should be wrapped by self-bonding tape for waterproof. ODU SELF-BONDING TAPE IF CABLE ODU ODU SELF-BONDING TAPE IN CASE OF L−ANGLE IF CABLE Note: The self-bonding tape should be prepared by customer. Fig.
CORRECTIVE MAINTENANCE ROI-S05751 5.2.2 IDU and Module Replacement The procedures for replacing IDU/module with a spare are given in the Chart 5-4. Chart 5-4 IDU and Module Replacement Caution: Persons performing maintenance must take necessary steps to avoid electro-static discharge which may damage the modules or cause error. Wear a conductive wrist strap connected to the grounded (G) jack on the front of the equipment shelf. This will minimize static build-up during maintenance. (see Fig.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Removing MODEM 3 When the MODEM will be replaced, turn off the power switch on the corresponding MODEM which is to be replaced, 4 Disconnect cables as following order, (1) Disconnect power supply cable from SELV connector. (2) Disconnect IF cable from IF IN/OUT connector. The adapter is reused. (3) Disconnect ground cable from the ground terminal. 5 Loosen two screws on the MODEM module, (See Fig.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Replacement of the OC-3 (Optical) INTFC in APS Caution: Do not stare at the laser beam or look at it directly with optical instruments. Otherwise, it may hurt your eyes (Class 1 Laser Product) For the OC-3 (OPTICAL) INTFC replacement in APS configuration, the OC-3 (OPTICAL) INTFC can be replaced without power OFF and not affect traffic when doing replacement as following order.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure 7 Loosen two screws on the OC-3 (OPTICAL) INTFC module is to be replaced, (See Fig. 5-11) 8 Extract the OC-3 (OPTICAL) INTFC module from the IDU shelf, Note: Be careful not catch the module on the cable when extracting the module. If the module caught on the live cables, it may be caused radio link error.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure System Upgrade for APS of OC-3 (OPTICAL) INTFC Caution: To avoid eye damage, do not stare at the laser beam or look at it directly with optical instruments. (Class 1 Laser Product) For the change of OC-3 (OPTICAL) INTFC system to the APS system, perform system setup without power OFF and not affect traffic when doing replacement as following order.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure 6 Click on the Provisioning button on “LCT MENU”, 7 Click on the “Forced” control button of the APS Maintenance Mode item, ----Condition for APS--APS Maintenance Mode Manual Forced 8 Click on the “SET” button in Common area, then “OK” is displayed in Progress area when the setup is properly executed, 9 In the Maintenance1 menu, Click on the “Working” button of the APS Manual Control and Click on the “Set” button, then, value t
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure System Change from e/w APS to w/o APS of OC-3 (OPTICAL) INTFC Caution: Do not stare at the laser beam or look at it directly with optical instruments. Otherwise, it may hurt your eyes (Class 1 Laser Product). For the change of OC-3 (OPTICAL) INTFC system of the APS system to without APS system, perform system setup without power OFF and not affect traffic when doing system change as following order.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure 7 Click on the “SET” button in Common area, then “OK” is displayed in Progress area when the setup is properly executed, 8 Perform step 8 to step 11 when it is needed, ---Equipment Setup--User Interface SONET OC-3 Redundancy Setting 1+1(Hot Standby TERM) INTFC (Main) OC-3(OPTICAL) INTFC (Prot) Not Used XPIC Usage APS Function Not Used Used(Main Master) Available Modulation Scheme Unavailable 128QAM Transmission Capacity
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Removing OC-3 INTFC, GbE INTFC, CTRL 1 Referring to Chart 2-1, set the IDU to maintenance ON condition by LCT, Note: When the CTRL is a failure, replace it with a spare as explained below. Note: When the CTRL is replaced without power OFF, refer to the “Replacing the CTRL Used MMC or LCT”.
CORRECTIVE MAINTENANCE ROI-S05751 1+0 SYSTEM IDU SCREW SCREW MODEM ! IF IN/OUT XPIC CTRL XPIC CTRL TX RX XPIC RESET Gb E INTFC PWR ODU MD/ CBL SELV G PULL G PULL PWR (Blank Cover) OC-3 IN OC-3 OUT G G XIF IN XIF OUT TX RX XPIC RESET ! IF IN/OUT XIF IN XIF OUT PWR ODU MD/ CBL SELV PWR NMS NE AUX/ALM EOW CALL MMC MAINT MEMORY IDU SCREW 1+1 SYSTEM IDU MODEM No.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Mounting OC-3 (OPTICAL) INTFC w/o APS For the OC-3 (OPTICAL) INTFC mounting without APS, install the module as following order, 1 Referring to Chart 2-1, set the IDU to maintenance ON condition by LCT, ---Maintenance1--Item Maintenance Value On Setting Off On Set 2 Turn OFF the power switch on the MODEM, 3 Align the OC-3 (OPTICAL) INTFC to the shelf, then push it in until the multipin connector firmly fits, 4 Tighten the two
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Mounting GbE (OPTICAL) INTFC For the GbE (OPTICAL) INTFC mounting, install the module as following order, 1 Referring to Chart 2-1, set the IDU to maintenance ON condition by LCT, ---Maintenance1--Item Maintenance Value On Setting Off On Set 2 Turn OFF the power switch on the MODEM, 3 Align the GbE (OPTICAL) INTFC to the shelf, then push it in until the multipin connector firmly fits, 4 Tighten the two screws on the module,
CORRECTIVE MAINTENANCE ROI-S05751 Step Procedure OC-3/GbE INTFC, CTRL 1 Referring to Chart 2-1, set the IDU to maintenance ON condition by LCT, ---Maintenance1--Item Maintenance Value On Setting Off On Set 2 Turn OFF the power switch on the MODEM, 3 Check that the switch on the MODEM (both MODEM for 1+1 configuration) is off position, 4 Align the module to the IDU shelf, then push it in until the multipin connector firmly fits, 5 Tighten two screws on the module, 6 Connect all cables to
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Replacing the CTRL Using the MMC or LCT. This procedure explains how to replace the CTRL using the MMC or LCT. This procedure is applied when the CTRL is not failed, or when the equipment configuration data are saved into the MMC or LCT/PNMx. Note: If the NMS parameters (Network Config.) can not be restored, then the resetup with the PNMx is required.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure 6 When the MAINT LED blinks, insert the MMC into the MMC slot on the CTRL front, which has equipment configuration data used in the former CTRL, 7 The download of the equipment configuration data start, the deployment is performed. When the CTRL has been made provision, MAINT LED on the IDU turns to light. Check that the MAINT LED lights and set the PROTECT SW to OFF position (for lower side).
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Note: If the NMS parameters (Network Config.) can not be restored, then the resetup with the PNMx is required. The Use of the LCT for the CTRL Replacement When the LCT is used, the replacement can be performed without the MMC. (The resetup with the PNMx for the Network Config. is necessary.) 1 Referring to Chart 2-1, set the IDU to Maintenance ON condition by LCT (Check that the MAINT LED lights.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step 5 Procedure Remove the cables connected to the CTRL, loosen two fixed screws and remove the CTRL, Note: Be careful to avoid catching the module on the cable when extracting the module. If the module is caught on the live cables, it may cause a radio link error. 5-46 6 Prepare the spare CTRL. Set the PROTECT SW on the spare CTRL to ON position (for upper side), (The PROTECT SW setting distinguish the normal start up or protected start up.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure Replacing the DC-DC CONV (Optional). When the power is supplied to the SELV of the DC-DC CONV (optional) but the PWR LED of the DC-DC CONV is not lit though the power switch is on, before replacing the DC-DC CONV, check the conduction of the fuse in the DC-DC CONV.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step 5-48 Procedure 11 Turn on the power switch on the DC-DC CONV, 12 Check that PWR LED on the DC-DC CONV is on, 13 Turn on the power switch on the MODEM, 14 Check that PWR LED on the MODEM is on, 15 Check that ALM LED on the IDU is unlited, 16 Set the IDU to maintenance OFF condition by LCT.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step Procedure B. IDU REPLACEMENT REMOVING 1 Turn off the power switch on the MODEM (both MODEM in 1+1 configuration), 2 Disconnect the IF cable, signal cables and the power cable, etc. as following order, (1) Disconnect XPIC CTRL cables from opposite IDU. (XPIC configuration only.) (2) Disconnect XIF coaxial cables from opposite IDU. (XPIC configuration only.) (3) Disconnect OC-3, LAN, Aux. signal cables from connector.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-4 (Cont’d) Step 7 Procedure Form the wiring, and fix the cables using cable binder to the mounting rack, Notes: 1. Do not cross the cables on front of indicators and power switch used for maintenance. 2. Take suitable radius to wiring the IF cable. (e.g. 10DFB: 70 cm) 8 Turn on the power switch on the IDU. Hot Surface SCREW Note: Weight 4 kg. Caution: The top surface of the IDU above MODEM is hot in operation. Fig.
CORRECTIVE MAINTENANCE ROI-S05751 5.2.3 Fuse Replacement When the power is supplied to the SELV but the IDU can not be powered on with the power switch, check the conduction of fuse in the MODEM. Chart 5-5 Fuse Replacement Step Procedure 1 Set the power switch on the MODEM which is not powered to Off position, 2 Disconnect cables connected to the MODEM as following order, (1) Disconnect power supply cable from SELV connector. (2) Disconnect IF cable from IF IN/OUT connector. The adapter is reused.
CORRECTIVE MAINTENANCE ROI-S05751 (MODEM) (Front) RESERVE Reserve Fuse (6.3A) 21606.3 Fuse RKS-F91000-0107 Fuse Cap Fig.
CORRECTIVE MAINTENANCE ROI-S05751 When the power is supplied to the SELV of the DC-DC CONV (optional) but the PWR LED of the DC-DC CONV is not lit though the power switch is on, check the conduction of the fuse in the DC-DC CONV.
CORRECTIVE MAINTENANCE ROI-S05751 Chart 5-6 (Cont’d) Step Procedure 16 Tighten two screws on the DC-DC CONV, 17 Connect cables to the DC-DC CONV as reversed order in step 2, 18 Turn on the power switch on the DC-DC CONV, 19 Check that power is on. 20 Turn on the power switch on the IDU/DC-DC CONV UNIT, 21 Check that power is on. RESERVE RESERVE (DC-DC CONV) Reserved Fuse Reserve Fuse (8A) GAB250V8 Fuse CBE-006255-001 ! CAUTION HOT SURFACE Avoid contact.
CONTENTS ROI-S05749-05FE August, 2007 NEC NLite E 6-38 GHz SONET DIGITAL RADIO SYSTEM Section II OPERATION CONTENTS TITLE PAGE 1 GENERAL •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 1-1 2 OPERATING EQUIPMENT ••••••••••••••••••••••••••••••••••••••••• 2-1 2.1 IDU Shelf •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 2-4 2.2 CTRL ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 2-5 2.
CONTENTS ROI-S05749 TITLE CL-2 2 pages PAGE 3.5.9 Functionality Classification ••••••••••••••••••••••••••••••••• 3-32 3.6 Protection Switching •••••••••••••••••••••••••••••••••••••••••• 3-33 3.6.1 1 + 1 Twin-path System ••••••••••••••••••••••••••••••••••••••• 3-33 3.6.2 Hot-standby System ••••••••••••••••••••••••••••••••••••••••••• 3-33 3.6.
ROI-S05749-05FE August, 2007 CONTENTS CL-3
GENERAL ROI-S05749 1. GENERAL This section provides instructions for operation of the 6 to 38 GHz SONET microwave radio system. This section describes interface terminals and jacks, controls, indicators, and test jacks. Use of the LCT is required for local operation, monitoring, control and setup. For details of system and provisioning setup, refer to Section IV NLite E LCT Manual.
GENERAL ROI-S05749 NEC NLite E MODEM(1) INTFC (1) MDP-150MB-1AA INDOOR UNIT INTFC (2) 0678 (H2930) DATE SER. No. , WEIGHT: 4 kg (WITH OPTION) CTRL MODEM(2) −48 V 2.
ROI-S05749 OPERATING EQUIPMENT 2. OPERATING EQUIPMENT The indicators, switches, interface terminals and jacks for wiring with the associated equipment are described here. The IDU component modules listed in Table 2-1 are plugged-in from front of the IDU shelf as shown in Fig. 2-1. The component modules of the ODU shown in Fig. 2-2 are listed in Table 2-2.
OPERATING EQUIPMENT ROI-S05749 1 ! IF IN/OUT XIF IN XIF OUT XPIC CTRL TX RX XPIC RESET G PWR ODU MD/ CBL SELV 4, or 5 PULL 5* PWR G G 2 PROTECT LCT NMS NE AUX/ALM 1 EOW CALL PASOLINK NEO MMC MAINT MEMORY IDU 6 ! IF IN/OUT XIF IN XIF OUT SC IN/OUT XPIC CTRL TX RX XPIC RESET PWR ODU MD/ CBL SELV G 3 PULL PWR G G 2 PROTECT LCT NMS NE AUX/ALM SC IN/OUT EOW CALL PASOLINK NEO MMC MAINT MEMORY IDU 6 Table 2-1 IDU COMPOSITION H2930 MDP-150MB-1AA No.
ROI-S05749 NLite E RX LEV MON IFL FG 6 - 38 GHz ODU Table 2-2 ODU COMPOSITION TRP-( )G-1B 6 GHz 7 GHz) 8 GHz 10 GHz 11 GHz 18 GHz 23 GHz 26 GHz 38 GHz NWANWANWANWANWANWANWANWANWA009024( ) 009026( ) 009028( ) 009030( ) 009032( ) 009038( ) 009040( ) 009042( ) 009048( ) 1 RF CKT H2202( ) H2203( ) H2204( ) H2225( ) H2205( ) 2 IF CKT — 3 — PS H2229( ) Note: Component modules are enclosed in the ODU case. 2-3 Fig.
OPERATING EQUIPMENT ROI-S05749 2.1 IDU Shelf G G G G Jack (IDU) G Electrostatic Discharge (ESD) jack used to connect wrist strap band. * Caution*:Engineers for maintenance of the equipment must take the necessary steps to avoid bit errors or cause damage to the modules due to electrostatic discharge. Wear a conductive wrist strap connected to the ground jack (G) on the front of the IDU to minimize static build-up during maintenance.
OPERATING EQUIPMENT ROI-S05749 2.2 CTRL CALL PROTECT NE NMS LCT PASOLINK NEO PROTECT LCT NMS NE AUX/ALM AUX/ALM SC IN/OUT SC IN/OUT EOW EOW MMC CALL MMC MAINT MEMORY IDU MAINT(amber) MEMORY(amber) IDU(red) The CTRL generates various control signals based upon LCT setup data and gathered operating status in the IDU and from the ODU, has SC, EOW, LAN, NE, EXT ALM, HK, Cluster ALM signals interface.
OPERATING EQUIPMENT ROI-S05749 Interface Signals (CTRL) SC IN/OUT (D-Sub Female 44 pins) Input/Output Signal NE2: Network Element Level: RS-485 DSC (RS-232C): 2 CH Bit rate: 9600 bps Level: RS-232C DSC (V.11): 2 CH Bit rate: 64 Kbps Level: V.
OPERATING EQUIPMENT ROI-S05749 Switch (CTRL) Switch Operating CALL Transmits EOW calling signal to sound the buzzer in the opposite station. PROTECT Prevent service interruption when the CTRL module is replaced. Remarks Accessing the Memory Card (MMC) is required to apply the function.
OPERATING EQUIPMENT ROI-S05749 User Interface Pin Assignment (CTRL) Terminal Description Pins 22 (COM), 37 (NC) and 8 (NO) ⎯ RL4 ODU CPU1/ODU CPU2/Cable Open alarm output*2 Between Between Pins 22 and 37 Pins 22 and 8 Normal state : Closed Open Alarm/Event state : Open Closed Pins 21 (COM), 36 (NC) and 7 (NO) ⎯ RL5 IDU total alarm output*2 Between Pins 21 and 36 Closed Open Between Pins 21 and 7 Open Closed Pins 20 (COM), 35 (NC) and 6 (NO) ⎯ RL6 High BER1/High BER2 alarm output*2 Between Pins 20
OPERATING EQUIPMENT ROI-S05749 User Interface Pin Assignment (CTRL) Terminal Description CTRL SC IN/OUT (D-sub Female, 44 Pins) NE2/DSC Service channel data input/output Pins 1 (+) and 2 (–) NE2 TXD Pin 3 Ground Pins 4 (+) and 5 (–) V.11-1 TX data input Pins 6 (+) and 7 (–) V.11-1 RX data output Pins 8 (+) and 9 (–) V.11-2 TX data input Pins 10 (+) and 11 (–) V.
OPERATING EQUIPMENT ROI-S05749 User Interface Pin Assignment (CTRL) Terminal LCT (USB connector type B) Description Local craft terminal (LCT) data input/output Pin 1 Vbus Pins 2 (–) and 3 (+) D Pin 4 Ground NMS (RJ-45) PNMS data (10Base-T) input/output Pins 1 (+) and 2 (–) NMS TXD Pins 3 (+) and 6 (–) NMS RXD Pins 4, 5, 7 and 8 Not Connected NE (RJ-45) NE data (10Base-T) input/output Pins 1 (+) and 2 (–) NMS TXD Pins 3 (+) and 6 (–) NMS RXD Pins 4, 5, 7 and 8 Not Connected Notes:
OPERATING EQUIPMENT ROI-S05749 EOW Connection When EOW signal is connected between two IDUs, perform wiring as follows. Terminal Station A EOW 4W S EOW 4W R Buzzer IN Call OUT Back -to- Back Station B 1 2 3 4 1 2 3 4 16 17 18 19 16 17 18 19 30 31 32 33 30 31 32 33 IDU Dir. B ALM/AUX IN/OUT (D-Sub, 44 Pins) EOW 4W S 1 2 3 4 EOW 4W R 16 17 18 19 Buzzer IN Call OUT IDU Dir. A ALM/AUX IN/OUT (D-Sub, 44 Pins) EOW Extension 30 31 32 33 IDU Dir.
OPERATING EQUIPMENT ROI-S05749 2.3 MODEM G TX (green) RX (green) XPIC RESET(amber) IF IN/OUT ! IF IN/OUT XIF IN XIF OUT XPIC CTRL TX RX XPIC RESET PWR(green) SELV ODU(red) MD/CBL(red) PWR ODU MD/ CBL SELV XPIC CTRL XIF OUT XIF IN PULL PWR PWR Caution: Do not apply to the equipment a voltage that varies sharply. The equipment operation may be impaired.
OPERATING EQUIPMENT ROI-S05749 Interface Signals (MODEM) IF IN/OUT (TNC Female) TX Frequency: 340 MHz RX Frequency: 140 MHz Power supply: −48 V Impedance: 50 ohms Connecting IF Cable length: 5D-FB: less than 150 m 8D-FB: less than 300 m 10D-FB: less than 350 m G (Screw): Ground terminal (5 mm square cable (more than 2.5 mm diameter cable) (AWG#10) is recommended to apply for the frame ground. The proper press fix terminal tool shall be used.
OPERATING EQUIPMENT ROI-S05749 Indicators (MODEM) LED PWR Indication Remarks The PWR switch of the MODEM is turned on. DC power is supplied to the ODU also. Transmit RF power of the ODU decreased approx. −3 dB from preadjusted ATPC minimum (MIN) level in provisioning. Check Metering using LCT for local and/or opposite site in Maintenance menu Receiver input level of the ODU falls below squelch level. APC loop of local oscillator in ODU is unlocked. ODU IF signal from the MODEM to ODU is lost.
OPERATING EQUIPMENT ROI-S05749 User Interface Pin Assignment (MODEM) Terminal Description SELV SELV (DC IN) (Molex M5569-04A1 Connector, 4 Pins) −48 V DC power input Note: Only −48 V (−40.5 to −57 V) is available. Pins 1 and 3 Ground Pins 2 and 4 −48 V IF IN/OUT TNC Jack (Female) * IF signal IN/OUT and PS OUT to the ODU XPIC CTRL (D-Sub Female, 15 pins) Used for interconnection configuration.
OPERATING EQUIPMENT ROI-S05749 2.4 OC-3 OPTICAL INTFC STM-1 (OPT) INTFC STM-1 OUT STM-1 IN ALM STM-1 OUT STM-1 IN ONLINE ALM (red) ONLINE(green) Caution: Do not insert/extract the OC-3 INTFC with the power ON. Turn OFF the PWR switch on the MODEM and remove all cables connected to the OC-3 INTFC before inserting/ extracting theOC-3 INTFC, or that INTFC may be damaged. The OC-3 INTFC provides an optical signal interface only.
OPERATING EQUIPMENT ROI-S05749 Interface Signals (OC-3 INTFC) OC-3 IN/OUT LC Optical OC-3 Input/Output, G.957 Optical Type: G.957 Bit Rate: 155.520 Mbps Level: L-1.1: 0 to −8 dBm (TX)/−10 to −34 dBm (RX) S-1.1: −8 to −15 dBm (TX)/−8 to −28 dBm (RX) Code: NRZ Wavelength: 1310 nm Indicators (OC-3 INTFC) LED Indication Remarks LOSS of OC-3 from MUX is detected. Check MUX and wiring. Frame synchronization of input OC-3 signal from MUX is lost. Check MUX and wiring.
OPERATING EQUIPMENT ROI-S05749 2.5 4P LAN INTFC 4P LAN PORT1 PORT2 ALM LED(red) PORT3 PORT4 ALM 100M PORT 1 PORT 2 100M 100M PORT 3 PORT4 100M 4P LAN INTFC The 4P LAN INTFC (optional) is installed into the Main-INTFC slot (Slot1) in the system configuration and it provides 4 Port LAN Fast Ethernet interfaces. The LAN interface is used 4 Port shared (P1-P4) mode, 2 Port (P1-P2/P3-P4) shared mode or separated (P1/P2/P3/P4) mode.
OPERATING EQUIPMENT ROI-S05749 User Interface Signals (4P LAN INTFC) LAN PORT1 PORT4 (RJ-45) to Input/Output Signal: LAN interface Port 1, Port 2, Port 3 and Port 4. Selectable 2 Mbps to 100 Mbps CH is assigned for LAN. 10/100Base-T(x) Auto-sensing or fixed Flow control: Full duplex or Half duplex Forwarding mode: Store-and-Forwarding Indicators (4P LAN INTFC) LED Indication 100M LAN signal is in 100BASE-TX mode.
OPERATING EQUIPMENT ROI-S05749 2.6 GbE INTFC 1000BASE-SX INDICATOR 1000BASE-T 1000BASE-SX ALM OUT IN PORT The GbE INTFC (optional) provides 1000BASE-SX/1000BASE-T interface. The GbE INTFC is installed into the Main-INTFC slot (Slot1) instead of the OC-3 INTFC in the SONET (128 QAM) system configuration. The signal is connected either SFP (for 1000BASE-SX) or RJ-45 (for 1000MASE-T). These bytes (E1/F1/DCCr) are available between radio links.
OPERATING EQUIPMENT ROI-S05749 User Interface Pin Assignment (GbE INTFC) Terminal Description 1000BASE-SX (SFP Fiber connector) Multimode Fiber/LC Connector IN (Right side) 1000BASE-SX Input OUT (Left side) 1000BASE-SX Output 1000BASE-T (RJ-45, 8 pins) 1000BASE-T Input/Output (MDI/MDI-X) Pin 1 DATA-A+/ DATA-B+ Pin 2 DATA-A−/ DATA-B− Pin 3 DATA-B+/ DATA-A+ Pin 4 DATA-C+/ DATA-D+ Pin 5 DATA-C−/ DATA-D− Pin 6 DATA-B−/ DATA-A+ Pin 7 DATA-D+/ DATA-C+ Pin 8 DATA-D−/ DATA-C− Note: Cable
OPERATING EQUIPMENT ROI-S05749 Indicators (GbE INTFC) LED Indicator Indication Remarks Indicates which Port is applied to the signal interface. When the indicator is flashing slowly, the input signal is off in the corresponding interface port which is set to be used. When the indicator is flashing fast, the input/output signal is on in the corresponding interface port which is set to be used.
OPERATING EQUIPMENT ROI-S05749 2.7 DC-DC CONV DC-DC CONV − 43V STD G − 43V + PWR G OUT ALM ALM OUT FUSE (250V/8AH) SELV PWR LED(green) FUSE (250V/8AH) PULL PWR PWR SELV Note: If the PWR LED is not lit though the PWR switch has set to ON, set the PWR switch to OFF, remove two fuses from the module and check the conduction of them. Caution: Do not apply to the equipment a voltage that varies sharply. The equipment operation may be impaired.
OPERATING EQUIPMENT ROI-S05749 Indicators (DC-DC CONV) LED Indication PWR Remarks The PWR switch of the DC-DC CONV is turned on. Switches (DC-DC CONV) Switch Operating PWR IDU and ODU power on/off switch.
OPERATING EQUIPMENT ROI-S05749 2.8 ODU RF IN/OUT NLite E RX LEV MON IFL FG (FRONT VIEW) (REAR VIEW) FG (Frame Ground) RX LEV MON Antenna Direct Mounting Type IFL (IF IN/ OUT) RF IN/OUT RF IN/OUT (REAR VIEW) Coaxial Cable Type (6/7/8 GHz) (REAR VIEW) WG Type (6/7/8 GHz) The ODU receives 340 MHz IF signal from the IDU and converts it to an RF signal using a local signal generated by a synthesized local oscillator.
OPERATING EQUIPMENT ROI-S05749 Interface Signals (ODU) IFL (N Female) TX Frequency 340 MHz RX Frequency: 140 MHz Power supply: −48 V Impedance: 50 ohms Connecting IF Cable length: 5D-FB: less than 150 m 8D-FB: less than 300 m 10D-FB: less than 350 m FG (Screw) Frame ground, connecting near by ground point. RF IN/OUT RF signal interface. - N female connector for the 6/7/8 GHz ODU with coaxial cable connection.
SYSTEM SETUP ROI-S05749 3. SYSTEM SETUP This section provides system setup to make up proper system configuration. The setup is performed accessing to the LCT program using the PC. For the detail procedure, refer to Section IV Appendix LCT Operation Manual. 3.1 Equipment Setup The equipment setup menu decides system fundamental configuration. Note: For the details of setup item of the LAN PORT USAGE, refer to the LAN INTERFACE (10/100BASE T(X)) Application and Setting in Section IV.
SYSTEM SETUP ROI-S05749 Equipment Setup for SONET User Interface Redundancy Setting INTFC Main (WORK) INTFC SUB (PROT) XPIC Usage APS Function Modulation Scheme Transmission Capacity OC-3 GbE over OC-3 2Port LAN over OC-3 1+0(TERM) 1+1(Hot Standby TERM) 1+1(Twinpath TERM) OC-3(Optical) OC-3(Electrical) GbE over OC-3 2Port LAN over OC-3 Not Used OC-3 (Optical) WS WS/LAN Not Used Used (Main Master) Used (SUB Master) Unavailable Available 128QAM 156MB TX RF Frequency(No.1) [MHz] TX RF Frequency(No.
SYSTEM SETUP ROI-S05749 Equipment Setup for SONET ---ODU FREQ INF--TX Start Frequency(No.1) [MHz] TX Stop Frequency(No.1) [MHz] Frequency Step(No.1) [MHz] Shift Frequency(No.1) [MHz] Upper/Lower(No.1) Sub Band(No.1) TX Start Frequency(No.2) [MHz] TX Stop Frequency(No.2) [MHz] Frequency Step(No.2) [MHz] Shift Frequency(No.2) [MHz] Upper/Lower(No.2) Sub Band(No.
SYSTEM SETUP ROI-S05749 3.2 Provisioning Setup The provisioning setup menu determines system fundamental functions.
SYSTEM SETUP ROI-S05749 LAN Port Setting (For LAN INTFC) INTFC (Main) Setting Switching Function Clock Souce Setting Port1 Port Usage Speed & Duplex Flow Control Collision Report Port2 Port Usage Speed & Duplex LAN Port Setting (For LAN INTFC) Flow Control Collision Report Link Loss Forwarding INTFC (SUB) Setting Switching Function Port1 Port Usage Speed & Duplex Flow Control Collision Report Link Loss Forwarding Internal Clock DMR Internal -> Clock Not Used Used AUTONEG (Auto-MDI/MDX) 10M-Half (MD
SYSTEM SETUP OC-3 Setting ALS TX Power Control Condition for TX/RX SW Condition for APS Relay Setting TCN Threshold(15min) ROI-S05749 MS-AIS Generation ALS Function ALS Interval ATPC Threshold Level(No.1/2) [dBm] Additional ATT(No.1/2 [dB] ATPC Range(MAX)(No.1/2) [dB] ATPC Range(MIN)(No.1/2) [dB] ATPC Power Mode(No.1/2) MTPC TX Power (No.1/2) [dBm] ATPC Threshold Level(No.1/2) [dBm] Additional ATT(No.
SYSTEM SETUP ROI-S05749 3.3 Events and Performance The alarm and status condition are based upon equipment setup and provisioning setup, therefore indication items vary depending on the those setup. The summarized event and performance monitoring that are displayed on the LCT PC are listed in the following table. For the detailed items, refer to Section IV Appendix LCT OPERATION MANUAL.
SYSTEM SETUP ROI-S05749 Event List SONET Alarm Status ODU ODU TX Power TX Input RX Level APC ODU CPU Mute Status LO REF TX SW Status RX SW Status : only XPIC configuration : only 1+1 configuration : only 1+1 configuration MODEM MODEM MODEM Unequipped LOF Route ID High BER Low BER Early Warning MOD DEM Input Voltage Power Supply IF Cable Short Linearizer Status Linearizer Fail Cable EQL XIF XCTRL XPIC Status XREF ATPC Power Mode : only XPIC configuration CTRL CTRL Module MMC Mount APS SW Fail APS Onlin
SYSTEM SETUP ROI-S05749 Event List SONET INTFC (Main) Unequipped Type Mismatch OC-3(1) LOS (MUX) OC-3(1) LOS (DMR) OC-3(1) LOF (MUX) OC-3(1) LOF (DMR) OC-3(1) Output Control OC-3(1) E-BER (MUX) OC-3(1) E-BER (DMR) OC-3(1) SD (MUX) OC-3(1) SD (DMR) OC-3(1) In-Phase OC-3(1) TF INTFC (Main) Unequipped Type Mismatch Module LAN Link Link Loss Forwarding Speed & Duplex LOS (DMR) LOF (DMR) E-BER (DMR) SD DMR Inphase TF GbE INTFC 3-9
SYSTEM SETUP ROI-S05749 Event List SONET INTFC (Sub) INTFC(2) Unequipped OC-3(2) LOS (MUX) OC-3(2) E-BER (MUX) OC-3(2) E-BER (DMR) OC-3(2) SD (MUX) OC-3(2) SD (DMR) OC-3(2) Output Control OC-3(2) In-Phase OC-3(2) LOS (DMR) OC-3(2) LOF (MUX) OC-3(2) LOF (DMR) OC-3(2) TF Unequipped Type Mismatch Module LAN Link LAN Collision Link Loss Forwarding Speed & Duplex TCN-RX LEV TCN-RX LEV-15min TCN-RX LEV-1day 3-10 OPT INTFC applies APS *1 *1 When LAN Port *1 *1
SYSTEM SETUP ROI-S05749 Event List SONET 15min 1 day TCN-OFS-15min Total TCN-UAS-15min Total TCN-ES-15min Total TCN-SES-15min Total TCN-BBE-15min Total TCN-SEP-15min Total TCN-OFS-15min(MUX) TCN-UAS-15min(MUX) TCN-ES-15min(MUX) TCN-SES-15min(MUX) TCN-BBE-15min(MUX) TCN-SEP-15min(MUX) TCN-OFS-15min(MUX)(P) TCN-UAS-15min(MUX)(P) TCN-ES-15min(MUX)(P) TCN-SES-15min(MUX)(P) TCN-BBE-15min(MUX)(P) TCN-SEP-15min(MUX)(P) TCN-OFS-1day Total TCN-UAS-1day Total TCN-ES-1day Total TCN-SES-1day Total TCN-BBE-1day Total
SYSTEM SETUP ROI-S05749 Event List SONET PMON(History) RX Level DMR (W) DMR (W) MUX (W) MUX (W) RX Level(15min) RX Level(1day) (1day) Status OFS SEP BBE ES SES UAS (15min) Status OFS SEP BBE ES SES UAS (day) Status OFS SEP BBE ES SES UAS (15min) Status OFS SEP BBE ES SES RMON(Line)(15min) only for LAN Status RX UNICAST RX BROADCAST RX MULTICAST RX PAUSE RX CEC ERR RX ALIGNMENT ERR RX SYMBOL ERR RX UNDERSIZE RX FRAGMENTS RX Pkts 64 RX Pkts 65 to 127 RX Pkts 128 to 255 RX Pkts 256 to 511 3-12
SYSTEM SETUP ROI-S05749 Event List SONET RX Pkts 512 to 1023 RX Pkts 1024 to 1536 TX JABBERS TX UNICAST TX BROADCAST TX MULTICAST TX PAUSE TX COLLISION Notes : *1 When the LAN/WS INTFC is provided, status of each LAN PORT is displayed as follows. Status of LAN PORT Link Sub PORT1 Sub PORT1 Link Link Collision Normal Normal LLF Normal Normal Speed & Duplex 100M-Full (MDIX) 100M-Full (MDIX) Notes:For the GbE INTFC, there are distinctions for the following functions from the 10BASE-T/100BASE-Tx 1.
SYSTEM SETUP ROI-S05749 3.4 Control The control condition is based upon equipment setup and provisioning setup, therefore control items vary depending on the those setup. The control items that are displayed on the LCT PC are listed in the following table. the control operation can be performed in Maintenance “ON”.
SYSTEM SETUP ROI-S05749 Control List (SONET) Control Maintenance TX SW Manual Control RX SW Manual Control RX SWMaintenance Mode ATPC Manual Control(No.1) ATPC Manual Control(No.2) TX Mute Control(No.1) TX Mute Control(No.2) CW Control(No.1) CW Control(No.2) APS Manual Control (Auto/Working/Protection) APS Maintenance Mode IF Loopback(No.1) IF Loopback(No.2) Main Loopback (Near End) Main Loopback (Near End) INTFC (1) Main Loopback (Near End) INTFC (2) Main Loopback (Far End) Linearizer Control(No.
SYSTEM SETUP ROI-S05749 3.5 Setup Description The following describes to select suitable functions for the system operation by the provisioning setup. 3.5.1 Automatic Laser Shutdown Control (OPT INTFC) (SONET) The OC-3 INTFC (only for OPT) is provided with the Automatic Laser Shutdown (ALS) function that can be enabled or disabled.
SYSTEM SETUP ROI-S05749 (c) Manual Restart (90 sec.) Control Upon receiving a command signal for manual restart for test from the LCT or the PNMT while the optical input signal to the RX 2 is off, the IDU emits the laser signal from the TX 2 to the RX 1 for 90 ±10 sec. This would then cause the laser output of TX1 to turn on. If, at this time, the fault at point A has been recovered, the ALS function will be released and the operation will return to normal (if not it returns to automatic condition).
SYSTEM SETUP ROI-S05749 3.5.2 Automatic Protection Switching (APS) (OPT INTFC Optional APS Configuration) (SONET) (a) Line Protection The Automatic Protection Switching (APS) provides for unidirectional line protection against optical cable interface failures. It is performed by detected alarm condition or remote control signal.
SYSTEM SETUP ROI-S05749 SW CTRL ASSOCIATED EQUIPMENT NLite E Received OPT failure (1) (Work) WORKING WORKING (Prot) PROTECTION PROTECTION OC-3 (OPT) INTFC (No.1) OC-3 (OPT) INTFC (No.2) WORKING WORKING (Work) (2) OC-3 (OPT) INTFC (No.1) PROTECTION PROTECTION (Prot) OC-3 (OPT) INTFC (No.2) SW CTRL ASSOCIATED EQUIPMENT (1) (Work) Received OPT failure WORKING WORKING NLite E OC-3 (OPT) INTFC (No.1) (Prot) PROTECTION PROTECTION OC-3 (OPT) INTFC (No.
SYSTEM SETUP ROI-S05749 (b) APS Function Setup The APS switchover is performed with the following order of priority of two (2) modes. (1) When “APS Condition-SF” is lower priority (default). • UNEQUIP > LKI*1 > FSW > SF > SD*2 > MSW (2) When “APS Condition-SF” is higher priority. • UNEQUIP > LKI*1 > SF(P) > FSW > SF(W) > SD*2 > MSW Notes: *1 Excluding when the Lock in Usage is set Not Used. *2: Excluding when the APS Condition-SD(B1) is set to Excluded SD. UNEQUIP:Unequipped redundant OC-3 INTFC (OPT).
SYSTEM SETUP ROI-S05749 LCT MENU Alarm/Status Equipment Setup Inventory AUX I/O Maintenance Provisioning BER Threshold Setting SC Assignment OC-3 Setting TX Power Control Condition for TX/RX SW Condition for APS Relay Setting TCN Threshold (15min) TCN Threshold (1day) PMON Select Others Metering PMON(Current) PMON(History) ---Condition for APS--APS Maintenance Mode Manual APS Condition-SF(PROT) Priority High APS Condition-SD(B1) Included SD Lock in Usage Not Used Lock in Detect Count [times] Lock
SYSTEM SETUP ROI-S05749 • APS Condition-SD(B1) This is a setup that it includes the SD or excludes SD for the switchover control condition. When including it, the switchover is performed when SD reaches the threshold value which is set in BER Threshold/SD (MUX) in provisioning.
SYSTEM SETUP ROI-S05749 3.5.3 Automatic Transmitter Power Control The automatic transmit power control (ATPC) function automatically varies the TX output power according to path conditions. In the SHF and EHF band, fading exerts heavy influences on propagation, causing the receive signal level at the opposite station to vary. The ATPC function operates by controlling the transmit output power of the opposite station according to the variation of the received signal level at the local station.
SYSTEM SETUP ROI-S05749 TRANSMITTING STATION RECEIVING STATION MODEM TX POWER CONT REMOTE MODEM RX RX IN LEV CTRL CTRL REMOTE ATPC CTRL ATPC CTRL MODEM RX TX MODEM Fig. 3-4 ATPC, Functional BLock Diagram Example of ATPC setting. Where ATPC MAXIMUM PWR of ATPC Range is set to 0 dB, ATPC MINIMUM PWR is set to -10 dB and RX Threshold to -55 dBm. In this case, if RX level is lower than -55 dBm, monitor/control is performed with the interval of 8 msec.
SYSTEM SETUP ROI-S05749 Using MTPC-ATPC The ATPC Control System of the PASOLINK transmits the information on the receiving level to the opposite station and controls the transmission level of its local station in accordance with the receiving level of the opposite station. Transmission level control can be used not only for setting the same operation (ATPC-ATPC) between local station and opposite station but also for operation in combination of stations with different operations (MTPC-ATPC, ATPC-MTPC).
SYSTEM SETUP ROI-S05749 (MTPC) MASTER STATION (ATPC) SUBSTATION 1 (ATPC) SUBSTATION 2 (B) (A) (C) (ATPC) SUBSTATION 5 (ATPC) SUBSTATION 3 (ATPC) SUBSTATION 4 : Diffraction to other route. (A),(B) (C) : RX received level down. A constant transmit output power in both MTPC and ATPC is maintained using the ALC function which is provided in the RF CKT module. The ALC circuit detect the transmit output power using a diode to obtain a DC voltage proportional to the transmit power.
SYSTEM SETUP ROI-S05749 3.5.4Loopback Control The loopback function is provided for checking the system quality during maintenance and/or to quickly isolate a fault location on the SONET configuration. The control is performed by the LCT, the PNMT or the PNMS. Provided here is the control of the: • Near-End loopback is performed at the OC-3 INTFC module. • Far-End loopback is performed at the OC-3 INTFC module. • IF loopback (IF-LB) is performed at the MODEM module ((c) in Fig. 3-5) for IF signal.
SYSTEM SETUP ROI-S05749 LAN port to alert the equipment connected with the LAN port when the system has been disconnected by the fault in the radio section. The other is to transmit the information for cutting the link interconnected with the LAN port in the opposite station when the link between the LAN port and equipment is faulty. This function can be selected by setting “Provisioning” on LCT to “Enable” or “Disable”. AUTO: Output Stop Radio Fault FAULT HUB LAN LAN HUB 3.5.
SYSTEM SETUP ROI-S05749 For example, at the station A, when the NLite E equipment detects the OC3 input Loss Of Signal (LOS) and/or Loss Of Frame (LOF), the information is transmitted to the station B by using RFCOH. When the station B detects the information, NLite E equipment stops the OC-3 output signal. Similarly, it is the same even if a receiving input level down or loss of radio frame (LOF) appear in station B.
SYSTEM SETUP ROI-S05749 3.5.7 Cross Polarization Interference Canceller (XPIC) Reset Control For the Cross Polarization Interference Canceller (XPIC) to function properly, signals for both Main Master and Sub Master sides must be received normally. For this reason, when either signal is in abnormal condition, the XPIC RESET function provides a way for turning off the XPIC operation. Local/Remote XPIC reset can be controlled separately to the Main Master and Sub Master.
SYSTEM SETUP ROI-S05749 3.5.8 Network Management (Optional) The Network Management System (NMS) configuration is shown in Fig. 3-7. The PASOLINK network management system (PNMS) is connected to the NMS (LAN) connector of the IDU located at the designated maintenance center while the PASOLINK network management terminal (PNMT) is connected to the LCT USB connector on the IDU of remote stations.
SYSTEM SETUP ROI-S05749 3.5.9 Functionality Classification The functionality of the NLite E is defined by optional system parameters, interface card and transmission capacities as listed in the following categories. The functionality is found in the Software Key in the LCT Inventory menu. Functionality Classification of the NLite E 1 2 3 4 Capacity and Redundancy Bit Rate LAN Interface XPIC Functionary 1+0 System 1+1 System Fixed Available Available 1. 10 MB 1.
SYSTEM SETUP ROI-S05749 3.6 Protection Switching Protection switching is provided in the 1+1 Twin-path and the HS systems. 3.6.1 1 + 1 Twin-path System Protection switching in this system is performed by a hitless switch (HL SW) on the ( )INTFC module of the IDU at the receiving end. When both the No. 1 and No. 2 channels are in normal operating condition, the OC-3 data streams from the associated MUX equipment are sent to the receiving end through the No. 1 and No. 2 channels.
SYSTEM SETUP ROI-S05749 When the modulator alarm is detected in the MODEM or when the TX IF input alarm, TX power alarm or APC alarm is detected in the ODU, the alarm signal is sent to the switch control logic circuit on the CTRL module. The switch control logic circuit produces a TX switch control signal for selecting the ODU that is in the normal condition.
SYSTEM SETUP ROI-S05749 (b) RX Switch RX switching in 1+1 Twin-path/HS system is performed by the HL SW on the ( ) INTFC module. Two types of RX switch controls are provided: automatic switching that is initiated by the quality deterioration of the received signal and manual switching that is initiated by the operator using the LCT. The switching mode and switching priority for automatic and manual switching are identical to those of TX switching.
SYSTEM SETUP ROI-S05749 • RX SW Condition-Early Warning 1. Included Early Warning, this switch over the RX SW at less than 1E-9. 2. Excluded Early Warning, this switch over the RX SW at Low BER setting values 1E-6, 1E-7, 1E-8 or 1E-9. (default value is 1E-7) • RX Switching Condition Cross Reset (only XPIC 1+1 configuration): 1. Included Cross Reset, this switch over the RX SW when XPIC reset control is acted. 2. Excluded Cross Reset, this does not switch over the RX SW though XPIC reset control is acted.
SAFETY INFORMATION ROI-S05747-052E August, 2007 SAFETY INFORMATION This safety instruction is prepared to protect accident resulting personal injury or death and also physical damage of the equipment during maintenance or installation. To avoid hazardous conditions, read this Instruction Manual thoroughly before equipment operation.
SAFETY INFORMATION ROI-S05747 ! -48V OUTPUT Power down IDU before disconnection or connection of cable. ! WARNING Turn off power of IDU before disconnecting cable. ! Do not disconnect I/F cable between the IDU and the ODU in operation condition, to avoid damaging the IDU and the ODU. The −48 V DC power is superimposed on the center conductor of the I/F cable between the IDU and the ODU.
WARNING ROI-S05747 WARNING WARNING The –48 V DC power is superimposed on the center conductor of the coaxial cable between the IDU and the ODU. Connecting a test set equipment directly to this terminal may damage it and touching the coaxial cable core may cause electrical shock. WARNING Do not touch the I/F cable jack core before turning off the power switch. If touching the coaxial cable core may cause electrical shock.
CAUTION ROI-S05747 CAUTION CAUTION While the power supply is ON, do not connect/disconnect the power supply connector. Otherwise, the DC-DC CONV may break down. CAUTION Locate the ODU within the area protected by lightning rod. To avoid surge currents caused by lightning circulating in the equipment earth system, connect the equipment earth system (frame ground) to ground of the lightning rod at ground level.
NOTICE (PLACING) ROI-S05747 NOTICE (PLACING) 1. When the ODU is installed in the indoor, as the ODU generates Non-ionizing radiation and it may cause health effect, then, it is required to take adequate measures. 2. Do not block the vents of the equipment. It may cause break down due to heating up of inner equipment in stuffy condition. Ensure to follow the set up and usage rules as follows. Do not set up the equipment on the carpet, heating floor or bare concrete.
NOTICE (PLACING) ROI-S05747 (b) Environmental Temperature Impact for the Equipment In the airtight room, it may be caused rising in temperature with the heat generation of the equipment. Furnish an air-conditioner for industrial use in accordance with the situation. Do not apply air directly from the air-conditioner to the equipment. When the equipment is located in face of the air from the air-conditioner, it could be condensed into dew by temperature variation. (c) 6.
ROI-S05755-054E April, 2007 ABBREVIATIONS ABBREVIATIONS The following abbreviations are used in the manual for the NLite E equipment.
ABBREVIATIONS ROI-S05755 ABBREVIATION DESCRIPTION CONV Converter CPU Central Processing Unit CTRL Control CW Carrier Wave D DADE Differential Absolute Delay Equalizer DC Direct Current DCCr Data Communication Channel in RSOH DCK Drop Clock DDT Drop Data DEM Demodulator DFP Drop Frame Pulse DMR Digital Microwave Radio DSC Digital Service Channel E Electrical E/O Electrical/Optical E-BER Excessive-Bit Error Rate EMC Electro Magnetic Compatibility EOW Engineering Orderwir
ROI-S05755 ABBREVIATIONS ABBREVIATION DESCRIPTION F FAS Frame Alignment Signal FEC Forward Error Correction FG Frame Ground FIL Filter FPGA Field Programable Gate Array FREQ Frequency F/W Firmware G G Ground GND Ground H HD Hard Disk HK House Keeping ICK Insert Clock ID Identification IDT Insert Data IDU Indoor Unit IE Internet Explorer IEEE Institute of Electrical and Electronic Engineers IF Intermediate Frequency I/F Inter Facility IFL Inter Facility Link IN In
ABBREVIATIONS ROI-S05755 ABBREVIATION DESCRIPTION L LAN Local Area Network LB Loop Back LCD Liquid Crystal Display LCT Local Craft Terminal LED Light Emitting Diode LLF Link Loss Forwarding LEV Level LO Local LOF Loss of Frame LOS Loss of Signal M -4- MAC Media Access Control MAINT Maintenance MD Modulator Demodulator MDI Media Dependent Interface MDIX Media Dependent Interface with Crossover MFAS Multi Frame Alignment Signal MIX Mixer MII Media Independent Interface
ROI-S05755 ABBREVIATIONS ABBREVIATION DESCRIPTION N NC Normal Closed NE Network Element NMS Network Management System NO Normal Open NORM Normal NRZ Nonreturn to Zero O O Optical O/E Optical/Electrical ODU Outdoor Unit OFS Out of Frame Second OH Overhead OMT Orthogonal Mode Transducer OPT Optical OS Operating System OUT Output OW Orderwire P Protection PC Personal Computer PDH Plesiochronous Digital Hierarchy PH Phase PKG Package PM PASOLINK Management PMON P
ABBREVIATIONS ROI-S05755 ABBREVIATION DESCRIPTION Q QAM Quadrature Amplitude Modulation QPSK Quadrature Phase Shift Keying R RAM Random Access Memory REC Rectifier LO REF Local Reference Frequency RF Radio Frequency RFCOH Radio Frame Complementary Overhead RL Relay RMON Remote Network Monitoring ROM Read Only Memory RS Reed Solomon RSOH Regenerator Section Overhead RST Regenerator Section Termination RSL Received Signal Level RX Receive SC Service Channel SD Signal Degra
ROI-S05755 ABBREVIATIONS ABBREVIATION DESCRIPTION SYS System TCN Threshold Crossing Notification TRP Transmitter-Receiver Equipment TX Transmit T U UAE Unavailable Event UAS Unavailable Second URL Uniform Resource Locator USB Universal Serial Bus V VF Voice Frequency V/H Vertical/Horizontal VOL Volume Vo-p Volt zero (0) to Peak W W Working Web World Wide Web WG Waveguide X XC Cross Connect XIF IFof Cross Polarization XPIC Cross Polarization Interference Canceller XPD
ABBREVIATIONS ROI-S05755 (This page is intentionally left blank.
APPENDIX FCC STATEMENT INFORMATION ..................................
1.0 FCC INFORMATION The device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference. (2) This device must accept any interference received. This device must be professionally installed. MADE IN JAPAN The NLite E 5.8 GHz radios will be used for fixed Point to Point applications. The NLite L radio utilizes a parabolic antenna that requires professional installers for path alignment.